2020 Apr 29
1
[EXTERNAL] SNMP shutdown timing out
...ess?
I tried setting them all with -x thing= arguments as well as letting it
pull from ups.conf, same result. It's all SNMPv3 settings.
sudo snmp-ups -DDDD -a nutdev1 -x secLevel=authPriv -x secName=nut -x
authProtocol=MD5 -x privProtocol=DES -x
authPassword=NutScan at Password43LongerWord -x
privPassword=NutScan at Password43LongerWord -k
The output with -DDDD is the same either way.
> tcpdump to listen for packets across UDP 161 is one way to check what is
> actually being sent.
I guess that really is the next step, isn't it? Darn. I was hoping to
avoid that. Can't do it until Mon...
2013 Jan 29
1
SNMPv3
...management card
My basic question is, does nut's SNMPv3 implementation work?
I have this in /etc/ups/ups.conf
......
[tfapc01]
driver = snmp-ups
port = tfapc01.testfest.ixorg.org
mibs = apcc
snmp_version = v3
secLevel = authPriv
secName = tfsnmpprof1
authPassword = ralow6moHet7zoboP8
privPassword = tuseL8Pakaz9degim7
authProtocol=MD5
privProtocol=AES
desc = "APC SU700 SNMP v3 device, with the highest security level"
......
Now I test
/sbin/snmp-ups -DDD -a tfapc01
Network UPS Tools - Generic SNMP UPS driver 0.68 (2.6.5)
0.000000 debug level is '3'
0.000600 SNMP U...
2020 Apr 28
2
nut-scanner, SNMPv3, APC UPS not chatting
...one)
Privacy Protocol: DES (only option other than none)
In access control I've enabled user nut.
However, when I try to use nut-scanner on it:
$ nut-scanner -S -s apcups --secLevel authPriv --secName nut --authProtocol
MD5 --authPassword NutScan at Password43LongerWord --privProtocol DES
--privPassword NutScan at Password43LongerWord
Scanning SNMP bus.
Error: unknown authtypeError generating Ku from authentication pass phrase
snmpwalk gives a different error:
$ snmpwalk -v 3 -u nut apcups -x DES -X NutScan at Password43LongerWord -a MD5
-A NutScan at Password43LongerWord
snmpwalk: Decryption err...
2020 May 04
2
Fwd: [EXTERNAL] SNMP shutdown timing out
...me result.
nomad
-------------- next part --------------
Script started on 2020-05-04 09:19:50-07:00
]0;lvd at chscc-pc-052:~: || lvd at chscc-pc-052 ~ [936] ; nut-scanner -S --secLevel authPriv --secName nut --authProtocol MD5 --privProtocol DES --authPassword NutScan at P
Password43LongerWord --privPassword NutScan at Password43LongerWord -s apcups
Scanning SNMP bus.
Error: unknown authtypeError generating Ku from authentication pass phrase
]0;lvd at chscc-pc-052:~: || lvd at chscc-pc-052 ~ [937] ; please snmp-ups -DDDD -a nutdev1 -x secLevel=authPriv -x secName=nut -x authProtocol=MD5 -x privProtocol...
2017 Nov 30
2
SNMPv3 fails when more than one UPS is configured in ups.conf
...).
[ups1]
desc = "APC Smart-UPS 5000 SNMP in rack 1 - AP9617"
driver = snmp-ups
mibs = apcc
port = [ups1...]
# snmp_version = v1
# community = [xxx]
snmp_version = v3
secLevel = authPriv
secName = [xxx]
authPassword = [xxx]
authProtocol = MD5
privPassword = [xxx]
privProtocol = DES
[ups2]
desc = "APC Smart-UPS 5000 SNMP in rack 2 - AP9619"
driver = snmp-ups
mibs = apcc
port = [ups2...]
snmp_version = v1
community = [xxx]
# snmp_version = v3
# secLevel = authPriv
# secName = [xxx]
# authPassword = [x...
2018 Sep 14
0
snmp-ups driver for APC smartUPS No supported device detected. Nut-scanner finds the device
... Driver = snmp-ups
Port: ups6.domain.name (also tried 192.168.24.9)
Snmp_version = v3
secLevel = authPriv
secName = ups6
authPassword = PASSWORDSTRING
authProtocol = MD5
privPassword = PASSWORDSTRING
privProtocol = AES
pollfreq = 15
desc = “apc ups”
But when I run the service, I get this error
# /usr/sbin/upsdrvctl start
Network UPS Tools – UPS driver controller 2.7.2
Network UPS Tools – Generic SNMP UPS driver 0.7...
2020 Apr 28
0
[EXTERNAL] nut-scanner, SNMPv3, APC UPS not chatting
...one)
Privacy Protocol: DES (only option other than none)
In access control I've enabled user nut.
However, when I try to use nut-scanner on it:
$ nut-scanner -S -s apcups --secLevel authPriv --secName nut --authProtocol MD5 --authPassword NutScan at Password43LongerWord --privProtocol DES --privPassword NutScan at Password43LongerWord
Scanning SNMP bus.
Error: unknown authtypeError generating Ku from authentication pass phrase
snmpwalk gives a different error:
$ snmpwalk -v 3 -u nut apcups -x DES -X NutScan at Password43LongerWord -a MD5 -A NutScan at Password43LongerWord
snmpwalk: Decryption err...
2020 May 04
0
Fwd: [EXTERNAL] SNMP shutdown timing out
...unfortunate result. Mind you, it could be the UPS card, I'm
using the same one for both tests.
: || nomad at castle nut-2.7.4 [93] ; please drivers/snmp-ups -a nutdev1 -x
secLevel=authPriv -x secName=nut -x authProtocol=MD5 -x privProtocol=DES
-x authPassword=NutScan at Password43LongerWord -x
privPassword=NutScan at Password43LongerWord -k
Network UPS Tools - Generic SNMP UPS driver 0.97 (2.7.4)
No matching MIB found for sysOID '.1.3.6.1.4.1.318.1.3.2.10'!
Please report it to NUT developers, with an 'upsc' output for your device.
Going back to the classic MIB detection method.
Detect...
2016 Jun 03
2
Restarting service issues
Hi,
Every time that I have to restart the nut-server it's a nightmare.
For example, after editing ups.conf
In many cases the only "solution" is to reboot the system.
These are the errors:
systemctl -l status nut-driver
? nut-driver.service - Network UPS Tools - power device driver controller
Loaded: loaded (/usr/lib/systemd/system/nut-driver.service; static;
vendor preset:
2019 Oct 08
0
APC AP9630 SNMP AES
...snmp udp request and reply
port = hostname
snmp_version = v3
secLevel = authPriv
# 4 lowercase ascii letters
secName = xxxx
#
# 16 lower case ascii letters
authPassword = xxxxxxxxxxxxxxxx
# 15 lower case ascii letters
privPassword = yyyyyyyyyyyyyyy
authProtocol = SHA
privProtocol = AES
[..]
* driver debug output and tcpdump attached in nuttrace & nut.pcap
Searching for 9630 i found some similar reports to mailing list nut-upsuser from 2013, 2014 and 2016 indicating that others have this problem too. Th...
2020 Apr 29
2
SNMP shutdown timing out
I'm in the process of trying to get NUT to manage an APC SmartUPS.
Monitoring of the UPS is working fine:
$ upsc nutdev1 at localhost
Init SSL without certificate database
ambient.1.humidity.alarm.high: 60.00
ambient.1.humidity.alarm.low: 30.00
ambient.1.temperature.alarm.high: 40.00
ambient.1.temperature.alarm.low: 10.00
battery.charge: 94.00
battery.charge.restart: 0
battery.current: 0.00