search for: pr3000lcdrtxl2u

Displaying 12 results from an estimated 12 matches for "pr3000lcdrtxl2u".

2024 Mar 21
2
CyberPower PR3000LCDRTXL2U and NUT 2.8.0 - mute?
I have a CyberPower PR3000LCDRTXL2U with a BP48V75ART2U expansion chassis, which I am monitoring using NUT 2.8.0 (on Gentoo Linux). TThe UPS appears to be telling me that the batteries need replacement due to age. CyberPower support has confirmed that for me and told me how i should be able to mute the alarm from the front pane...
2024 Mar 21
1
CyberPower PR3000LCDRTXL2U and NUT 2.8.0 - mute?
On Thu, Mar 21, 2024 at 12:23?PM Phil Stracchino via Nut-upsuser < nut-upsuser at alioth-lists.debian.net> wrote: > I have a CyberPower PR3000LCDRTXL2U with a BP48V75ART2U expansion > chassis, which I am monitoring using NUT 2.8.0 (on Gentoo Linux). TThe > UPS appears to be telling me that the batteries need replacement due to > age. CyberPower support has confirmed that for me and told me how i > should be able to mute the alarm fro...
2024 Apr 02
1
CyberPower PR3000LCDRTXL2U — battery date reset?
So, I just rebuilt the battery packs in my PR3000LCDRTXL2U and its expansion unit. You don't want to KNOW. If the internal batteries have overheated and bulged, you CANNOT remove the battery pack intact even by partially disassembling the UPS, you have to pry the batteries out via the top of the chassis one by one. It's not pretty. Three an...
2020 Aug 08
0
NUT and CyberPower PR3000LCDRTXL2U
Does anyone know whether it is possible to set battery.charge.low lower than 20 on a CyberPower PR3000LCDRTXL2U? 'upsrw -s battery.charge.low 15' returns OK, but does not reduce the setting below 20. Now you may be thinking, "Why would you want to set it lower than 20?" Because with three battery packs, my calculated runtime is about 35 minutes at my full normal operating load, about twic...
2024 Apr 02
1
CyberPower PR3000LCDRTXL2U — battery date reset?
...r liability, and for end-users' fire hazard really) is to not claim the device is safe to use anymore. Jim On Tue, Apr 2, 2024, 07:11 Ben <bkamen at benjammin.net> wrote: > On 4/1/24 7:37 PM, Phil Stracchino via Nut-upsuser wrote: > > So, I just rebuilt the battery packs in my PR3000LCDRTXL2U and its > expansion unit. You don't want to KNOW. If the internal batteries have > overheated and bulged, you CANNOT remove the battery pack intact even by > partially disassembling the UPS, you have to pry the batteries out via the > top of the chassis one by one. It's not p...
2024 Mar 21
1
CyberPower PR3000LCDRTXL2U and NUT 2.8.0 - mute?
On 3/21/24 14:00, Greg Oliver via Nut-upsuser wrote: > All I can say is definitely replace the batteries if you are going to > keep using it.? The CyberPower(s) I have had in the past all have the > battery check that cannot be turned off and when the batteries are > actually "dead" the unit will kill the load to everything every time it > runs the check.? Just FYI.
2019 Dec 16
2
Shutdown time configuration
I switched a while back to a Cyberpower PR3000LCDRTXL2U UPS with an external battery chassis. We've lost power twice since I installed it, and both times, the UPS has killed power to everything while still indicating 80% capacity before NUT has even initiated shutdown on anything. Here's what upsc reports on it right now: battery.charge: 100...
2019 Jan 27
4
Just an interesting data point
...that much of a reduction. I have the snmp-ups driver working with it, have not enabled upsmon yet, but upsc seems to get a rather limited set of data from it: minbar:root:~:1 # upsc backstop at localhost battery.runtime: 25200.00 battery.runtime.elapsed: 0.00 device.mfr: CYBERPOWER device.model: PR3000LCDRTXL2U device.serial: PTEHU2000098 device.type: ups driver.name: snmp-ups driver.parameter.mibs: cyberpower driver.parameter.pollinterval: 2 driver.parameter.port: backstop.caerllewys.net driver.parameter.snmp_version: v1 driver.parameter.synchronous: no driver.version: 2.7.4 driver.version.data: cyberpow...
2019 Jan 22
2
CpberPower PR3000LCDRTXL2UN support
I'm looking at switching from an APC UPS to a different brand after having had my third SU3000RM in a row blow up power transistors. I'm looking at the Cyperpower PR3000LCDRTXL2U. I see the PR3000E and the PR6000LCDRTXL5U listed as supported, but not the PR3000LCDRTXL2U. Howeverit seems likely that if the PR6000LCDRTXL5U is supported, the PR3000LCDRTXL2U ought to work as well. I've been running apcupsd, but if I go with the CyberPower unit I'll be installing NUT 2...
2020 Jun 22
2
Runtime testing
So, a while back I got around to ordering replacement batteries for my CyberPower PR3000LCDRTXL2U. When they arrived, I went to swap them in. I was horrified at the flimsiness of CyberPower's battery "trays". I've seen heavier gauge plastic on "blister" packages in the store. I ALSO discovered that the expansion unit had been shipped to me with one of its two bat...
2019 Dec 16
3
Shutdown time configuration
On 2019-12-16 05:34, Roger Price wrote: > On Sun, 15 Dec 2019, Phil Stracchino wrote: > >> I switched a while back to a Cyberpower PR3000LCDRTXL2U UPS with an >> external battery chassis. We've lost power twice since I installed it, >> and both times, the UPS has killed power to everything while still >> indicating 80% capacity before NUT has even initiated shutdown on anything. >> >> I don't think I eve...
2019 Dec 16
0
Shutdown time configuration
On Sun, 15 Dec 2019, Phil Stracchino wrote: > I switched a while back to a Cyberpower PR3000LCDRTXL2U UPS with an > external battery chassis. We've lost power twice since I installed it, > and both times, the UPS has killed power to everything while still > indicating 80% capacity before NUT has even initiated shutdown on anything. > > I don't think I ever got all the way th...