2011 Jul 19
2
KIN-1500AP RM + Windows 2008 64-bit Standard R2 SP1 (nut 2.6.1)
...AG ONLINE SYSLOG+WALL+EXEC
NOTIFYFLAG ONBATT SYSLOG+WALL+EXEC
NOTIFYFLAG LOWBATT SYSLOG+WALL+EXEC
RBWARNTIME 43200
NOCOMMWARNTIME 300
FINALDELAY 5
upssched.conf:
*
*
CMDSCRIPT /bin/upssched-cmd
AT ONBATT * START-TIMER onbattwarn 10
AT ONLINE * CANCEL-TIMER onbattwarn
AT LOWBATT * EXECUTE lowbattwarn
AT ONBATT * START-TIMER timeshutdown 100
AT ONLINE * CANCEL-TIMER timeshutdown
After start I can see couple neutral events:
upsd.exe - listening on 192.168.1.2 port 3493.
upsd.exe - User monuser at 192.168.1.2 logged into UPS [KIN1500].
Also, there are a lot of errors, such as "upsmon -...
2011 Jun 08
2
Misconfiguration of Windows MSI installer 2.6.0-1 with my Powerware 5115 connected via USB port
...YFLAG ONLINE SYSLOG+WALL+EXEC
NOTIFYFLAG ONBATT SYSLOG+WALL+EXEC
NOTIFYFLAG LOWBATT SYSLOG+WALL+EXEC
RBWARNTIME 43200
NOCOMMWARNTIME 300
FINALDELAY 5
*upssched.conf:*
CMDSCRIPT /bin/upssched-cmd
AT ONBATT * START-TIMER onbattwarn 10
AT ONLINE * CANCEL-TIMER onbattwarn
AT LOWBATT * EXECUTE lowbattwarn
AT ONBATT * START-TIMER timeshutdown 100
AT ONLINE * CANCEL-TIMER timeshutdown
There are huge count of windows events such as "upsmon - Poll UPS [
PW5115 at 192.168.1.12] failed - Data stale."
Can anyone help me to get right configs?
Thanks
-------------- next part --------------
An...
2013 Jun 28
2
How to Simulate UPS on battery?
...using 10 seconds to reduce
the testing time)
Here's the upssched.conf for S2:
$ cat /usr/local/etc/nut/upssched.conf
CMDSCRIPT /usr/local/sbin/upssched-cmd.sh
PIPEFN /var/run/upssched/upssched.pipe
LOCKFN /var/run/upssched/upssched.lock
AT LOWBATT * START-TIMER lowbattwarn 1
AT ONBATT * START-TIMER onbattwarn 10
AT ONLINE * CANCEL-TIMER onbattwarn
And here is the upsmon.conf on S2:
$ cat /usr/local/etc/nut/upssched.conf
RUN_AS_USER _ups
MONITOR PW5125 at s1.EXAMPLE.COM 1 monuser tHEuNSPOKENpSWD slave
MIN...
2017 May 14
2
[HCL] Cyber Power Systems CP1500AVRLCDa supported by usbhid-ups
...60 on the number of seconds given by the command. That is why
the request for a 59 second delay resulted in no delay at all.
===
I see the same behavior with this model.
The following command excerpts from the upssched.conf file work as expected:
AT LOWBATT ups2 at 127.0.0.1 START-TIMER ups2-lowbattwarn 1
AT ONBATT ups2 at 127.0.0.1 START-TIMER ups2-onbatt-early 60
AT ONBATT ups2 at 127.0.0.1 START-TIMER ups2-onbatt-final 180
AT ONBATT ups2 at 127.0.0.1 EXECUTE ups2-start-batt
AT ONLINE ups2 at 127.0.0.1 CANCEL-TIMER ups2-onbatt-early
AT ONLINE ups2 at 127.0.0.1 CANCEL-TIM...