search for: onbatteri

Displaying 20 results from an estimated 25 matches for "onbatteri".

Did you mean: onbattery
2007 Oct 23
1
MGE Pulsar Ellipse 800 offearly or box shutdown late
I'm struggling to configuring nut for MGE Pulsar Ellipse 800 (at least Ellipse 800) for two boxes - home firewall and file server. I'm using Debian 4.0 Etch, every one of them. I'm built (after some dangerouse experiments) a testing configuration, where boxes are plugged to line, server playing as a master, firewall as a slave, and UPS connected to an electric heater about 300 Wats (no
2014 Sep 11
2
How do I disable messages from upsmon?
I've followed the config setup docs and also the excellent guide from Roger Price. I'm using openSUSE 13.1 and built NUT 2.7.2 from the sources (latest stable). I'm hooked up to a dummy UPS that basically just cycles from fully charged down to about 20% discharged. I was pleased when I started seeing the messages on my screen indicating the UPS was online or on-battery. Given how
2007 Oct 24
4
MGE Ellipse 800 shutdown problems - using upsmon NOTIFYCMD
upsmon.conf using NOTIFCMD and NOTIFYFLG is working well, it is calling my script "notify" on requested events (ONBATTERY,LOWBATTERY and ONLINE). Command #upsmon -c fsd -u monmaster myups at localhost gracefully shutdown my box and after several seconds switch off the ups's load. Two problems: - notify script is called and executed as user "nut" (as it used to be
2007 Oct 25
0
newmge-shut warning (was: MGE Ellipse 800 shutdown problems)
I'm now doubting if I've made this statement or not, so here it is: newmge-shut is *not* ready for production usage! I've lately found some bugs during the MGE PSP 3.0.4/3.0.5/3.0.6 updates. So for the moment, prefer to keep using mge-shut. 2007/10/25, R?zsa G?bor <mailer.tovis at freemail.hu>: > newmge-shut ??? > Shutdown, switch of ups does not work. Using command >
2014 May 21
0
upssched timer configuration with redundant UPSes ?
Hello list, I have the following hardware setup: - HP C7000 enclosure, with 4 blade servers - two power supply modules in the enclosure (one is enough to sustain the 4 blades) - two UPSes, each one feeding one of the enclosure power supplies I would like to configure NUT to initiate an early shutdown of that environment only if *both* UPSes are on battery. I've created the 2
2014 Sep 12
0
How do I disable messages from upsmon?
On Sep 11, 2014, at 10:38 AM, Rob Groner <rgroner at RTD.com> wrote: > I?m still getting the onbattery, online, comm good, comm bad, etc system messages. Clearly there is some default behavior going on. How do I keep these system messages from happening? From http://www.networkupstools.org/docs/man/upsmon.conf.html: "NOTIFYFLAG type flag[+flag][+flag]? By default, upsmon sends
2013 Jan 09
1
Is there any "fake UPS" driver (and Solaris 10+ integration)?
Hello all, I am a long-time user of NUT (since last millennium, or so it seems) and beside Linux where I've started, I also integrated it with our Solaris 8 and 9 servers' shutdown procedures - avoiding the possible "hole" when the line power returns right at the bad moment when UPSes and systems are already told to power off. In this case, they see no event like "I am
2007 Oct 25
12
MGE Ellipse 800 shutdown problems
Thanks for suggetions and keep me indumb about making of Debian packages:D I will try this package "nut_2.2.0-2_i386.deb" One little questionm, shoud I use newmge-shut driver? - my ups is quite old - more then 3 years, connected through serial cable. >> PS: Arjen de Korte suspected something was wrong around my "heater" load, >> for now I have used two 150W lamps
2007 Oct 23
3
MGE Pulsar Ellipse 800 off early or box shutdown late
> If you set lowbatt=70 then the behaviour you are seeing is normal. Don't > set lowbatt and you'll get the default manufacturer settings which is > LOWBATTERY at 30% charge level. > > Philippe Thanks for quick response! I realized this and forget this setting! For now I think that my box does not recognize signal about low battery - I'm only started to read SHUT
2012 Nov 06
4
apcupsd
Anyone else around using apcupsd? I seem to be seeing a problem, and I'd like someone to check me on it: I edit /etc/apcupsd/apccontrol to replace the value of SHUTDOWN from /sbin/shutdown to /bin/false (we don't want 3 or 6 servers shutting down over a 2 second or so blip, which it really wants to do). What's happened is that a machine shut down the other day, and looking at it, I
2011 Nov 11
1
Step by step help for Windows Vista User?
Hi all, sorry for this message, but maybe I am the most dumb user in here, so, please accept my appologies asking novice questions. I have tried 6 searched for more than 4 hours now, read all html-man files I could think need to be read and also the major one, but I did not manage to get the NUT to successfully run on my Vista machine. (it runs, but I cannot use it ... see later). I am
2020 Apr 23
3
Low battery unexpected shutdown
Hi, recently I observed that during a power outage, my NUT setup doesn't shutdown properly. Indeed it never reaches the LowBattery state to notify and initiate shutdown on clients. Reviewing my setup and logs I think I'm facing multiple problems and I'm unable to point to real root cause. First, let me focus on my scenario and current setup: In normal status (ONLINE, fully charged)
2008 May 20
1
UPS gracefull restart
Hi, I'm just looking at the code of snmp-ups driver in the source tree. I'm trying to find out, what can I change in the code to force the snmp-ups driver to send shutdown command to the upsd to shutdown the computer when I set up on the UPS via telnet that it should restart gracefully. The communication otherwise works perfectly but the gracefull restarts and turn off. Using apcsmart
2015 Sep 18
2
[HCL] Micropower LCD 1000 supported by blazer_usb
Device web page http://www.samurai-power.com/samurai-smart-1000-lcd UPS is marked as Micropower LCD 1000, but in Slovenia is remarked as Samurai LCD 1000 [ups] driver = blazer_usb port = auto vendorid = 0001 productid = 0000 upsc ups Init SSL without certificate database battery.charge: 100 battery.voltage: 27.40 battery.voltage.high: 26.00 battery.voltage.low: 20.80 battery.voltage.nominal:
2009 Aug 09
1
New NUT HCL entry / (brand)Inform (series)Informer Compact
Hi Mutlu, 2009/8/7 Mutlu T. <cmtunc at gmail.com> > Redirecting to debian.org domain due to being rejected as spam by free.fr > > > ------- Forwarded message ------- > From: "Mutlu T." <cmtunc at gmail.com> > To: arnaud.quette at free.fr > Cc: > Subject: New NUT HCL entry / (brand)Inform (series)Informer Compact > Date: Fri, 07 Aug 2009 15:31:04
2009 Mar 28
1
APCUPSD port 3551 permission problem
I need a little help on this problem, please? I include my /etc/apcupsd/apcupsd.conf file is attached. port 3551 udp/tcp has been added to the (running) firewall. My APC is recognized as: APC Back-UPS 450 FW:844.Kld.D USB FW:Kld This from the hardware browser. PS says: root 2419 0.0 0.0 4196 584 ? Ss Mar23 0:09 /sbin/apcupsd -f /etc/apcupsd/apcupsd.conf Is group 2419 the
2013 Jan 29
0
APC SmartUPS 1500 (USB) does not report OL/OB state
Hi, I have the following system configuration (probably does not matter, but anyway): Ubuntu Linux x86 VM running under ESXi bare metal hypervisor. UPS is connected to the ESXi host, and VM communicates to the UPS using USB pass through option. Details of elaborated shutdown sequence are out of topic, so I skip them. NUT was installed from the package, I believe it is recent enough. NUT was set
2006 Dec 21
2
Specs for Powercom Kingpro UPSes!
Hey all, I found a pinout of powercom's Kingpro UPSes in their manual. http://www.powercom-ups.com/manuals/kingpro.pdf Page 11. Unfortunately, this doesn't give PROTOCOL details. Does anyone have a "first step" at how to decode that? (for example, how to gauge line speed, how to "snoop" the serial port under windows? (for which the only software exists right
2020 Jun 22
2
Runtime testing
So, a while back I got around to ordering replacement batteries for my CyberPower PR3000LCDRTXL2U. When they arrived, I went to swap them in. I was horrified at the flimsiness of CyberPower's battery "trays". I've seen heavier gauge plastic on "blister" packages in the store. I ALSO discovered that the expansion unit had been shipped to me with one of its two
2020 Apr 23
0
Low battery unexpected shutdown
Hello. Battery, battery, battery. I am only thinking at worn batteries. I recently had the same symptoms with an hp/eaton g3 1500va. One of the 3 batteries was reading a healthy 12.8v, but when put under load it would quickly drain. I would measure each battery and test them under load, like with a car headlight bulb switched on both fillaments. On Thu, 23 Apr 2020, 16:54 Marc Franquesa,