Displaying 2 results from an estimated 2 matches for "s10r000".
Did you mean:
  s100000
  
2015 Sep 10
0
blazer_usb Shutdown
...ich should also be available in v2.7.1) but it looks like you can manually test the shutdown with the following command (after everything else has been stopped; perhaps send this from another system?):
/usr/lib/ups/driver/blazer_usb -a ups91500 -DDD -k
You should see a debug line with "send: S10R000".
Although it appears that a 600-second delay is within spec, you could try 540 to see if it makes a difference. It is also possible that the UPS is hardwired for a two-minute delay.
> I also tried to raise FINALDELAY to 600 and changed SHUTDOWNCMD to shutdown -h +10
These don't affe...
2015 Sep 10
2
blazer_usb Shutdown
Hi,
I am using a ALLNET 91500 UPS with blazer_usb driver
  /usr/lib/ups/driver/blazer_usb -a ups91500 -L
Network UPS Tools - Megatec/Q1 protocol USB driver 0.10 (2.7.1)
I have this settings:
upsc ups91500 at localhost
battery.charge: 100
battery.runtime: 12000
battery.voltage: 27.50
battery.voltage.high: 27.3
battery.voltage.low: 18.0
device.type: ups
driver.flag.novendor: enabled
driver.name: