2017 Jun 04
0
[HCL] Cyber Power Systems CP1500AVRLCDa supported by usbhid-ups
...136.0          139.0
> 121.7   122.1        121            136.0          120.0
This is starting to come back to me - I think we saw this with several other CPS devices.
Here's an excerpt from the CP1500AVRLCDa HID descriptor:
Collection(Physical)
    Report ID(16)
        Usage(LowVoltageTransfer)
        Logical Minimum(97)
        Logical Maximum(103)
        Feature(Data,Variable,Absolute)
        Usage(LowVoltageTransfer)
        Input(Constant,Variable,Absolute)
        Usage(HighVoltageTransfer)
        Logical Minimum(136)
        Logical Maximum(142)
        Feature(Data,Variable,...
2018 Sep 01
0
Adding drivers to NUT?
...In case, we should signal that in 'device.type'.
Now, just a few questions on the mapping:
1. Are the following items read-only?
   And do they change from time to time and need to be polled, or once
retrieved they remain the same (i.e. they are static)?
   - input.transfer.low / UPS.Input.LowVoltageTransfer
   - input.transfer.high / UPS.Input.HighVoltageTransfer
   - input.transfer.low / UPS.PowerConverter.Output.LowVoltageTransfer
   - input.transfer.high / UPS.PowerConverter.Output.HighVoltageTransfer
   - battery.charge.warning / UPS.PowerSummary.WarningCapacityLimit
   - battery.charge.low / UPS....
2017 Jun 03
2
[HCL] Cyber Power Systems CP1500AVRLCDa supported by usbhid-ups
On 5/30/2017 10:47 PM, Charles Lepple wrote:
> On May 22, 2017, at 11:13 AM, Mike <the.lists at mgm51.com> wrote:
>>
>> On 5/21/2017 10:39 AM, Charles Lepple wrote:
[snip]
> Even though the CPS sub-driver has been written already, I would like to take a look at the raw "explore" mode output:
> 
>
2006 Sep 08
3
newhidups with APC Smart-UPS 1500
Hello,
I'm using the stable amd64 port of Debian Linux. I installed (the 
latest) nut-2.0.1-4 and nut-usb packages for utilizing an APC Smart-UPS 
1500 USB. I tried "apcupsd" first but "nut" makes an even more 
sophisticated impression on me and has more security options.
I had problems with the newhidups driver. It didn't find a device with 
matching VendorID. And
2018 Sep 03
0
Adding drivers to NUT?
...t; >
> > Now, just a few questions on the mapping:
> > 1. Are the following items read-only?
> >    And do they change from time to time and need to be polled, or once
> > retrieved they remain the same (i.e. they are static)?
> >    - input.transfer.low / UPS.Input.LowVoltageTransfer
> >    - input.transfer.high / UPS.Input.HighVoltageTransfer
> >    - input.transfer.low / UPS.PowerConverter.Output.LowVoltageTransfer
> >    - input.transfer.high / UPS.PowerConverter.Output.HighVoltageTransfer
> >    - battery.charge.warning / UPS.PowerSummary.WarningCapa...
2006 Sep 22
1
Ablerex 625L USB version
...IC HID 0.1
Network UPS Tools: 0.28 USB communication driver 0.28 - core 0.30 
(2.1.0)
Path: 00860004.Flow.FlowID, Type: Feature, Value: 0.000000
Path: 00860004.Flow.ConfigVoltage, Type: Feature, Value: 0.000000
Path: 00860004.Flow.ConfigFrequency, Type: Feature, Value: 0.000000
Path: 00860004.Flow.LowVoltageTransfer, Type: Feature, Value: 0.000000
Path: 00860004.Flow.HighVoltageTransfer, Type: Feature, Value: 0.000000
Path: 00860004.Flow.iManufacturer, Type: Feature, Value: 0.000000
Path: 00860004.Flow.iProduct, Type: Feature, Value: 0.000000
Path: 00860004.Flow.iSerialNumber, Type: Feature, Value: 0.000000
Pa...
2006 Oct 18
2
newhidups with APC Smart-UPS 1500
...: Input, Value: 230.000000
> > Path: UPS.Output.ConfigVoltage, Type: Feature, Value: 230.000000
> > Path: UPS.Output.HighVoltageTransfer, Type: Input, Value: 253.000000
> > Path: UPS.Output.HighVoltageTransfer, Type: Feature, Value: 
> > 253.000000
> > Path: UPS.Output.LowVoltageTransfer, Type: Input, Value: 208.000000
> > Path: UPS.Output.LowVoltageTransfer, Type: Feature, Value: 
> > 208.000000
> > Path: UPS.Output.APCDelayBeforeStartup, Type: Input, Value: 0.000000
> > Path: UPS.Output.APCDelayBeforeStartup, Type: Feature, Value: 
> > 0.000000
>...
2006 Nov 11
1
Help with newhidups subdriver for Dynex UPS
...s., Type: Feature
Path: UPS.PowerSummary.AudibleAlarmControl, Type: Feature, Value: 2.000000
Path: UPS.PowerSummary.iManufacturer, Type: Feature, Value: 3.000000
Path: UPS.Input.ConfigVoltage, Type: Feature, Value: 120.000000
Path: UPS.Input.Voltage, Type: Feature, Value: 120.000000
Path: UPS.Input.LowVoltageTransfer, Type: Feature, Value: 90.000000
Path: UPS.Input.HighVoltageTransfer, Type: Feature, Value: 140.000000
Path: UPS.Output.Voltage, Type: Feature, Value: 120.000000
Path: UPS.Output.PercentLoad, Type: Feature, Value: 92.000000
Path: UPS.Output.Test, Type: Feature, Value: 1.000000
Path: UPS.Output.Dela...
2018 Jul 26
5
Adding drivers to NUT?
Dear Daniele,
nice to meet you, I'm a collegue of Gabriele.
The problem with "blazer_usb" driver ("blazer_ser" works correctly) is related to the following commands:
- "F" and "I": when the KRAULER subdriver check these UPS answers it uses wrong constants to check the lenght of the received packets, so these commands are considered as "not
2014 Mar 24
2
Incorrect Values From usbhid-ups
...ature,
ReportID: 0x0d, Offset: 0, Size: 8, Value: 3
   0.263390     Path: UPS.Input.ConfigVoltage, Type: Feature,
ReportID: 0x0e, Offset: 0, Size: 8, Value: 120
   0.263488     Path: UPS.Input.Voltage, Type: Feature, ReportID:
0x0f, Offset: 0, Size: 16, Value: 119
   0.263575     Path: UPS.Input.LowVoltageTransfer, Type: Feature,
ReportID: 0x10, Offset: 0, Size: 16, Value: 88
   0.263585     Path: UPS.Input.LowVoltageTransfer, Type: Input,
ReportID: 0x10, Offset: 0, Size: 16, Value: 88
   0.263593     Path: UPS.Input.HighVoltageTransfer, Type: Feature,
ReportID: 0x10, Offset: 16, Size: 16, Value: 139
   0...
2005 Oct 02
3
more on 2.0.3-pre
Gentlemen,
I have now had a chance to run some initial tests of my changes to
apc-hid.c of the current development tree. Running newhipups and 
inspecting the -DDDD output seems to indicate that with the fix below
everything seems to work as expected. However, I have not yet shut
my system in order to take the UPS out of action so that I can do my
various tests with a lightbulb load. I still hope
2014 Jun 06
0
Question about voltage threshold setting in NUT
Hello Charles,
Thank you for your reply.
For the discrete value thing, this morning I did try to run
sudo upsrw -s input.transfer.low=x -u * -p * ups
I changed "x" value from 60 to 96 then checked upsc result. All the script
return OK but only 84 and 96 got picked up and working.
Out model is Eaton 3S 500. And in windows it has a Eaton Personal Solution
Pac. In Battery transfer
2014 Jun 06
2
Question about voltage threshold setting in NUT
On Jun 5, 2014, at 10:53 PM, Charles Lepple wrote:
> As you have seen, the "default.*" and "overwrite.*" names are not actual variables: they are configuration options to change what is returned from upsc. That is why you get VAR-NOT-SUPPORTED.
typo; should have been "override.*"
-- 
Charles Lepple
clepple at gmail
2007 Jan 26
1
newhidups output for Geek Squad GS1285U
...s., Type: Feature
Path: UPS.PowerSummary.AudibleAlarmControl, Type: Feature, Value: 2.000000
Path: UPS.PowerSummary.iManufacturer, Type: Feature, Value: 3.000000
Path: UPS.Input.ConfigVoltage, Type: Feature, Value: 120.000000
Path: UPS.Input.Voltage, Type: Feature, Value: 123.000000
Path: UPS.Input.LowVoltageTransfer, Type: Feature, Value: 90.000000
Path: UPS.Input.HighVoltageTransfer, Type: Feature, Value: 140.000000
Path: UPS.Output.Voltage, Type: Feature, Value: 123.000000
Path: UPS.Output.PercentLoad, Type: Feature, Value: 0.000000
Path: UPS.Output.Test, Type: Feature, Value: 1.000000
Path: UPS.Output.Delay...
2016 Dec 03
2
Problem installing NUT on 16.04
...ature, 
ReportID: 0x0d, Offset: 0, Size: 8, Value: 3
    0.133070    Path: UPS.Input.ConfigVoltage, Type: Feature, ReportID: 
0x0e, Offset: 0, Size: 8, Value: 120
    0.133141    Path: UPS.Input.Voltage, Type: Feature, ReportID: 0x0f, 
Offset: 0, Size: 16, Value: 129
    0.133228    Path: UPS.Input.LowVoltageTransfer, Type: Feature, 
ReportID: 0x10, Offset: 0, Size: 16, Value: 88
    0.133233    Path: UPS.Input.LowVoltageTransfer, Type: Input, 
ReportID: 0x10, Offset: 0, Size: 16, Value: 88
    0.133238    Path: UPS.Input.HighVoltageTransfer, Type: Feature, 
ReportID: 0x10, Offset: 16, Size: 16, Value: 139...
2006 Feb 10
1
newhidups capture - Atlantis-Land HID UPS
Hello Charles!
   As promised, I just checked out the CVS and recompiled everything. In 
the attached .txt is what is coming out from my UPS. I am wondering 
about all those zeroes.
Also, this morning I plan to connect the UPS to a Win box running the 
monitoring program supplied with the UPS (UPSilon2000) and a USB sniffer 
program. If you have any suggestions on what to look for in the data, 
2005 Jul 26
1
Some newhidups questions
...bytes) => 28 06 96 0C 8C     == ??
  UPS.APC860018.Input                   (2 bytes) => 30 78              == 120
  UPS.APC860018.ConfigVoltage           (2 bytes) => 31 74              == 116
  UPS.APC860018.Voltage                 (2 bytes) => 32 58              == 88
  UPS.APC860018.LowVoltageTransfer      (2 bytes) => 33 8B              == 139
  UPS.APC860018.HighVoltageTransfer     (2 bytes) => 34 B1              == 177
  UPS.APC860018.APC860024               (2 bytes) => 35 02              == 2
  UPS.APC860018.APC860061               (2 bytes) => 36 00              == 0
  UPS.APC8...
2020 Oct 21
1
Can't get CyberPower UPS to work with Raspberry Pi 4
...urer, Type: Feature, ReportID:
0x0d, Offset: 0, Size: 8, Value: 3
   0.033910 Path: UPS.Input.ConfigVoltage, Type: Feature, ReportID: 0x0e,
Offset: 0, Size: 8, Value: 120
   0.034656 Path: UPS.Input.Voltage, Type: Feature, ReportID: 0x0f, Offset:
0, Size: 16, Value: 120
   0.035409 Path: UPS.Output.LowVoltageTransfer, Type: Feature, ReportID:
0x10, Offset: 0, Size: 16, Value: 100
   0.035450 Path: UPS.Output.LowVoltageTransfer, Type: Input, ReportID:
0x10, Offset: 0, Size: 16, Value: 100
   0.035487 Path: UPS.Output.HighVoltageTransfer, Type: Feature, ReportID:
0x10, Offset: 16, Size: 16, Value: 139
   0.035523...
2019 Jun 11
2
UPS shuts down on NUT boot with low battery [APS Back-UPS RS 550G]
...x28, Offset: 0, Size: 32, Value: -1.34135e+09
>    0.072280   Path: UPS.Input.ConfigVoltage, Type: Feature, ReportID: 0x30, Offset: 0, Size: 8, Value: 230
>    0.072912   Path: UPS.Input.Voltage, Type: Feature, ReportID: 0x31, Offset: 0, Size: 16, Value: 235
>    0.073536   Path: UPS.Input.LowVoltageTransfer, Type: Feature, ReportID: 0x32, Offset: 0, Size: 16, Value: 176
>    0.074160   Path: UPS.Input.HighVoltageTransfer, Type: Feature, ReportID: 0x33, Offset: 0, Size: 16, Value: 282
>    0.074783   Path: UPS.Input.ff860024, Type: Feature, ReportID: 0x34, Offset: 0, Size: 16, Value: 128
>...
2019 Jun 11
0
UPS shuts down on NUT boot with low battery [APS Back-UPS RS 550G]
...et: 0, Size: 32, Value: -1.34135e+09
>>   0.072280   Path: UPS.Input.ConfigVoltage, Type: Feature, ReportID: 0x30, Offset: 0, Size: 8, Value: 230
>>   0.072912   Path: UPS.Input.Voltage, Type: Feature, ReportID: 0x31, Offset: 0, Size: 16, Value: 235
>>   0.073536   Path: UPS.Input.LowVoltageTransfer, Type: Feature, ReportID: 0x32, Offset: 0, Size: 16, Value: 176
>>   0.074160   Path: UPS.Input.HighVoltageTransfer, Type: Feature, ReportID: 0x33, Offset: 0, Size: 16, Value: 282
>>   0.074783   Path: UPS.Input.ff860024, Type: Feature, ReportID: 0x34, Offset: 0, Size: 16, Value: 128
&g...