Displaying 19 results from an estimated 19 matches for "phymin".
Did you mean:
phy_id
2009 Mar 13
7
Weird Load and Battery Temp Readings
I've acquired and installed NUT 2.4.1 on a D-Link DNS323 NAS. With
exception of Load and Battery Temp readings all works well. A upsc
ups at localhost command returns;
battery.charge: 100
battery.charge.low: 10
battery.charge.warning: 50
battery.date: 2001/09/25
battery.mfr.date: 2008/06/05
battery.runtime: 2122
battery.runtime.low: 120
battery.temperature: 3022999999999998800
battery.type:
2012 Mar 21
5
Socomec sicon Netys 2000 PR ups USb driver for ubuntu
Hello i tried to connect my netys 2000 pr ups to ubuntu 11.10 and i have a problem connecting it. After readin a few post i realized to dianosse the connection.
I need help resolving the connextion issue
So here is the response to??/lib/nut/usbhid-ups -u root -DDDDD -a netys:
Network UPS Tools - Generic HID driver 0.35 (2.6.1)
USB communication driver 0.31
? ?0.000000 ? ? send_to_all: SETINFO
2014 Feb 25
0
Setting UPS values can be confusing
...4002 hid_lookup_usage: UPS -> 00840004
0.624002 hid_lookup_usage: PowerSummary -> 00840024
0.624002 hid_lookup_usage: RemainingCapacityLimit -> 00850029
0.624002 string_to_path: depth = 3
0.624002 Report[buf]: (2 bytes) => 11 0a
0.624002 PhyMax = 0, PhyMin = 0, LogMax = 100, LogMin = 1
0.624002 Unit = 00000000, UnitExp = 0
0.624002 Exponent = 0
0.624002 Path: UPS.PowerSummary.RemainingCapacityLimit, Type:
Feature, ReportID: 0x11, Offset: 0, Size: 8, Value: 10
0.624002 send_to_all: SETINFO battery.charge.low "10"...
2017 May 11
4
APC Back-UPS XS 1500G says "No battery"
I have a new-ish APC Back-UPS XS 1500G connected via USB. It's giving me
a "ups.alarm: No battery installed!" error. I also installed and
configured apcupsd to give that a try and it's giving me the same error.
I suspect this is a driver problem because while NUT claims the battery
isn't plugged in, it's giving me battery runtime/charge info. Both can't
be valid
2014 Oct 10
1
Return on experience with an Emerson/Liebert GXT3
Hi
On 10/06/2014 03:04 PM, Charles Lepple wrote:> I think I see what is going on.
>
>???? 0.368670??? Report[buf]: (5 bytes) => 05 4e 00 48 00
>???? 0.368698??? PhyMax = 0, PhyMin = 0, LogMax = 1, LogMin = 0
>???? 0.368723??? Unit = 00000000, UnitExp = 0
>???? 0.368747??? Exponent = 0
>???? 0.368776??? Path: UPS.PowerSummary.Voltage, Type: Feature, ReportID: 0x05, Offset: 0, Size: 16, Value: 0
>???? 0.368805??? Input/OutputVoltage = 0 -> assuming correction fa...
2017 May 12
0
APC Back-UPS XS 1500G says "No battery"
...gt; 0.571443 hid_lookup_path: 008500d1 -> BatteryPresent
> 0.571446 Path: UPS.PowerSummary.PresentStatus.BatteryPresent, Type: Input, ReportID: 0x16, Offset: 3, Size: 1, Value: 0
> 0.571449 Report[buf]: (5 bytes) => 16 04 00 00 00
> 0.571451 PhyMax = 0, PhyMin = 0, LogMax = 1, LogMin = 0
> 0.571453 Unit = 00000000, UnitExp = 0
> 0.571455 Exponent = 0
> 0.571457 hid_lookup_path: 00840004 -> UPS
> 0.571459 hid_lookup_path: 00840024 -> PowerSummary
> 0.571461 hid_lookup_path: 00840002 -> Presen...
2015 Mar 13
0
Problems with NUT 2.7.2 on CentOS 7 and using the Mini-Box OpenUPS
...y affect ups.mfr and ups.model in upsc.
>
> And if I run upsd with high level of debug, after working OK for a while, I see these ?broken pipe? messages :
>
> 0.419974 Entering libusb_get_report
> 0.421967 Report[get]: (4 bytes) => 60 c4 ff 3b
> 0.422056 PhyMax = 0, PhyMin = 0, LogMax = 16777215, LogMin = 0
> 0.422069 Unit = 00001001, UnitExp = 0
> 0.422080 Exponent = 0
> 0.422093 hid_lookup_path: 00840004 -> UPS
> 0.422107 hid_lookup_path: 00840024 -> PowerSummary
> 0.422121 hid_lookup_path: 00850068 -> RunTimeToEmpty
> 0...
2006 May 22
3
USB UPS and FreeBSD
I am looking at the newhid driver for this Pulsar EXtreme here but it gives
odd results, for example there is no status variable :)
eg
debug level is '2'
Checking device (0463/FFFF) (/dev/usb0//dev/ugen0)
- VendorID: 0463
- ProductID: ffff
- Manufacturer: unknown
- Product: unknown
- Serial Number: unknown
- Bus: /dev/usb0
Trying to match device
Device matches
HID descriptor retrieved
2013 Feb 08
0
Very long delay for shutdown.restart on usbhid-ups powercom
...correctly processed, but with
uncorrect parameters:
55.348163 instcmd(shutdown.return, 30)
55.348205 powercom_shutdown_nuf: value = 30, command = 5E00
55.348218 hu_find_valinfo: found 24064 (value: 30)
55.348229 Unit = 00000000, UnitExp = 0
55.348239 Exponent = 0
55.348249 PhyMax = 0, PhyMin = 0, LogMax = 65535, LogMin = 0
55.348920 Report[set]: (3 bytes) => 0f 00 5e
55.348945 Set report succeeded
55.348956 instcmd: SUCCEED
Value 30 is converted to 24064, and this seems the delay that is
configured on the device to complete its shutdown:
[...]
56.358009 Path: UPS.PowerSumma...
2014 Oct 06
1
Return on experience with an Emerson/Liebert GXT3
Hi
On 10/03/2014 03:42 PM, Charles Lepple wrote:> On Oct 3, 2014, at 7:50 AM, paul.chavent at fnac.net wrote:
>
>
> This is what I was referring to (from the belkin-hid log):
>
>???? 1.325782??? Report[buf]: (5 bytes) => 05 53 00 48 00
>???? 1.325799??? Path: UPS.PowerSummary.ConfigVoltage, Type: Feature, ReportID: 0x05, Offset: 16, Size: 16, Value: 0
>????
2024 Mar 25
0
There is no voltage information
...ot;
> 0.278517 hid_lookup_usage: UPS -> 00840004
> 0.278621 hid_lookup_usage: Output -> 0084001c
> 0.278769 hid_lookup_usage: Voltage -> 00840030
> 0.278913 string_to_path: depth = 3
> 0.279025 Report[buf]: (3 bytes) => 2b 9e 08
> 0.279133 PhyMax = 0, PhyMin = 0, LogMax = 65535, LogMin = 0
> 0.279240 Unit = 00f0d121, UnitExp = -1
> 0.279304 Exponent = -8
> 0.279412 Path: UPS.Output.Voltage, Type: Feature, ReportID: 0x2b,
> Offset: 0, Size: 16, Value: 2.206e-05
> 0.279523 Input/OutputVoltage = 2.206e-05 -> assuming correcti...
2024 Mar 25
0
There is no voltage information
...ot;
> 0.278517 hid_lookup_usage: UPS -> 00840004
> 0.278621 hid_lookup_usage: Output -> 0084001c
> 0.278769 hid_lookup_usage: Voltage -> 00840030
> 0.278913 string_to_path: depth = 3
> 0.279025 Report[buf]: (3 bytes) => 2b 9e 08
> 0.279133 PhyMax = 0, PhyMin = 0, LogMax = 65535, LogMin = 0
> 0.279240 Unit = 00f0d121, UnitExp = -1
> 0.279304 Exponent = -8
> 0.279412 Path: UPS.Output.Voltage, Type: Feature, ReportID: 0x2b,
> Offset: 0, Size: 16, Value: 2.206e-05
> 0.279523 Input/OutputVoltage = 2.206e-05 -> assuming correcti...
2016 May 28
0
Powercom INF-800 support
...0.145763 instcmd(shutdown.return, [NULL])
> 0.145767 powercom_shutdown_nuf: value = (null), command = 5400
> 0.145770 hu_find_valinfo: found 21504 (value: (null))
> 0.145773 Unit = 00000000, UnitExp = 0
> 0.145775 Exponent = 0
> 0.145778 PhyMax = 0, PhyMin = 0, LogMax = 65535, LogMin = 0
> 0.155952 Report[set]: (3 bytes) => 0f 00 54
> 0.155981 Set report succeeded
> 0.155986 instcmd: SUCCEED
>
When you attempted the shutdown.return, was the UPS powered or on battery?
My older Tripplite SMART2200VS won't shutdown....
2016 May 28
1
Powercom INF-800 support
...d(shutdown.return, [NULL])
> 0.145767 powercom_shutdown_nuf: value = (null), command = 5400
> 0.145770 hu_find_valinfo: found 21504 (value: (null))
> 0.145773 Unit = 00000000, UnitExp = 0
> 0.145775 Exponent = 0
> 0.145778 PhyMax = 0, PhyMin = 0, LogMax = 65535, LogMin = 0
> 0.155952 Report[set]: (3 bytes) => 0f 00 54
> 0.155981 Set report succeeded
> 0.155986 instcmd: SUCCEED
>
>
> When you attempted the shutdown.return, was the UPS powered or on
> battery? My older Tripplite SMA...
2015 Mar 13
3
Problems with NUT 2.7.2 on CentOS 7 and using the Mini-Box OpenUPS
I?m a new user of NUT and the OpenUPS - in the past I?ve used APC hardware and apcupsd on Centos 6.
I?ve built NUT 2.7.2 from source but used the OpenUPS HID driver v0.4 that?s in github. I?m using firmware version 1.5 on the openups which is the latest published version; I?ve also tried 1.7 which Mini-box sent to me but reverted to the published version. Their support seems a bit slow!
I?ve got
2016 May 28
2
Powercom INF-800 support
...psdrv_shutdown...
0.145763 instcmd(shutdown.return, [NULL])
0.145767 powercom_shutdown_nuf: value = (null), command = 5400
0.145770 hu_find_valinfo: found 21504 (value: (null))
0.145773 Unit = 00000000, UnitExp = 0
0.145775 Exponent = 0
0.145778 PhyMax = 0, PhyMin = 0, LogMax = 65535, LogMin = 0
0.155952 Report[set]: (3 bytes) => 0f 00 54
0.155981 Set report succeeded
0.155986 instcmd: SUCCEED
Every 2 sec driver outputs the following:
10.254942 upsdrv_updateinfo...
10.507035 libusb_get_interrupt: Connection timed out
1...
2023 Jan 13
1
battery.voltage Powercom Macan MRT-3000
...Usage Name | Data Access | Length
26 0X8430 Battery Voltage R/O 3 Byte
But I get for this position the next data:
0.544555 [D4] Entering libusb_get_report
0.549533 [D3] Report[get]: (3 bytes) => 1a 02 15
0.549550 [D5] PhyMax = 0, PhyMin = 0, LogMax = 9216, LogMin = 2304
0.549561 [D5] Unit = 00000000, UnitExp = 0
0.549569 [D5] Exponent = 0
0.549576 [D5] hid_lookup_path: 00840004 -> UPS
0.549583 [D5] hid_lookup_path: 00840012 -> Battery
0.549591 [D5] hid_lookup_path: 00840030 ->...
2009 Sep 20
2
TrippLite Eco Series UPS
I purchased a TrippLite ECO550UPS from Amazon a few days ago thinking
I was going to use it for my Windows Media Center HTPC. I've since
changed my mind and decided to use Mythbuntu but it I can't get my UPS
working with nut. I've tried all of the tripplite drivers and the
usbhid-ups driver. The tripplite_usb and usbhid_ups output is listed
below. The tripplite and tripplitesu drivers
2006 May 16
2
MGE Pulsar Extreme communication problems
Hi,
I am trying to talk to an MGE Pulsar Extreme UPS over RS232 with the
mge-shut driver but I'm having some problems.
It appears to init OK but I can't, say, turn the outlets off, eg..
harrow:~>upsc mge@localhost
battery.charge: 78
battery.charge.low: 20
battery.runtime: 05760
driver.name: mge-shut
driver.parameter.port: /dev/cuad1
driver.version: 2.0.3
driver.version.internal: 0.65