2018 Sep 01
0
Adding drivers to NUT?
...even though MGE Office Protection Systems has been part of Eaton since
circa 2007, with, as far as I can remember, their products no longer
branded as MGE).
Maybe, we will reconsider this in future, if we rewrite the driver
from scratch, or if we decide to rename all the drivers with a leading
'nutdrv_'...
I extrapolated the (non-cosmetic) changes you made and applied them to
the metasys driver, apart from the removal of the devices with an 'id
code' < 14.
Speaking of that, since you removed them: do they support the command
you added (battery SOC, #8)? If not, we should make it o...
2018 Sep 03
0
Adding drivers to NUT?
...' field of the load.off.delay and
> > load.on.delay instant commands?
>
> Keor PDU is a commercial name for a Rack UPS, in the USB_DEVICE() macro I tried to add a small description, I don't know if it's enough for you, what kind of comment would you like?
>
> Regarding nutdrv_qx the only VID:PID combo is for one family: "Legrand Daker DK+ 1kVA / 2kVA / 3kVA / 5kVA / 6kVA / 10kVA". This could be the description.
> The items were Static, so I changed the file accordingly, i also added the DEFAULT_ONDELAY and DEFAULT_OFFDELAY. Probably i forgot it in a first ti...
2018 Jul 26
5
Adding drivers to NUT?
...aid, users can always set their own values for
'battery.voltage.{high,low}' and fine-tune calculations.
Plus, we can always add a note here or there and recommend using
certain values to have a slightly less inaccurate estimate for a given
device.
See:
- https://networkupstools.org/docs/man/nutdrv_qx.html#_battery_charge
- the various 'default.battery.*' and 'override.battery.*' items,
'runtimecal', 'chargetime' and 'idleload', here:
https://networkupstools.org/docs/man/nutdrv_qx.html#_extra_arguments
If you still can't find acceptable values, and...