search for: upsbasiccontrolconservebattery

Displaying 6 results from an estimated 6 matches for "upsbasiccontrolconservebattery".

2014 Feb 25
1
snmp-ups shutdowns
...1.6.2.2.0 integer 3" This OID is curiously commented out in drivers/apc-mib.c, and has been since the beginning of our revision control history. I don't see why we couldn't add it back in as an instant command. I wonder if there was some confusion with .1.3.6.1.4.1.318.1.1.1.6.1.1.0 (upsBasicControlConserveBattery), which is currently mapped to "shutdown.return" >>> # turn off UP gracefully (APC) (stays off even if power is restored) >>> #UPS_OID=".1.3.6.1.4.1.318.1.1.1.6.2.1.0 integer 3" This should map to the "shutdown.stayoff" instant command. -- Charles...
2014 Feb 27
2
snmp-ups shutdowns
...1.6.2.2.0 integer 3" This OID is curiously commented out in drivers/apc-mib.c, and has been since the beginning of our revision control history. I don't see why we couldn't add it back in as an instant command. I wonder if there was some confusion with .1.3.6.1.4.1.318.1.1.1.6.1.1.0 (upsBasicControlConserveBattery), which is currently mapped to "shutdown.return" >>> # turn off UP gracefully (APC) (stays off even if power is restored) >>> #UPS_OID=".1.3.6.1.4.1.318.1.1.1.6.2.1.0 integer 3" This should map to the "shutdown.stayoff" instant command. -- Charles...
2014 Feb 19
0
snmp-ups shutdowns
On Wed, 19 Feb 2014, Jim Klimov wrote: > On 2014-02-19 03:04, Tim Rice wrote: > > Now here are the OIDs (pick one) to actually turn the UPS off > > after the shutdown delay. > > > > # reboot gracefully (APC) (stays off until utility power is restored) > > UPS_OID=".1.3.6.1.4.1.318.1.1.1.6.2.2.0 integer 3" > > # turn off UP gracefully (APC) (stays
2014 Feb 19
2
snmp-ups shutdowns
On 2014-02-19 03:04, Tim Rice wrote: > If you've got a AP9630 card these notes may be useful. > > # APC ap9630 notes: > # Use firmware 6.0.6 or later if you want SNMPv3 > # Configuration->Shutdown > # In "Start of Shutdown" section, set "Low Battery Duration" and > # "Shutdown Delay" to get enough grace time for the ESXI shutdown > #
2014 Feb 27
0
snmp-ups shutdowns
On Feb 27, 2014, at 7:07 AM, jimklimov at cos.ru wrote: > This apparently implies that, unlike some docs say, the snmp-ups driver can send the shutdown signals (is not crippled by design)? ;) We're working on it: http://buildbot.networkupstools.org/~buildbot/cayman/docs/latest/docs/man/snmp-ups.html#_shutdown A quick check says that the implementation has been there since v2.6.4, and
2014 Feb 27
3
snmp-ups shutdowns
...nks :) > > This OID is curiously commented out in drivers/apc-mib.c, and has been since the beginning of our revision control history. I don't see why we couldn't add it back in as an instant command. > > I wonder if there was some confusion with .1.3.6.1.4.1.318.1.1.1.6.1.1.0 (upsBasicControlConserveBattery), which is currently mapped to "shutdown.return" > >>>> # turn off UP gracefully (APC) (stays off even if power is restored) >>>> #UPS_OID=".1.3.6.1.4.1.318.1.1.1.6.2.1.0 integer 3" > > This should map to the "shutdown.stayoff" instant...