search for: built_bi

Displaying 2 results from an estimated 2 matches for "built_bi".

Did you mean: built_by
2024 Dec 16
1
NUT on FBSD 14-2 fails to shut down UPS - select with socket: Invalid argument
I'm still digging into this but thought I'd post what I have so far in case there's a known issue that's easily fixed. I'm using the version of NUT that's in the ports tree (see the info at the bottom). Using the SNMP drivers to talk with two ACP SmartUPSs. NUT is functional about monitoring and initiating host shutdown. However, when it comes time to shut down the UPSs
2024 Dec 17
1
NUT on FBSD 14-2 fails to shut down UPS - select with socket: Invalid argument
Hello, Thanks for the report and sorry about any complications. A few first questions: * is this setup known to have been working with earlier NUT releases (e.g. same OS and devices, older NUT - can try with a custom build of older tags)? Is this a regression, or we never knew the correct mappings for timeouts and/or shutdown commands used by this model? * is there the `select` error when