2014 Jan 21
2
Shutdown when both (all) UPS on battery / low battery
On Jan 21, 2014, at 8:05 AM, Rafa? Oleszek wrote: > MONITOR UPS_251 at localhost 2 monmaster password master > MONITOR UPS_252 at localhost 2 monmaster password master I think the "2"s here should be "1". "powervalue is an integer representing the number of power supplies that the UPS feeds *on this system*." So if UPS_251 is connected to one power supply on the system running upsmon, and U...
2014 Jan 21
0
Shutdown when both (all) UPS on battery / low battery
I tried all options: 1,2 and in MINSUPPLIES: 1,2,3,4 still didn't work. UPS_251 and UPS_252 feeds all environment and it's not feed directly one server, but many of them. > On Jan 21, 2014, at 8:05 AM, Rafa? Oleszek wrote: > >> MONITOR UPS_251 at localhost 2 monmaster password master >> MONITOR UPS_252 at localhost 2 monmaster password master > > I think the...
2014 Jan 23
2
Shutdown when both (all) UPS on battery / low battery
...password slave MINSUPPLIES 1 With only one dummy-ups set to "OB LB", upsmon kept polling. When both were set to "OB LB", it tried to shut down the system. That was with NUT 2.7.1 - I don't remember any bugs in this area, but it would be in the changelog. > UPS_251 and UPS_252 feeds all environment and it's not feed directly one > server, but many of them. Right, and only the master is responsible for shutting down the UPS itself. Or do you mean that not all of the servers are connected to both UPSes? -- Charles Lepple clepple at gmail
2014 Jan 23
0
Shutdown when both (all) UPS on battery / low battery
...gt; With only one dummy-ups set to "OB LB", upsmon kept polling. When both > were set to "OB LB", it tried to shut down the system. > > That was with NUT 2.7.1 - I don't remember any bugs in this area, but it > would be in the changelog. > >> UPS_251 and UPS_252 feeds all environment and it's not feed directly one >> server, but many of them. > > Right, and only the master is responsible for shutting down the UPS > itself. Or do you mean that not all of the servers are connected to both > UPSes? > > -- > Charles Lepple > c...
2014 Jan 21
0
Shutdown when both (all) UPS on battery / low battery
...Thank you for your reply. I tested configuration on live environment and on dummy-ups. I also built the newest NUT version, tested on dummy-ups and it didn't work with my config. My config files: upsmon.conf: RUN_AS_USER root MONITOR UPS_251 at localhost 2 monmaster password master MONITOR UPS_252 at localhost 2 monmaster password master MINSUPPLIES 2 SHUTDOWNCMD "/etc/ups/test" NOTIFYCMD /usr/sbin/upssched POLLFREQ 5 POLLFREQALERT 5 HOSTSYNC 15 DEADTIME 30 POWERDOWNFLAG /etc/killpower NOTIFYFLAG ONLINE SYSLOG+WALL+EXEC NOTIFYFLAG ONBATT SYSLOG+WALL+EXEC NOTIFYFLAG LOWB...
2014 Jan 21
3
Shutdown when both (all) UPS on battery / low battery
On Jan 21, 2014, at 3:16 AM, Rafa? Oleszek wrote: > I would like to mention that MINSUPPLIES manipulation doesn't work. My nut version is : 2.2.2-4 (RHEL 5) What do your configuration files look like? Setting MINSUPPLIES to 2 should work. You can run upsmon with a debug level of 3 or greater, and it will print the current and minimum "power value", which is what determines