battery not installed, but battery still 100% and NUT 2.7.2-4 does not catch this and report a error
2017 Apr 04
4
battery not installed, but battery still 100% and NUT 2.7.2-4 does not catch this and report a error
2017-04-04 14:18 GMT+02:00 Jon Bendtsen <jon.bendtsen at jonix.dk>:
> On 04/04/17 14.10, Roger Price wrote:
>
>> On Tue, 4 Apr 2017, Arnaud Quette wrote:
>>
>>
> [cuuuuut]
>
> Hi Arnaud, It seems to me that, looking out into the future, there are
>> three
>> things upsmon needs:
>>
>> 1. A fall-through <notify type> of "UNKNOWN" so that all status changes,
>> no
>> matter how wierd, can be caught. Such a cat...
battery not installed, but battery still 100% and NUT 2.7.2-4 does not catch this and report a error
2017 Apr 10
2
battery not installed, but battery still 100% and NUT 2.7.2-4 does not catch this and report a error
On 10/04/17 15.25, Jon Bendtsen wrote:
> On 04/04/17 15.19, Arnaud Quette wrote:
>>
>>
>> 2017-04-04 14:18 GMT+02:00 Jon Bendtsen <jon.bendtsen at jonix.dk
>> <mailto:jon.bendtsen at jonix.dk>>:
[cuuuuut]
> I'd say your change is a success :-)
well, almost, but maybe that is outside NUT's control.
/usr/lib/nagios/plugins/check_ups -H dkvideobackup -u apc1500
UPS OK - Status=Online, Unknown Utility=227.5V Batt=100.0% Load=0.0%
|voltage=227500mV;;;0 battery=100%;;;0;100 load=0%;;;0;10...
battery not installed, but battery still 100% and NUT 2.7.2-4 does not catch this and report a error
2017 Apr 10
0
battery not installed, but battery still 100% and NUT 2.7.2-4 does not catch this and report a error
On 04/04/17 15.19, Arnaud Quette wrote:
>
>
> 2017-04-04 14:18 GMT+02:00 Jon Bendtsen <jon.bendtsen at jonix.dk
> <mailto:jon.bendtsen at jonix.dk>>:
[cuuuuut]
>
> there is a Github issue: https://github.com/networkupstools/nut/issues/415
> + a branch with the implementation:
> https://github.com/networkupstools/nut/tree/upsmon_alarm
>
> For now:
> - upsmon can react on the ALARM notify type, as with other events, and
> WALL+SYS...
battery not installed, but battery still 100% and NUT 2.7.2-4 does not catch this and report a error
2017 Apr 04
2
battery not installed, but battery still 100% and NUT 2.7.2-4 does not catch this and report a error
On Tue, 4 Apr 2017, Arnaud Quette wrote:
> Hi Jon, Stuart and the list
>
> 2017-04-04 1:09 GMT+02:00 Stuart Gathman <stuart at gathman.org>:
> Which NOTIFYCMD is run when there is an ALARM?
> Have you specified that in your upsmon.conf?
>
> And that is the question of the hour.? How do you specify that?? Note
> that this is not the REPLBATT
battery not installed, but battery still 100% and NUT 2.7.2-4 does not catch this and report a error
2017 Apr 04
0
battery not installed, but battery still 100% and NUT 2.7.2-4 does not catch this and report a error
On 04/04/17 14.10, Roger Price wrote:
> On Tue, 4 Apr 2017, Arnaud Quette wrote:
>
[cuuuuut]
> Hi Arnaud, It seems to me that, looking out into the future, there are three
> things upsmon needs:
>
> 1. A fall-through <notify type> of "UNKNOWN" so that all status changes, no
> matter how wierd, can be caught. Such a catch-all <notify type> would also...
battery not installed, but battery still 100% and NUT 2.7.2-4 does not catch this and report a error
2017 Apr 10
0
battery not installed, but battery still 100% and NUT 2.7.2-4 does not catch this and report a error
...17 16.39, Jon Bendtsen wrote:
> On 10/04/17 15.25, Jon Bendtsen wrote:
>> On 04/04/17 15.19, Arnaud Quette wrote:
>>>
>>>
>>> 2017-04-04 14:18 GMT+02:00 Jon Bendtsen <jon.bendtsen at jonix.dk
>>> <mailto:jon.bendtsen at jonix.dk>>:
>
> [cuuuuut]
>
>
>> I'd say your change is a success :-)
>
> well, almost, but maybe that is outside NUT's control.
>
> /usr/lib/nagios/plugins/check_ups -H dkvideobackup -u apc1500
> UPS OK - Status=Online, Unknown Utility=227.5V Batt=100.0% Load=0.0%
> |voltage=227500mV;...
2009 May 20
2
upsmon shutdown based on Time since power fail.
For various reasons - I have been trying to get my Desktops and/or
servers to shut-down a fixed time after a power fail - or better still a
fixed time - or a low battery whichever comes first.
I note in my upsc:
*> upsc belkinusb*
battery.charge: 100
battery.charge.low: 30
battery.charge.warning: 30
battery.runtime: 120
battery.type: PbAc
battery.voltage: 27.3
battery.voltage.nominal: 24