UPS not Shutting Down
...th
# the -h option and/or read the driver's documentation.
offdelay = 120
ondelay = 240
[pve1]
driver = "usbhid-ups"
port = "auto"
vendorid = "06DA"
productid = "FFFF"
desc = "Phoenixtec Power Co., Ltd Innova Unity"
serial = "CPANM2436540037"
override.battery.charge.low = 70
override.battery.runtime.low = 2500
# wait 5 minutes for ups to power off
override.ups.delay.shutdown = 300
On Sat, 1 Jun 2024 at 19:12, Jim Klimov <
jimklimov+nut_at_gmail.com_chribonn at duck.com> wrote:
> Thinking of it, one purpose of up...
2024 Jun 02
0
UPS not Shutting Down
...ondelay = 240
> >
> > [pve1]
> > driver = "usbhid-ups"
> > port = "auto"
> > vendorid = "06DA"
> > productid = "FFFF"
> > desc = "Phoenixtec Power Co., Ltd Innova Unity"
> > serial = "CPANM2436540037"
> > override.battery.charge.low = 70
> > override.battery.runtime.low = 2500
> > # wait 5 minutes for ups to power off
> > override.ups.delay.shutdown = 300
>
> I don't see the line
>
> lowbatt = 70
>
> which you need to make a permanent...
2024 Jun 02
0
UPS not Shutting Down
...ondelay = 240
> >
> > [pve1]
> > driver = "usbhid-ups"
> > port = "auto"
> > vendorid = "06DA"
> > productid = "FFFF"
> > desc = "Phoenixtec Power Co., Ltd Innova Unity"
> > serial = "CPANM2436540037"
> > override.battery.charge.low = 70
> > override.battery.runtime.low = 2500
> > # wait 5 minutes for ups to power off
> > override.ups.delay.shutdown = 300
>
> I don't see the line
>
> lowbatt = 70
>
> which you need to make a permanent...