Displaying 3 results from an estimated 3 matches for "timerexpir".
Did you mean:
  timerexpired
  
2014 May 29
0
Resetting replace battery status on Pulsar 1500
...22.677037     hid_lookup_path: ffff0018 -> LCMSystem
  22.677039     hid_lookup_path: ffff001a -> LCMAlarm
  22.677045     hid_lookup_path: 00ff0001 -> not found in lookup table
  22.677049     hid_lookup_path: 00840002 -> PresentStatus
  22.677052     hid_lookup_path: ffff0093 -> TimerExpired
  22.677055     Path: UPS.LCMSystem.LCMAlarm.[1].PresentStatus.TimerExpired, Type: Feature, ReportID: 0x5d, Offset: 0, Size: 8, Value: 1
This seems to be setting the RB flag:
  65.871141     Path: UPS.LCMSystem.LCMAlarm.[2].PresentStatus.TimerExpired, Type: Feature, ReportID: 0x5d, Offset: 8, S...
2014 May 29
2
Resetting replace battery status on Pulsar 1500
On 28 May 2014, at 21:59, Charles Lepple <clepple at gmail.com> wrote:
>> What would log it?
> 
> The driver.
OK.
>> I could try running the driver with debugging and see if that shows anything of interest.
> 
> That should help. Unfortunately for non-debug operation, it appears that most of the usbhid-ups instcmd messages are buried at debug level 3 or 5. That
2018 Jan 16
2
Eaton 5PX after battery replacement still says "replace battery" in NUT
...e: 2.592e+06
   5.572599	Path: UPS.LCMSystem.LCMAlarm.[1].LCMAlarmID, Type: Feature, ReportID: 0x50, Offset: 0, Size: 8, Value: 1
   5.606524	Path: UPS.LCMSystem.LCMAlarm.[1].Mode, Type: Feature, ReportID: 0x57, Offset: 0, Size: 8, Value: 0
   5.643485	Path: UPS.LCMSystem.LCMAlarm.[1].PresentStatus.TimerExpired, Type: Feature, ReportID: 0x5d, Offset: 0, Size: 8, Value: 1
   5.643505	Path: UPS.LCMSystem.LCMAlarm.[1].PresentStatus.TimerExpired, Type: Input, ReportID: 0x5d, Offset: 0, Size: 8, Value: 1
   5.681732	Path: UPS.LCMSystem.LCMAlarm.[1].Timer, Type: Feature, ReportID: 0x5a, Offset: 0, Size: 32, V...