2024 Dec 16
1
NUT on FBSD 14-2 fails to shut down UPS - select with socket: Invalid argument
...tify about state 4: no notification tech defined,
will not spam more about it
Driver failed to start (exit status=1)
Network UPS Tools - Generic SNMP UPS driver 1.31 (2.8.2)
select with socket: Invalid argument
Detected Smart-UPS 3000 RM on host 192.5.37.79 (mib: apcc 1.60)
Initiating UPS shutdown
[upsbottom] nut_snmp_set: can't set .1.3.6.1.4.1.318.1.1.1.6.1.1.0: Timeout
Shutdown failed!
upsnotify: failed to notify about state 4: no notification tech defined,
will not spam more about it
Driver failed to start (exit status=1)
: || nomad at castle ~ [51] ; pkg info nut
nut-2.8.2
Name : nu...
2024 Dec 17
1
NUT on FBSD 14-2 fails to shut down UPS - select with socket: Invalid argument
...tech defined,
> will not spam more about it
> Driver failed to start (exit status=1)
> Network UPS Tools - Generic SNMP UPS driver 1.31 (2.8.2)
> select with socket: Invalid argument
> Detected Smart-UPS 3000 RM on host 192.5.37.79 (mib: apcc 1.60)
> Initiating UPS shutdown
> [upsbottom] nut_snmp_set: can't set .1.3.6.1.4.1.318.1.1.1.6.1.1.0: Timeout
> Shutdown failed!
> upsnotify: failed to notify about state 4: no notification tech defined,
> will not spam more about it
> Driver failed to start (exit status=1)
>
> : || nomad at castle ~ [51] ; pkg info nut...