Displaying 20 results from an estimated 28 matches for "lutti".
Did you mean:
tutti
2017 Jun 16
3
Help with Elite 800VA usb UPS
...the startup procedure in rc.local file, everything is
fine...
I have only to make a deep test.
Is there a way to add a NOTIFYMSG value for the battery test?
Thank you lots
Andrea
2017-06-16 14:50 GMT+02:00 Charles Lepple <clepple at gmail.com>:
> On Jun 16, 2017, at 2:20 AM, Andrea de Lutti <adelutti at gmail.com> wrote:
> > Using 'guestimation' (low: -0.866667, high: -1.083333)!
> > Initial battery charge undetermined
> > Driver failed to start (exit status=1)
>
> The "low" and "high" voltages should correspond to the battery...
2017 Jun 12
2
Help with Elite 800VA usb UPS
Thanks a lot, I will do it and keep you informed.
Best regards
Andrea
2017-06-12 12:34 GMT+02:00 Manuel Wolfshant <wolfy at nobugconsulting.ro>:
> On 06/12/2017 12:56 PM, Andrea de Lutti wrote:
>
>
>
>> > I have also successfully tested the battery...
>> >
>> > upscmd -uadmin -pups Elit at artu test.battery.start.quick
>>
>> I would also recommend testing the shutdown procedure and making sure
>> that everything works as expect...
2017 Jun 16
2
Help with Elite 800VA usb UPS
...ing 'guestimation' (low: -0.866667, high: -1.083333)!
Initial battery charge undetermined
Driver failed to start (exit status=1)
What should I do?
Thanks again,
Andrea
2017-06-12 12:34 GMT+02:00 Manuel Wolfshant <wolfy at nobugconsulting.ro>:
> On 06/12/2017 12:56 PM, Andrea de Lutti wrote:
>
>
>
>> > I have also successfully tested the battery...
>> >
>> > upscmd -uadmin -pups Elit at artu test.battery.start.quick
>>
>> I would also recommend testing the shutdown procedure and making sure
>> that everything works as expect...
2017 Jun 27
2
Help with Elite 800VA usb UPS
On Jun 26, 2017, at 7:03 AM, Andrea de Lutti <adelutti at gmail.com> wrote:
>
> Are there no warnings for battery test?
not sure if you saw my reply on 2016-06-17:
Do you mean a notification that a test is in progress, or something for the results?
There is the REPLBATT message in upsmon when the battery test fails, but I don&...
2017 Jun 12
3
Help with Elite 800VA usb UPS
>
> > root at artu:~# upsc Elit at artu
> > Init SSL without certificate database
> > battery.voltage: 13.90
> > battery.voltage.high: -1.08
> > battery.voltage.low: -0.87
> > device.type: ups
> > driver.name: blazer_usb
> > driver.parameter.pollinterval: 2
> > driver.parameter.port: auto
> > driver.version: 2.7.2
> >
2017 Jun 14
0
Help with Elite 800VA usb UPS
...tion unavailable
No values provided for battery high/low voltages in ups.conf
Using 'guestimation' (low: -0.866667, high: -1.083333)!
Initial battery charge undetermined
Driver failed to start (exit status=1)
What should I do?
Thanks again,
Andrea
2017-06-12 17:34 GMT+02:00 Andrea de Lutti <adelutti at gmail.com>:
> Thanks a lot, I will do it and keep you informed.
> Best regards
>
> Andrea
>
> 2017-06-12 12:34 GMT+02:00 Manuel Wolfshant <wolfy at nobugconsulting.ro>:
>
>> On 06/12/2017 12:56 PM, Andrea de Lutti wrote:
>>
>>
>>...
2017 Jul 05
1
Help with Elite 800VA usb UPS
Thank you lots! Finally I have everything working!
Which are the ups.status I can use with ups in dummy mode?
I have seen only OB, LB, OL...
thank you
Andrea
2017-07-04 19:55 GMT+02:00 Charles Lepple <clepple at gmail.com>:
> On Jul 3, 2017, at 11:06 AM, Andrea de Lutti <adelutti at gmail.com> wrote:
> >
> > ?I would like that NOTIFYCMD points to upssched?.
> >
> If I understand correctly, Roger is pointing out that your configuration
> is confusing upssched and upssched-script.
>
> Since you are using Ubuntu, upsmon.conf should...
2017 Jun 26
0
Help with Elite 800VA usb UPS
...EXEC
NOTIFYFLAG REPLBATT SYSLOG+WALL+EXEC
NOTIFYFLAG NOCOMM SYSLOG+WALL+EXEC
NOTIFYFLAG NOPARENT SYSLOG+WALL+EXEC
and enabled my email script:
NOTIFYCMD /root/mailnotify.sh
This is my working script:
#!/bin/sh
echo "$UPSNAME in is $NOTIFYTYPE state" | mailx -v -r "adelutti at gmail.com"
-s "$NOTIFYTYPE" -S smtp="smtp.gmail.com:587" -S smtp-use-starttls -S
smtp-auth=login -S smtp-auth-user="adelutti at gmail.com" -S
smtp-auth-password="mypassword" -S ssl-verify=ignore
adelutti+server at gmail.com;
Are there no warnings for...
2017 Jul 03
3
Help with Elite 800VA usb UPS
>
>
>
> MONITOR dummy at artu 1 user pass master
>> SHUTDOWNCMD "/sbin/shutdown -h +0"
>> NOTIFYCMD /usr/local/bin/upssched-script
>>
>
> Hi, As far as I can see, what you are getting in syslog corresponds
> correctly to what you have specified. You have specified that upsmon is to
> call upssched-script _directly_. This means that the argument
2017 Jun 07
2
Help with Elite 800VA usb UPS
Hi, I have tried several drivers for make my Elite UPS working.
With blazer_usb I can contact it, but I have no informations. This is the
best result.
OS: Ubuntu Xenial 16.04.2 LTS
NUT Version: Nut 2.7.2-4Ubuntu1 (Installed from Ubuntu Software Center)
Device name: Elite UPS 800VA (http://www.elit-ups.com/ita/pro_ups.html,
discontinued) I can provider their *not working* linux monitoring tool
2017 Jun 27
2
Help with Elite 800VA usb UPS
On Jun 27, 2017, at 9:23 AM, Andrea de Lutti <adelutti at gmail.com> wrote:
>
> Sorry, I didn't received it...
You should be subscribed to the list now.
> I don't have any REPLBATT message
Right, you would only get REPLBATT messages when the UPS reports that the battery *needs to be replaced* (and then at regular in...
2017 Jun 08
2
Help with Elite 800VA usb UPS
..." result:
root at artu:~# upsc ups at localhost
Init SSL without certificate database
Error: Unknown UPS
Trying with nutdrv_qx, protocol megatec the driver does not start...
2017-06-08 14:47 GMT+02:00 Charles Lepple <clepple at gmail.com>:
> On Jun 7, 2017, at 12:54 AM, Andrea de Lutti <adelutti at gmail.com> wrote:
> >
> >
> > Hi, I have tried several drivers for make my Elite UPS working.
> > With blazer_usb I can contact it, but I have no informations. This is
> the best result.
> >
> > OS: Ubuntu Xenial 16.04.2 LTS
> > NUT Ve...
2017 Jun 29
2
Help with Elite 800VA usb UPS
On Jun 29, 2017, at 6:52 AM, Andrea de Lutti wrote:
>>> Anyway I still not receive any email on any test (power cord disconnected and/or reconnected for example)
>>
>> Oh, I misinterpreted "working script" as a script that was sending email, rather than work-in-progress. Does that same command work from the com...
2017 Jul 03
2
Help with Elite 800VA usb UPS
...SLOG+WALL+EXEC
NOTIFYFLAG SHUTDOWN SYSLOG+WALL+EXEC
NOTIFYFLAG REPLBATT SYSLOG+WALL+EXEC
NOTIFYFLAG NOCOMM SYSLOG+WALL+EXEC
NOTIFYFLAG NOPARENT SYSLOG+WALL+EXEC
The upssched-script is
#! /bin/sh
case "$1" in
"ONBATT")
echo "On batt" | mailx -v -r "adelutti at gmail.com" -s "TEST NUT
object" -S smtp="smtp.gmail.com:587" -S smtp-use-starttls -S
smtp-auth=login -S smtp-auth-user="adelutti at gmail.com" -S
smtp-auth-password="gtmtnqyelhlumyds" -S ssl-verify=ignore
adelutti+server at gmail.com
;;
&q...
2017 Jun 11
3
Help with Elite 800VA usb UPS
So....seems so better...
Each time I rebbot, I miss the /var/run/nut folder...
root at artu:~# upsdrvctl start
Network UPS Tools - UPS driver controller 2.7.2
Network UPS Tools - Megatec/Q1 protocol USB driver 0.11 (2.7.2)
Can't chdir to /var/run/nut: No such file or directory
Driver failed to start (exit status=1)
root at artu:~# upsd
Network UPS Tools upsd 2.7.2
fopen
2017 Jun 08
0
Help with Elite 800VA usb UPS
On Jun 7, 2017, at 12:54 AM, Andrea de Lutti <adelutti at gmail.com> wrote:
>
>
> Hi, I have tried several drivers for make my Elite UPS working.
> With blazer_usb I can contact it, but I have no informations. This is the best result.
>
> OS: Ubuntu Xenial 16.04.2 LTS
> NUT Version: Nut 2.7.2-4Ubuntu1 (Installed...
2017 Jun 09
0
Help with Elite 800VA usb UPS
On Jun 8, 2017, at 9:15 AM, Andrea de Lutti <adelutti at gmail.com> wrote:
>
> Thank you for your reply Charles,
> this is the "upsc" result:
>
> root at artu:~# upsc ups at localhost
> Init SSL without certificate database
> Error: Unknown UPS
>
Use the name from ups.conf in front of "@localho...
2017 Jun 12
0
Help with Elite 800VA usb UPS
On 06/12/2017 12:56 PM, Andrea de Lutti wrote:
>
>
> > I have also successfully tested the battery...
> >
> > upscmd -uadmin -pups Elit at artu test.battery.start.quick
>
> I would also recommend testing the shutdown procedure and making sure
> that everything works as expected on pow...
2017 Jun 16
0
Help with Elite 800VA usb UPS
On Jun 16, 2017, at 2:20 AM, Andrea de Lutti <adelutti at gmail.com> wrote:
> Using 'guestimation' (low: -0.866667, high: -1.083333)!
> Initial battery charge undetermined
> Driver failed to start (exit status=1)
The "low" and "high" voltages should correspond to the battery voltage when it is disch...
2017 Jun 27
0
Help with Elite 800VA usb UPS
...r do I
have to change it manually? Which would be the right procedure for changing
the battery for calibrating NUT (over the manufacturer's suggestions)?
Thank you lots,
Andrea
2017-06-27 14:50 GMT+02:00 Charles Lepple <clepple at gmail.com>:
> On Jun 26, 2017, at 7:03 AM, Andrea de Lutti <adelutti at gmail.com> wrote:
> >
> > Are there no warnings for battery test?
>
> not sure if you saw my reply on 2016-06-17:
>
> Do you mean a notification that a test is in progress, or something for
> the results?
>
> There is the REPLBATT message in upsmo...