Displaying 2 results from an estimated 2 matches for "s02r0003".
Did you mean:
s02r0000
2018 Mar 02
1
Work around for power recycling after shutdown.return - TSSHARA UPS - nutdrv_qx driver - megatec protocol
...5' to the device),
- 'offdelay=120', 'ondelay=0' (the driver will send 'S02' to the device),
- 'offdelay=30', 'ondelay=180' (the driver will send 'S.5R0003' to the device),
- 'offdelay=120', 'ondelay=180' (the driver will send 'S02R0003' to the device),
- 'offdelay=30', 'stayoff' flag (the driver will send 'S.5R0000' to the device),
- 'offdelay=120', 'stayoff' flag (the driver will send 'S02R0000' to
the device).
>
> Jairo
2018 Feb 28
2
Work around for power recycling after shutdown.return - TSSHARA UPS - nutdrv_qx driver - megatec protocol
Answers bellow.
2018-02-28 1:41 GMT-03:00 Daniele Pezzini <hyouko at gmail.com>:
> 2018-02-27 14:51 GMT+01:00 Jairo Rotava <jairo.rotava at gmail.com>:
> > Hi,
> >
> > I had an issue where after returning the power from a shutdown.return the
> > ups would do another shutdown.return during the boot, and kept this
> forever.
> > After some