search for: powerconverterid

Displaying 20 results from an estimated 24 matches for "powerconverterid".

Did you mean: powerconverter
2006 Sep 22
1
Ablerex 625L USB version
...terySystem.Voltage, Type: Feature, Value: 0.000000 Path: 00860004.BatterySystem.Temperature, Type: Feature, Value: 0.000000 Path: 00860004.BatterySystem.Test, Type: Input, Value: 0.000000 Path: 00860004.BatterySystem.Test, Type: Feature, Value: 0.000000 Can't find object 00860004.PowerConverter.PowerConverterID Path: 00860004.PowerConverter.PowerConverterID, Type: Input Can't find object 00860004.PowerConverter.Input.InputID Path: 00860004.PowerConverter.Input.InputID, Type: Input Can't find object 00860004.PowerConverter.Input.FlowID Path: 00860004.PowerConverter.Input.FlowID, Type: Input Can'...
2006 Feb 27
1
MGE Nova 1100 using newhidups on netBSD 3.0
...ted a UPS: unknown/unknown Using subdriver: MGE HID 0.8 Looking up 00840004 Looking up 00840016 Looking up 00840017 entering string_to_path() parsing UPS Looking up UPS hid_lookup_usage: found 840004 parsing PowerConverter Looking up PowerConverter hid_lookup_usage: found 840016 parsing PowerConverterID Looking up PowerConverterID hid_lookup_usage: found 840017 Path depth = 3 0: UPage(84), Usage(4) 1: UPage(84), Usage(16) 2: UPage(84), Usage(17) Entering libusb_get_report Can't retrieve Report 11 (-5/5): Input/output error Path: UPS.PowerConverter.PowerConverterID, Type: Feature Look...
2006 Feb 10
1
newhidups capture - Atlantis-Land HID UPS
Hello Charles! As promised, I just checked out the CVS and recompiled everything. In the attached .txt is what is coming out from my UPS. I am wondering about all those zeroes. Also, this morning I plan to connect the UPS to a Win box running the monitoring program supplied with the UPS (UPSilon2000) and a USB sniffer program. If you have any suggestions on what to look for in the data,
2005 Dec 07
5
Atlantis-Land UPS with Cypress CY7C63723 chip (cypress_m8 driver) support
Hello everybody! I am trying to get an Atlantis-Land OnePower Line Interactive S1501 UPS (actually it is made by Ablerex) to talt to my Linux box through its USB port (no more RS-232...), either using the supplied program (UPSilon2000, works under Win and Linux) or whatever else. The UPSilon2000 program apparently works OK *if* it can talk to the UPS via a serial port; since my UPS has
2005 Dec 07
5
Atlantis-Land UPS with Cypress CY7C63723 chip (cypress_m8 driver) support
Hello everybody! I am trying to get an Atlantis-Land OnePower Line Interactive S1501 UPS (actually it is made by Ablerex) to talt to my Linux box through its USB port (no more RS-232...), either using the supplied program (UPSilon2000, works under Win and Linux) or whatever else. The UPSilon2000 program apparently works OK *if* it can talk to the UPS via a serial port; since my UPS has
2006 Sep 11
3
new ups for database?
I have a Belkin F6H500ukUNV ups that I am attempting to get working under nut, however it does not appear to be detected by nut, I'm assuming that I need to feed some information back to you guys to get it included in the database somwhere. I've included (what I can think might be) the relivant outputs. Please let me know if you require anything else. dmesg output /sbin/newhidsups
2007 Feb 16
5
MGE Nova AVR 600 USB on FreeBSD
...umber: unknown - Bus: /dev/usb0 Trying to match device Device matches HID descriptor retrieved (Reportlen = 358) Report descriptor retrieved (Reportlen = 358) Found HID device Report Descriptor size = 358 Detected a UPS: MGE UPS SYSTEMS/NOVA AVR Using subdriver: MGE HID 1.0 Path: UPS.PowerConverter.PowerConverterID, Type: Feature, ReportID: 0x0b, Offset: 0, Size: 8, Value: 1.000000 (I get lots of lines like this with various data form the UPS. The last couple of lines of output are..) upsdrv_updateinfo... dstate_init: sock /var/db/nut/mge-nova open on fd 5 upsdrv_updateinfo... Waiting for notifications... A...
2007 Feb 16
5
MGE Nova AVR 600 USB on FreeBSD
...umber: unknown - Bus: /dev/usb0 Trying to match device Device matches HID descriptor retrieved (Reportlen = 358) Report descriptor retrieved (Reportlen = 358) Found HID device Report Descriptor size = 358 Detected a UPS: MGE UPS SYSTEMS/NOVA AVR Using subdriver: MGE HID 1.0 Path: UPS.PowerConverter.PowerConverterID, Type: Feature, ReportID: 0x0b, Offset: 0, Size: 8, Value: 1.000000 (I get lots of lines like this with various data form the UPS. The last couple of lines of output are..) upsdrv_updateinfo... dstate_init: sock /var/db/nut/mge-nova open on fd 5 upsdrv_updateinfo... Waiting for notifications... A...
2016 Sep 08
2
blazer_usb MEC0002 problem Fry's Electronics (Turbo-X)
...1, Value: 100000 0.623826 Report[buf]: (9 bytes) => 16 03 55 00 50 00 53 00 20 0.623832 Path: 00860004.BatterySystem.Test, Type: Feature, ReportID: 0x03, Offset: 56, Size: 1, Value: 0 0.635732 Report[get]: (8 bytes) => 16 03 55 00 50 00 53 00 0.635745 Path: 00860004.PowerConverter.PowerConverterID, Type: Input, ReportID: 0x04, Offset: 0, Size: 4, Value: 300000 0.635751 Report[buf]: (8 bytes) => 16 03 55 00 50 00 53 00 0.635757 Path: 00860004.PowerConverter.Input.InputID, Type: Input, ReportID: 0x04, Offset: 8, Size: 4, Value: 500000 0.635765 Report[buf]: (8 bytes) => 16 03 55...
2014 Apr 05
0
I can't make changes to ups.delay.shutdown to stick
On Apr 5, 2014, at 7:18 AM, Mick wrote: > $ upsrw -s "ups.delay.shutdown"="30" iDowell at localhost > Username (suzy): admin > Password: > OK This command is sending the value to the UPS (via the usbhid-ups driver). > $ upsc iDowell at localhost ups.delay.shutdown > 30 And this command ends up reading the value back from the UPS. > However, following
2014 Apr 05
2
I can't make changes to ups.delay.shutdown to stick
...99896 Device matches 0.899930 failed to claim USB device: Device or resource busy 0.900102 detached kernel driver from USB device... 0.907834 HID descriptor length 412 0.962825 Report Descriptor size = 412 0.963065 Using subdriver: EXPLORE HID 0.1 0.966834 Path: UPS.PowerConverter.PowerConverterID, Type: Feature, ReportID: 0x0b, Offset: 0, Size: 8, Value: 0 0.966856 Path: UPS.PowerConverter.Output.OutputID, Type: Feature, ReportID: 0x0b, Offset: 8, Size: 8, Value: 0 0.970828 Path: UPS.PowerConverter.Output.Voltage, Type: Feature, ReportID: 0x0e, Offset: 0, Size: 8, Value: 230 0.9...
2014 Apr 05
2
I can't make changes to ups.delay.shutdown to stick
Hi All, I'm using an iDowell UPS with the usbhid-ups driver: $ upsc iDowell at localhost battery.charge: 100 battery.charge.low: 15 battery.runtime: 650 battery.type: Pb acc device.mfr: iDowell device.model: iBox device.serial: 00000001 device.type: ups driver.name: usbhid-ups driver.parameter.pollfreq: 30 driver.parameter.pollinterval: 2 driver.parameter.port: auto
2016 Sep 08
2
blazer_usb MEC0002 problem Fry's Electronics (Turbo-X) [HID PDC?]
...1, Value: 100000 0.478281 Report[buf]: (9 bytes) => 16 03 55 00 50 00 53 00 20 0.478291 Path: 00860004.BatterySystem.Test, Type: Feature, ReportID: 0x03, Offset: 56, Size: 1, Value: 0 0.490193 Report[get]: (8 bytes) => 16 03 55 00 50 00 53 00 0.490209 Path: 00860004.PowerConverter.PowerConverterID, Type: Input, ReportID: 0x04, Offset: 0, Size: 4, Value: 300000 0.490216 Report[buf]: (8 bytes) => 16 03 55 00 50 00 53 00 0.490223 Path: 00860004.PowerConverter.Input.InputID, Type: Input, ReportID: 0x04, Offset: 8, Size: 4, Value: 500000 0.490228 Report[buf]: (8 bytes) => 16 03 55...
2006 May 02
5
Newhidups gets unbound after a while
Hi everybody, If we let the feature running, it appears that the driver gets unbound after a while ( variable from quarter of hour to 6 hours ) and cannot reconnect. This behavior appear with both MGE Ellipse ASR and non-ASR models with connection to an UHCI and OHCI controllers. The USB core is from 2.4.28 kernel. We use nut-2.0.3. Start, powerfail and recovery detections, UPS shutdown work
2018 May 25
1
[HCL] IBM 1500VA/1000W Tower HV UPS supported by usbhid-ups
...lue: 0 9.761417 Path: UPS.PowerConverter.Output.PresentStatus.ffff004a, Type: Input, ReportID: 0x49, Offset: 16, Size: 8, Value: 0 9.762076 Path: UPS.PowerConverter.Output.Voltage, Type: Feature, ReportID: 0x42, Offset: 64, Size: 16, Value: 236 9.762275 Path: UPS.PowerConverter.PowerConverterID, Type: Feature, ReportID: 0x40, Offset: 24, Size: 8, Value: 1 9.790659 Path: UPS.PowerSummary.AudibleAlarmControl, Type: Feature, ReportID: 0x13, Offset: 0, Size: 8, Value: 2 9.825288 Path: UPS.PowerSummary.CapacityGranularity1, Type: Feature, ReportID: 0x0c, Offset: 0, Size: 8, Value...
2012 Jul 18
1
Problem connecting to eaton ups. No matching HID UPS found. Driver failed to start(exit status=1)
...ize: 8, Value: 0 4.645525 Path: UPS.PowerConverter.Output.PresentStatus.ShortCircuit, Type: Input, ReportID: 0x03, Offset: 24, Size: 8, Value: 0 4.689946 Path: UPS.PowerConverter.Output.Voltage, Type: Feature, ReportID: 0x0e, Offset: 0, Size: 8, Value: 230 4.690142 Path: UPS.PowerConverter.PowerConverterID, Type: Feature, ReportID: 0x0b, Offset: 72, Size: 8, Value: 1 4.690380 Path: UPS.PowerConverter.Rectifier.PresentStatus.DCBusUnbalanced, Type: Feature, ReportID: 0x03, Offset: 32, Size: 8, Value: 0 4.690555 Path: UPS.PowerConverter.Rectifier.PresentStatus.DCBusUnbalanced, Type: Input, ReportI...
2010 Sep 18
1
Dynamix 1000 VA USB and NUT
...ReportID: 0x03, Offset: 0, Size: 1 2.251394 Can't retrieve Report 03: Broken pipe 2.251414 Path: 00860004.BatterySystem.Test, Type: Feature, ReportID: 0x03, Offset: 56, Size: 1 2.254254 Can't retrieve Report 04: Broken pipe 2.254272 Path: 00860004.PowerConverter.PowerConverterID, Type: Input, ReportID: 0x04, Offset: 0, Size: 4 2.257400 Can't retrieve Report 04: Broken pipe 2.257434 Path: 00860004.PowerConverter.Input.InputID, Type: Input, ReportID: 0x04, Offset: 8, Size: 4 2.260426 Can't retrieve Report 04: Broken pipe 2.260466 Path: 008...
2016 May 03
2
New UPS Support: Eaton 5S 1000
Oops... changing that to --with-user=nut solved one problem. I have the driver, upsd and upsmon running now. Thank you! Now I'm back to another issue, every 2 seconds I get in the logs: May 3 13:45:23 myhost upsd[2587]: Connected to UPS [eaton]: usbhid-ups-eaton It seems happy to do this forever. On Tue, May 3, 2016 at 8:17 AM, Charles Lepple <clepple at gmail.com> wrote: > On
2016 May 04
2
New UPS Support: Eaton 5S 1000
...ze: 8, Value: 0 5.437989 Path: UPS.PowerConverter.Output.PresentStatus.ShortCircuit, Type: Input, ReportID: 0x03, Offset: 24, Size: 8, Value: 0 5.437998 Path: UPS.PowerConverter.Output.Voltage, Type: Feature, ReportID: 0x0e, Offset: 80, Size: 8, Value: 120 5.438008 Path: UPS.PowerConverter.PowerConverterID, Type: Feature, ReportID: 0x0b, Offset: 88, Size: 8, Value: 1 5.438016 Path: UPS.PowerConverter.Rectifier.PresentStatus.DCBusUnbalanced, Type: Feature, ReportID: 0x03, Offset: 32, Size: 8, Value: 0 5.438024 Path: UPS.PowerConverter.Rectifier.PresentStatus.DCBusUnbalanced, Type: Input, ReportI...
2015 Mar 03
0
Ippon Smart Winner 3000 New
...6.232688 Report[buf]: (9 bytes) => 42 e5 00 1e 01 f3 01 e3 00 6.233234 Path: UPS.PowerConverter.Output.Voltage, Type: Feature, ReportID: 0x42, Offset: 48, Size: 16, Value: 227 6.233561 Report[buf]: (5 bytes) => 40 01 04 01 01 6.233917 Path: UPS.PowerConverter.PowerConverterID, Type: Feature, ReportID: 0x40, Offset: 24, Size: 8, Value: 1 6.530351 Report[get]: (2 bytes) => 13 02 6.530812 Path: UPS.PowerSummary.AudibleAlarmControl, Type: Feature, ReportID: 0x13, Offset: 0, Size: 8, Value: 2 6.631077 Report[get]: (5 bytes) => 0c 01 02 64 64...