Displaying 2 results from an estimated 2 matches for "powerstatus".
Did you mean:
power_status
2018 Feb 04
0
[PATCH 3/3] OpenUPS: fix current calculations
Monitoring the input and output currents reported through upsc for an
OpenUPS device suggests that it is an energy creation device - the
power out is greater than the power into the system once the battery
is fully charged.
Analysis and measurement reveals several issues:
1. "UPS.PowerStatus.Output.Current" is scaled for NUTs "output.current"
value, which should be the output current from the UPS.
However, the value reported for "UPS.PowerStatus.Output.Current" is
not the output from the UPS terminals to the load, but is the
current into the LTC378...
2018 Feb 04
5
[PATCH 0/3] OpenUPS updates
Hi,
I've been checking out NUT with an OpenUPS board over the last couple
of weekends, and have noticed that it doesn't seem to report sensible
values. This lead me to investigate usbhid-ups and delve into various
issues.
As mentioned in a github issue, one of the problems is with the report
descriptor - dumping this from the usbhid-ups debug output and picking
through it reveals that