2017 Jan 10
0
NUT Client shuts down when performing runtime calibration on APC UPS
On Jan 9, 2017, at 9:46 AM, Merk - Oliver <oliver.merk at pecon.biz> wrote: > > I then connected to my QNAP and set the UPS settings on the web interface to "Shutdown server if power loss is 5 min", the UPS is configured to an SNMP-Connection with its IP-address. Started runtime calibration and after 5min. the QNAP NAS has shut down. But be...
2016 Dec 20
2
NUT Client shuts down when performing runtime calibration on APC UPS
Hello, I am using an APC UPS (Smart-UPS 2200 RM) to secure my SAN. The SAN runs on FreeBSD 9.1-RELEASE-p5 and is using NUT 2.6.5 version 2. Since the UPS has also a Network card AP9630 I am using the snmp-ups driver to connect the SAN to the UPS for signaling. Last week I need to change the battery pack and then I needed to perform a runtime calibration. I used the web interface of the AP9630
2017 Jan 09
2
NUT Client shuts down when performing runtime calibration on APC UPS
Here are the results from the output of upsc under different conditions from my Debian Test system with NUT 2.7.2 : Normal: ups.status: OL No wall power: ups.status: OB Runtime calibration (started from AP9630 web interface): ups.status: OB CAL So at this stage there is a difference! I then connected to my QNAP and set the UPS settings on the web interface to "Shutdown server if power
2017 Jan 09
0
NUT Client shuts down when performing runtime calibration on APC UPS
Thanks for your reply. Sorry for the delay, but until yet I haven't had a subscription, so I haven't seen your answer. I can test this, I have three APC USVs, each equipped with the AP9630 network card. I need to setup a Linux test VM with NUT first. I will give the feedback as soon as I can. Oliver ________________________________ This email was scanned by Bitdefender --------------
2017 Jan 11
0
NUT Client shuts down when performing runtime calibration on APC UPS
Thanks for your help. I have posted information, but I think I have answered myself, so maybe you haven't got an info. Sorry, using a mailing list is new for me ;-) Let's forget about the QNAP problem. It seems that although upsc is getting correct status information ("OL", "OB", "OB LB", OB CAL"), including calibration state, the QNAP special program
2017 Jan 11
3
NUT Client shuts down when performing runtime calibration on APC UPS
I've setup nas4free (latest version 11.0.0.4, which has NUT 2.7.4) in a VM and configured it via webinterface to my APC UPS and set "shutdown mode" to "UPS goes on battery" with a timer of 30s. Then I started runtime calibration on the UPS and after 30s nas4free has shut down! I think this is not the correct behavior, since the status was "OB CAL". The system