APC UPS BR550GI continuously rebooting and workaround
...ill start again and supplies power to the load.
11. and repeats steps 7 onwards.
Workaround: I modified halt to start the nut driver again(upsdrvctl start)
before root partition goes read-only. Once I did that the UPS did not
transfer to battery (step 8).
Driver Debug output: http://pastebin.com/GgLHq1AM
UPSC:
battery.charge: 100
battery.charge.low: 89
battery.charge.warning: 50
battery.date: 2001/09/25
battery.mfr.date: 2010/11/24
battery.runtime: 51900
battery.runtime.low: 120
battery.type: PbAc
battery.voltage: 14.1
battery.voltage.nominal: 12.0
device.mfr: American Power Conversion
device.mode...