2013 Jan 13
0
APC UPS: replacement battery always triggers shutdown
...token load while UPS is grounded on a surge protector) but it did not help.
>>
>> Perhaps I missed something running this procedure; if anyone has suggestions for solving this they'd be greatly appreciated.
>
>I've been in the same situation after replacing the battery in SC620I model.
>
>Then I found http://old.nabble.com/SmartUPS-and-new-battery-td20678966.html
>and followed the procedure:
>
>1. Shutdown the apcupsd daemon.
>2. Run apctest
>3. Choose option 6 to enter terminal mode
>4. Enter Y (UPS should respond SM)
>5. Enter 1 (one, not el; w...
2012 Nov 11
1
APC UPS: replacement battery always triggers shutdown
?I've been using nut on an APC Back-UPS 750 for several years with no problem, seeing the walled "UPS on battery power"
messages during short 1-2 minute outages. This is connected with the original USB cable that came with the unit.
After replacing the battery recently, nut always triggers a shutdown when AC power is cut off, even if only for 1 minute.
I see that the data fields