search for: l1152

Displaying 3 results from an estimated 3 matches for "l1152".

Did you mean: 1152
2018 May 07
4
Tripp Lite SU5000RT3U
Hi, I am trying to configure my Tripp Lite SU5000RT3U on Ubuntu 18.04 as I am not able to completely get all the data from the UPS. After installing all required packages from the Ubuntu repos (had to run sudo apt-get install dkms, I had to install the displaylink drivers from displaylink.org by doing sudo ./displaylink-driver-4.2.29.run, and I created a sim link by doing the following: sudo ln
2018 May 08
0
Tripp Lite SU5000RT3U
...39; command. > ups.debug.P: 30 35 30 30 0d 00 00 '0500...' > ups.debug.S: 31 34 30 30 30 30 0d '140000.' Status '4' means that a battery test hasn't been done recently. Other values here: https://github.com/networkupstools/nut/blob/v2.7.4/drivers/tripplite_usb.c#L1152-L1180 > ups.debug.T: 39 31 32 35 37 31 0d '912571.' 0x257 = 599 = 59.9 Hz; the following '1' indicates a nominal value of 60 Hz. You might be able to extract temperature from the first two digits. > ups.debug.V: 33 30 38 38 0d 00 00 '3088...' > You would also w...
2018 May 09
0
Tripp Lite SU5000RT3U
...0d 00 00 '0500...' >>> ups.debug.S: 31 34 30 30 30 30 0d '140000.' >> >> Status '4' means that a battery test hasn't been done recently. Other values here: >> >> https://github.com/networkupstools/nut/blob/v2.7.4/drivers/tripplite_usb.c#L1152-L1180 >> >>> ups.debug.T: 39 31 32 35 37 31 0d '912571.' >> >> 0x257 = 599 = 59.9 Hz; the following '1' indicates a nominal value of 60 Hz. You might be able to extract temperature from the first two digits. >> >>> ups.debug.V: 33 30 38 3...