search for: cp1350

Displaying 3 results from an estimated 3 matches for "cp1350".

Did you mean: cp1250
2020 Oct 31
2
ups.test.result meaning
Hi folks, new to list... nut 2.7.2 on Ubuntu 16.04 with Cyberpowersystems CP1350PFCLCD. After performing upscmd cp1350 at localhost test.battery.start.quick the result was "Done and warning". I searched through syslog but could find no additional information. What is the warning? Battery charge was 100% before test was performed. Here's the full output from ups...
2020 Oct 31
0
ups.test.result meaning
...since your test runtime of 305 is very close to the low limit of 300, that's the warning. Not yet a fail, but very, very close. On October 31, 2020 11:41:39 AM CDT, Rick Dicaire <kritek at gmail.com> wrote: >Hi folks, new to list... >nut 2.7.2 on Ubuntu 16.04 with Cyberpowersystems CP1350PFCLCD. > >After performing upscmd cp1350 at localhost test.battery.start.quick the >result was "Done and warning". I searched through syslog but could find no >additional information. > >What is the warning? > >Battery charge was 100% before test was performed. &gt...
2020 Nov 01
3
ups.test.result meaning
On Oct 31, 2020, at 8:30 PM, Gene Heskett <gheskett at shentel.net> wrote: > >> battery.voltage: 16.0 > At that voltage, 5 of the 12 cells are shorted >> battery.voltage.nominal: 24 The 16.0 is a scaled version of the fixed (bogus) 24.0 V reading, similar to this unit: https://networkupstools.org/ddl/Cyber_Power_Systems/CP1500PFCLCD.html I think we even