search for: or700lcdrm1u

Displaying 5 results from an estimated 5 matches for "or700lcdrm1u".

2012 Feb 22
1
[HCL] CyberPower OR700 supported by usbhid-ups
CyberPower OR700LCDRM1U (http://www.cyberpowersystems.com/products/ups-systems/smart-app-ups/rackmount-lcd/OR700LCDRM1U.html) upsc output: battery.charge: 100 battery.charge.low: 10 battery.charge.warning: 20 battery.mfr.date: CPS battery.runtime: 6000 battery.runtime.low: 300 battery.type: PbAcid battery.voltage: 14.5 b...
2012 Feb 15
1
CyberPower UPS Help
Hi all. I'm trying to get a CyberPower OR700LCDRM1U UPS working with NUT (via USB). I assumed this would be compatible since the OR2200LCDRM2U is. Clearly I'm wrong or missing something vital. I'm on FreeBSD, using the version of NUT from the ports tree (2.6.1). FWIW, I tried compiling from source with similar results. Here's my UPS...
2014 Aug 11
1
Cyberpower Value1200E might not need 0.667 battery scaling
...VR/BC900D */ > { USB_DEVICE(CPS_VENDORID, 0x0005), NULL }, > - /* Dynex DX-800U? */ > + /* Dynex DX-800U?, CP1200AVR/BC1200D, CP825AVR-G, CP1000AVRLCD, CP1000PFCLCD, CP1500C, CP550HG, etc. */ > { USB_DEVICE(CPS_VENDORID, 0x0501), &cps_battery_scale }, > /* OR2200LCDRM2U, OR700LCDRM1U, PR6000LCDRTXL5U */ > { USB_DEVICE(CPS_VENDORID, 0x0601), NULL }, > @@ -59,12 +66,48 @@ static usb_device_id_t cps_usb_device_table[] = { > { -1, -1, NULL } > }; > > +/*! Adjusts @a battery_scale if voltage is well above nominal. > + */ > +static void cps_adjust_b...
2014 Aug 09
0
Cyberpower Value1200E might not need 0.667 battery scaling
On Aug 8, 2014, at 9:15 AM, Charles Lepple <clepple at gmail.com> wrote: > On Aug 7, 2014, at 10:52 PM, Charles Lepple <clepple at gmail.com> wrote: > >> On Aug 7, 2014, at 10:18 PM, Matthew Stapleton <matthew4196 at gmail.com> wrote: >> >>> I just got a Cyberpower SOHO Value 1200 ELCD UPS and even with nut 2.7.2, it appears to report battery voltage
2014 Aug 08
2
Cyberpower Value1200E might not need 0.667 battery scaling
On Aug 7, 2014, at 10:52 PM, Charles Lepple <clepple at gmail.com> wrote: > On Aug 7, 2014, at 10:18 PM, Matthew Stapleton <matthew4196 at gmail.com> wrote: > >> I just got a Cyberpower SOHO Value 1200 ELCD UPS and even with nut 2.7.2, it appears to report battery voltage too low due to the battery scaling function (In drivers/cps-hid.c). Even though the ups has usb id: