search for: t1500

Displaying 9 results from an estimated 9 matches for "t1500".

Did you mean: 1500
2010 Sep 06
2
HP T1500 INTL
I have a HP T1500 INTL that isn't picked up under 2.4.3. I added the USB device ID to tripplite-hid.c like: /* HP T1500 INTL */ { USB_DEVICE(HP_VENDORID, 0x1f09), battery_scale_1dot0 }, and it seems to work just fine: # upsc UPS1 at localhost battery.charge: 100 battery.charge.low: 10 battery....
2019 Feb 12
4
Monitor Eaton 93PS UPS
I also operate an HP T1500 G3 which it's an Eaton made UPS. Connected on usb i get frequent communication errors and data aquisition stopped. Mine has a serial connection, also. Operating via serial has no trouble. Maybe it's something related to usb setting in bios, i.e. Legacy mode, speed setting, etc. However on s...
2005 Dec 05
3
Powerware 5125 works ?
Hi there. At the moment I'm trying to get my HP T1500 XR (Powerware 5125) UPS to work with NUT. NUT registers that the UPS is on battery/online, but I just cant get the program to shut down the computer I'm using the original cable (thus I didn't enter anything in the ups.conf file) If I remove the cable and run the daemon/program the compute...
2006 Feb 25
3
Compaq R1500 UPS and Linux
-----BEGIN PGP SIGNED MESSAGE----- Hash: SHA1 - -----BEGIN PGP SIGNED MESSAGE----- Hash: SHA1 Hi! Has anyone gotten it working at all with Linux :) I picked one up for thiry bucks and would love to monitor it! Liz - -----BEGIN PGP SIGNATURE----- Version: GnuPG v1.4.1 (Darwin) iD8DBQFD/5fEIACpLcG4dhwRAmeCAJ9+8FGXqKoOlZdkw/KFXb9n0PEemwCdHaoD NVnv7JjmBAjNsExK6WzAdnA= =pcPX - -----END PGP
2018 Jan 23
0
HPE Power Protector
Hello, Can NUT-CLIENT communicate with a HPE Power Protector server ? The HP T1500 G3 INTL it?s connected to Power Protector server running Windows Server 2012. The Nut-Client it?s installed on a Power Mac G5 running Ubuntu 16.04 / Linux 4.4.0 Thank you ! Alex -------------- next part -------------- An HTML attachment was scrubbed... URL: <http://lists.alioth.debian.org/piper...
2019 Feb 12
0
Monitor Eaton 93PS UPS
Zitat von nicolae788 <nicolae788 at gmail.com>: > I also operate an HP T1500 G3 which it's an Eaton made UPS. Connected on > usb i get frequent communication errors and data aquisition stopped. Mine > has a serial connection, also. Operating via serial has no trouble. Maybe > it's something related to usb setting in bios, i.e. Legacy mode, speed > settin...
2019 Feb 12
0
Monitor Eaton 93PS UPS
On February 12, 2019 9:37:17 AM UTC, nicolae788 <nicolae788 at gmail.com> wrote: >I also operate an HP T1500 G3 which it's an Eaton made UPS. Connected >on >usb i get frequent communication errors and data aquisition stopped. >Mine >has a serial connection, also. Operating via serial has no trouble. >Maybe >it's something related to usb setting in bios, i.e. Legacy mode, speed &g...
2019 Feb 11
2
Monitor Eaton 93PS UPS
Hello, we try to use Network UPS tools to monitor a network connected Eaton 93PS UPS. It basically works but we get frequent "Data is stale - check driver" warnings with a "data is no longer stale" shortly after in the log. We tried both snmp-ups and netxml-ups driver and both raise the same error. If have captured the communication between nut and UPS but all
2018 Dec 03
2
MGE EllipseMAX 1500 shuts down after a few hours
I have taken out the batteries and measured them with a multimeter. They put out 13V (they are rated 12V 9Ah). Putting them back again and disconnecting the UPS from the mains it is kept on, powering all the connected devices. The shutdowns only occur when the UPS is being monitored. Are you sure it's a battery problem? Do UPS perform further tests when they are being polled for data?