ups.test.result meaning
I'm going to guess that since your test runtime of 305 is very close to the low limit of 300, that's the warning. Not yet a fail, but very, very close. On October 31, 2020 11:41:39 AM CDT, Rick Dicaire <kritek at gmail.com> wrote: >Hi folks, new to list... >nut 2.7.2 on Ubuntu 16.04 with Cyberpowersystems CP1350PFCLCD. > >After performing upscmd cp1350 at localhost test.battery.start.quick the >result was "Done and warning". I searched through syslog but could find no >addi...
2020 Oct 31
2
ups.test.result meaning
Hi folks, new to list... nut 2.7.2 on Ubuntu 16.04 with Cyberpowersystems CP1350PFCLCD. After performing upscmd cp1350 at localhost test.battery.start.quick the result was "Done and warning". I searched through syslog but could find no additional information. What is the warning? Battery charge was 100% before test was performed. Here's the full output from upsc after test:
2020 Nov 01
4
ups.test.result meaning
On Sat, Oct 31, 2020 at 2:42 PM Tim Dawson <tadawson at tpcsvc.com> wrote: > I'm going to guess that since your test runtime of 305 is very close to > the low limit of 300, that's the warning. Not yet a fail, but very, very > close. > I tried setting override.battery.runtime.low = 60 in ups.conf, and waited for the UPS to reach 100% charge, and ups.status to report only
2020 Nov 01
1
ups.test.result meaning
> > > > battery.voltage: 16.0 > At that voltage, 5 of the 12 cells are shorted > > output.voltage: 138.0 > too high by about 15 volts > > Wow! That battery is beyond toasted, shoulda been replaced months ago. > And the output voltage is a bit much if its truthfull. > Thanks for the response Gene! I've ordered a replacement unit. I'm not sure about the