Displaying 2 results from an estimated 2 matches for "pw_status_req".
2007 Sep 19
1
Programming problem.
...example
' a ups that don't support battery_test would not have this
command enabled.'
The hex responce look like this from a PW3105:
0c <-- first byte is the number of commands (12)
01 <-- How many bytes reported below for each command
31 <-- PW_ID_BLOCK_REQ
33 <-- PW_STATUS_REQ
34 <-- PW_METER_BLOCK_REQ
35 <-- PW_CUR_ALARM_REQ
36 <-- PW_CONFIG_BLOC_REQ
3c <-- PW_LIMIT_BLOCK_REQ
40 <-- PW_COMMAND_LIST_REQ (this command)
43 <-- PW_UPS_TOP_DATA_REQ
8a <-- PW_LOAD_OFF_RESTART
8b <-- PW_UPS_OFF
a0 <-- PW_SET_REQ_ONLY_MODE
cf <...
2014 Feb 16
1
Eaton Powerware 5110 - some stats not reported
The meter map is basically a bitmap that indicates what variables are output (and in what format) by the UPS. You will likely see a variable, 'not mapped' or nothing. The variables and 'not mapped' items are output by the UPS in the measurement block, and the map tells nut how to read it. 'Unmapped' means that there is a variable there that nut is ignoring, and the xcp