Displaying 4 results from an estimated 4 matches for "karandreas".
2020 Sep 03
0
UPS reboots with APC UPS
On Thu, 3 Sep 2020, stefanos at karandreas.gr wrote:
> battery.charge.low: 30
> ups.delay.shutdown: 20
>
> I am trying to understand what controls/triggers the UPS reboot signal.
> 1. Have had the UPS reboot while on power and 100% battery when manually
> restarting M1 for updates taking down both M1 (during boot, so th...
2020 Sep 03
1
UPS reboots with APC UPS
> On 2020-09-03 18:29, Roger Price wrote:
> NUT is designed to
>
> 1. Power off the system attached to the UPS when some criteria is
> reached, eg. status [LB]
>
> 2. Some time later, in your case ups.delay.shutdown = 20 seconds, the
> UPS shuts down its power outlets.
>
I see, I wasn't aware of that part.
While that holds true for the 1st example-case I stated
2020 Sep 03
2
UPS reboots with APC UPS
Hello,
I have been using NUT for a short period of time and have some questions
regarding the UPS reboot signal that I can't figure out. Have tried some
googling and reading the DOCs but I am struggling to understand how some
variables / things are supposed to work, so would appreciate any help
with any of the following questions.
I am running NUT on standalone mode on a linux machine
2023 Jan 13
1
Support of PowerWalker CSW / GXB series
Hello,
can anyone comment on how well these ups work with NUT and which is the
preferred driver?
I haven't found much information in the mailing list, seems blazer_usb,
nutdrv_qx etc work (sometimes)?
Specifically I am looking at Powerwalker VI 1200 CSW and Powerwalker VI
1500 GXB models.