1
Return on experience with an Emerson/Liebert GXT3
Hi
On 10/03/2014 03:42 PM, Charles Lepple wrote:> On Oct 3, 2014, at 7:50 AM, paul.chavent at fnac.net wrote:
>
>
> This is what I was referring to (from the belkin-hid log):
>
>???? 1.325782??? Report[buf]: (5 bytes) => 05 53 00 48 00
>???? 1.325799??? Path: UPS.PowerSummary.ConfigVoltage, Type: Feature, ReportID: 0x05, Offset: 16, Size: 16, Value: 0
>???? 1.325814???...
2014 Oct 03
1
Return on experience with an Emerson/Liebert GXT3
Hi
On 10/02/2014 02:39 PM, Charles Lepple wrote:> On Oct 1, 2014, at 9:03 PM, paul.chavent at fnac.net wrote:
>
>>> It should run as user "nut" in Debian. You may want to reinstall the nut-server package, and check the post-inst error messages to make sure that the "nut" user is created, and that it is in the "nut" group as well.
>>
>> The u...
2014 Oct 01
3
Return on experience with an Emerson/Liebert GXT3
Hi.
I would like to share with you my experience on trying to use nut with a Liebert GXT3 on a Debian wheezy with nut-server 2.6.4.
Please find my observations below.
(1) I've installed the packaged version of nut-server
# aptitude install nut-server
(2) I did some tuning for my configuration
#??cat << EOF >> /etc/nut/ups.conf
user=nut
[liebert]
??????? driver=usbhid-ups
2014 Oct 10
1
Return on experience with an Emerson/Liebert GXT3
Hi
On 10/06/2014 03:04 PM, Charles Lepple wrote:> I think I see what is going on.
>
>???? 0.368670??? Report[buf]: (5 bytes) => 05 4e 00 48 00
>???? 0.368698??? PhyMax = 0, PhyMin = 0, LogMax = 1, LogMin = 0
>???? 0.368723??? Unit = 00000000, UnitExp = 0
>???? 0.368747??? Exponent = 0
>???? 0.368776??? Path: UPS.PowerSummary.Voltage, Type: Feature, ReportID: 0x05, Offset:
2014 Oct 02
0
Return on experience with an Emerson/Liebert GXT3
> https://github.com/networkupstools/nut/issues/138
> That issue also includes an override setting, so if I can't get any other testers, I plan to merge it as-is.
Ok, great.
> It should run as user "nut" in Debian. You may want to reinstall the nut-server package, and check the post-inst error messages to make sure that the "nut" user is created, and that it is