search for: sc620i

Displaying 2 results from an estimated 2 matches for "sc620i".

Did you mean: sc620
2013 Jan 13
0
APC UPS: replacement battery always triggers shutdown
...token load while UPS is grounded on a surge protector) but it did not help. >> >> Perhaps I missed something running this procedure; if anyone has suggestions for solving this they'd be greatly appreciated. > >I've been in the same situation after replacing the battery in SC620I model. > >Then I found http://old.nabble.com/SmartUPS-and-new-battery-td20678966.html >and followed the procedure: > >1. Shutdown the apcupsd daemon. >2. Run apctest >3. Choose option 6 to enter terminal mode >4. Enter Y (UPS should respond SM) >5. Enter 1 (one, not el; w...
2012 Nov 11
1
APC UPS: replacement battery always triggers shutdown
?I've been using nut on an APC Back-UPS 750 for several years with no problem, seeing the walled "UPS on battery power" messages during short 1-2 minute outages. This is connected with the original USB cable that came with the unit. After replacing the battery recently, nut always triggers a shutdown when AC power is cut off, even if only for 1 minute. I see that the data fields