2017 Apr 04
4
battery not installed, but battery still 100% and NUT 2.7.2-4 does not catch this and report a error
2017-04-04 14:18 GMT+02:00 Jon Bendtsen <jon.bendtsen at jonix.dk>: > On 04/04/17 14.10, Roger Price wrote: > >> On Tue, 4 Apr 2017, Arnaud Quette wrote: >> >> > [cuuuuut] > > Hi Arnaud, It seems to me that, looking out into the future, there are >> three >> things upsmon needs: >> >> 1. A fall-through <notify type> of "UNKNOWN" so that all status changes, >> no >> matter how wierd, can be caught. Such a cat...
2017 Apr 10
2
battery not installed, but battery still 100% and NUT 2.7.2-4 does not catch this and report a error
On 10/04/17 15.25, Jon Bendtsen wrote: > On 04/04/17 15.19, Arnaud Quette wrote: >> >> >> 2017-04-04 14:18 GMT+02:00 Jon Bendtsen <jon.bendtsen at jonix.dk >> <mailto:jon.bendtsen at jonix.dk>>: [cuuuuut] > I'd say your change is a success :-) well, almost, but maybe that is outside NUT's control. /usr/lib/nagios/plugins/check_ups -H dkvideobackup -u apc1500 UPS OK - Status=Online, Unknown Utility=227.5V Batt=100.0% Load=0.0% |voltage=227500mV;;;0 battery=100%;;;0;100 load=0%;;;0;10...
2017 Apr 10
0
battery not installed, but battery still 100% and NUT 2.7.2-4 does not catch this and report a error
On 04/04/17 15.19, Arnaud Quette wrote: > > > 2017-04-04 14:18 GMT+02:00 Jon Bendtsen <jon.bendtsen at jonix.dk > <mailto:jon.bendtsen at jonix.dk>>: [cuuuuut] > > there is a Github issue: https://github.com/networkupstools/nut/issues/415 > + a branch with the implementation: > https://github.com/networkupstools/nut/tree/upsmon_alarm > > For now: > - upsmon can react on the ALARM notify type, as with other events, and > WALL+SYS...
2017 Apr 04
2
battery not installed, but battery still 100% and NUT 2.7.2-4 does not catch this and report a error
On Tue, 4 Apr 2017, Arnaud Quette wrote: > Hi Jon, Stuart and the list > > 2017-04-04 1:09 GMT+02:00 Stuart Gathman <stuart at gathman.org>: > Which NOTIFYCMD is run when there is an ALARM? > Have you specified that in your upsmon.conf? > > And that is the question of the hour.? How do you specify that?? Note > that this is not the REPLBATT
2017 Apr 04
0
battery not installed, but battery still 100% and NUT 2.7.2-4 does not catch this and report a error
On 04/04/17 14.10, Roger Price wrote: > On Tue, 4 Apr 2017, Arnaud Quette wrote: > [cuuuuut] > Hi Arnaud, It seems to me that, looking out into the future, there are three > things upsmon needs: > > 1. A fall-through <notify type> of "UNKNOWN" so that all status changes, no > matter how wierd, can be caught. Such a catch-all <notify type> would also...
2017 Apr 10
0
battery not installed, but battery still 100% and NUT 2.7.2-4 does not catch this and report a error
...17 16.39, Jon Bendtsen wrote: > On 10/04/17 15.25, Jon Bendtsen wrote: >> On 04/04/17 15.19, Arnaud Quette wrote: >>> >>> >>> 2017-04-04 14:18 GMT+02:00 Jon Bendtsen <jon.bendtsen at jonix.dk >>> <mailto:jon.bendtsen at jonix.dk>>: > > [cuuuuut] > > >> I'd say your change is a success :-) > > well, almost, but maybe that is outside NUT's control. > > /usr/lib/nagios/plugins/check_ups -H dkvideobackup -u apc1500 > UPS OK - Status=Online, Unknown Utility=227.5V Batt=100.0% Load=0.0% > |voltage=227500mV;...
2009 May 20
2
upsmon shutdown based on Time since power fail.
For various reasons - I have been trying to get my Desktops and/or servers to shut-down a fixed time after a power fail - or better still a fixed time - or a low battery whichever comes first. I note in my upsc: *> upsc belkinusb* battery.charge: 100 battery.charge.low: 30 battery.charge.warning: 30 battery.runtime: 120 battery.type: PbAc battery.voltage: 27.3 battery.voltage.nominal: 24