2015 Sep 10
2
blazer_usb Shutdown
Hi,
I am using a ALLNET 91500 UPS with blazer_usb driver
  /usr/lib/ups/driver/blazer_usb -a ups91500 -L
Network UPS Tools - Megatec/Q1 protocol USB driver 0.10 (2.7.1)
I have this settings:
upsc ups91500 at localhost
battery.charge: 100
battery.runtime: 12000
battery.voltage: 27.50
battery.voltage.high: 27.3
battery.voltage.low: 18.0
device.type: ups
driver.flag.novendor: enabled
driver.name: bl...
2015 Sep 10
0
blazer_usb Shutdown
(please use reply-all - this list does not alter reply-to headers)
On Sep 10, 2015, at 6:23 AM, Thomas Aichinger <taich at qpl.at> wrote:
> 
> Hi,
> 
> I am using a ALLNET 91500 UPS with blazer_usb driver
> 
> /usr/lib/ups/driver/blazer_usb -a ups91500 -L
> Network UPS Tools - Megatec/Q1 protocol USB driver 0.10 (2.7.1)
[...]
> I set delay.shutdown to 600 sec but UPS turns power off after about 120 sec.
The shutdown delay gets discretized into a few different values, and is then sent to the UPS:
http://www.networkupstools.org/protocols/me...