search for: kin1500ap

Displaying 15 results from an estimated 15 matches for "kin1500ap".

2009 Dec 27
4
XPCC XVRT-1000 driver
-----BEGIN PGP SIGNED MESSAGE----- Hash: SHA1 Has anyone used nut with a XPCC UPS, in particular one of the XVRT units? Their supplied monitoring tool "works", but I'd really prefer to use nut if possible. I've systematically gone through each of the drivers in /lib/nut and none seem to talk with the unit properly. I'll be talking with a XPCC support person tomorrow, though
2007 Nov 06
1
BNT-1000AP
Hi guys, We've got a BNT-1000AP (powercom) BlackKnight UPS that works with the KIN1500AP model in the powercom driver. Well, almost. It seems the input frequency and the battery charge is swapped around: # upsc blackknight at localhost battery.charge: 46.5 driver.name: powercom driver.parameter.manufacturer: BlackKnight driver.parameter.modelname: BNT-1000AP driver.parameter.port:...
2006 Aug 17
1
powercom upstype identify problem
...om the notifyme script does not have the permission to execute. Currently the output of "upsc Inform@localhost" when the UPS is connected to the mains is: battery.charge: 97.7 driver.name: powercom driver.parameter.linevoltage: 220 driver.parameter.port: /dev/ttyS0 driver.parameter.type: KIN1500AP driver.version: 2.0.4 driver.version.internal: $ Revision: 0.5 $ input.frequency: 49.61 input.voltage: 236.3 input.voltage.nominal: 220 output.frequency: 49.61 output.voltage: 236.3 ups.load: 36.7 ups.mfr: PowerCom ups.model: Unknown ups.model.type: KIN1500AP ups.serial: Unknown ups.status: OL and...
2006 Aug 17
0
(no subject)
So, this is the result of upsc Inform@localhost with the UPS connected to the mains: battery.charge: 97.7 driver.name: powercom driver.parameter.linevoltage: 220 driver.parameter.port: /dev/ttyS0 driver.parameter.type: KIN1500AP driver.version: 2.0.4 driver.version.internal: $ Revision: 0.5 $ input.frequency: 49.61 input.voltage: 236.3 input.voltage.nominal: 220 output.frequency: 49.10 output.voltage: 236.3 ups.load: 38.9 ups.mfr: PowerCom ups.model: Unknown ups.model.type: KIN1500AP ups.serial: Unknown ups.status: OL and...
2005 Aug 19
1
Sustainer S-1000C (Powercom protocol)
...;>>>| Serial Port: /dev/ttyS0 | | Comm. Status: Conn. | | Press Ctrl_C to Exit UPSMON Plus Display Program!! Nevertheless, I haven't managed to make NUT work with it. When I tried using the powercom driver, I got the following response, no matter which type I entered (including the KIN1500AP I've seen on the wayback machine had the same problem - http://web.archive.org/web/20041020015206/lists.exploits.org/ups/Jan2004/00003.html): # upsdrvctl start Network UPS Tools - UPS driver controller 2.0.1 Network UPS Tools - PowerCom and similars protocol UPS driver $ Revision: 0.5 $ (2.0...
2005 Jul 30
0
Sustainer S-1000C
...| | Press Ctrl_C to Exit UPSMON Plus Display Program!! Nevertheless, I haven't managed to make NUT work with it. When I tried using the powercom driver, I got the following response, no matter which type I entered (including the KIN1500AP I've seen on the wayback machine had the same problem - http://web.archive.org/web/20041020015206/lists.exploits.org/ups/Jan2004/00003.html): # upsdrvctl start Network UPS Tools - UPS driver controller 2.0.1 Network UPS Tools - PowerCom and similars protocol UPS driver $ Revision: 0.5 $ (2.0...
2006 Aug 18
0
(no subject)
...quency: 0.00 input.voltage: -0.1 input.voltage.nominal: 220 output.frequency: 49.10 output.voltage: 57.6 ups.load: 5.8 ups.mfr: PowerCom ups.model: Unknown ups.model.type: KIN525AP ups.serial: Unknown ups.status: OB root@marto:/home/marto# /usr/local/ups/bin/powercom -DD -u root -a Inform -x type=KIN1500AP Network UPS Tools - PowerCom and similars protocol UPS driver $ Revision: 0.5 $ (2.0.4) debug level is '2' Values of arguments: manufacturer : 'PowerCom' model name : 'Unknown' serial number : 'Unknown' line voltage :...
2005 Jul 06
0
Powercom BNT-1500AP
Hey all, Does anybody know there is a full working setup for the PowerCom BNT-1500AP. I got some stuff working with the Powercom driver and the type set to "KIN1500AP". But it seems that there is still missing usablity. I was wondering if anybody found any better configs? ---- excerpt of ups.conf [AVR1500] driver = powercom port = /dev/ttyS0 desc = "PowerCom BNT-1500AP" modelname = "BNT-1500AP"...
2006 Apr 21
1
Powercom BNT-1200AP
Hello I have UPS Powercom Black Knight Pro 1200 (BNT-1200AP) I try to use nut, but powercom driver not understand my model Ok, i try to use type KIN1500AP and it's work But powercom driver can't set UPS's shutdown delay time Also i have powercom's original program (upsmon), and this program can do it What can i do for help to add this function to nut's powercom driver? For example may be i can see logs of work upsmon with COM-po...
2006 Aug 16
5
Master privileges unavailable on UPS, no access :(
...mon[7731]: Master privileges unavailable on UPS [Inform@localhost] Aug 16 14:11:09 marto upsmon[7731]: Reason: Access denied Can you tell me where my error is, my configuration files are: ups.conf: [Inform] driver = powercom port = /dev/ttyS0 desc = "inform guard" linevoltage = 220 type = KIN1500AP upsd.conf: ACL all 0.0.0.0/0 ACL localhost 127.0.0.1/32 ACCEPT localhost REJECT all ups.users: root password = pwd allowfrom = localhost actions = SET instcmds = ALL marto password = pwd allowfrom = localhost upsmon master upsmon.conf: MONITOR Inform@localhost 1 marto pwd master Thank you very mu...
2006 Dec 11
2
howto setup BNT-1500AP on gentoo
...has passed successfully. I use UPS POWERCOM BNT-1500AP. It is connected to serial port 1, i.e. for my system it/dev/tts/0. In/etc/nut/ups.conf [powercom] driver = powercom port = /dev/tts/0 desc = "PowerCom BNT-1500AP on IP-PBX" modelname = "BNT-1500AP" linevoltage = 230 type = KIN1500AP also trying: [powercom] driver = powercom port = /dev/tts/0 desc = "PowerCom BNT-1500AP on IP-PBX" modelname = "BNT-1500AP" linevoltage = 230 type = Egys At start by a command/etc/init.d/upsdrv start gives out the following: * Starting UPS drivers ... Network UPS Tools - U...
2006 Jul 08
0
Powercom BNT-600AP and NUT (powercom driver)
Hello, I'm new there. I bought an UPS Powercom BNT-600AP. It's compatible in NUT with driver powercom and protocol type KIN1500AP. But I have a simple problem: the 'upsc' shows wrong values in battery.charge (maybe in other rows also /ups.load, voltages?/) - if battery is 100% charged it shows only 92.6% or 93.0%. I thing I have wrong values in driver parameters: batteryPercentage, loadPercentage, etc. I tried put the...
2007 Oct 04
0
Powercom black knight 800AP (serial)
Hi, Nut versions: 2.2.0 and 2.0.2 (powercom -x type=KIN1500AP -x linevoltage=220) I've got the above mentioned serial UPS and have found some problems using it. 1) under linux 2.6.12 select() timed out on reading the serial port in NONBLOCK mode. Not sure about this one, seems most likely a kernel problem, since it's working OK in 2.6.20. But on...
2005 Dec 30
2
BNT600AP
Hi, I have a little problem with PowerCom BNT600AP after running driver I see: root@rask> powercom -D /dev/ttyS1 Network UPS Tools - PowerCom and similars protocol UPS driver $ Revision: 0.5 $ (2.0.2) debug level is '1' Values of arguments: manufacturer : 'PowerCom' model name : 'Unknown' serial number : 'Unknown' line
2006 Aug 17
2
powercom UPS shoutdown discussion
Thank you for your response. The point is that I have configured my system to shut down at the event "upsc Inform@localhost ups.status"!="OL", not at "LB". So there will be no /etc/killpower file created. At an ups.status != "OL" event, the following script named "notifyme" is run: echo `date` >> /root/upsLog echo " No power, shutting