Displaying 3 results from an estimated 3 matches for "belkinups".
Did you mean:
belkinunv
2014 Feb 11
2
error: Unknown UPS
Hi all,
I've got nut going with a Belkin F6C120auUNV. I'm able to communicate
with the UPS, upsc gives data:
$ sudo upsc BelkinUPS
battery.charge: 37
battery.charge.low: 30
battery.charge.warning: 30
battery.runtime: 120
battery.type: PbAc
battery.voltage: 23.7
...
I've enabled the CGI, and when I go to upsstats.cgi, I see a line entry
like this:
System: BelkinUPS
Model: [error: Unknown UPS] (light blue background)
Statu...
2014 Feb 11
0
error: Unknown UPS
On Feb 11, 2014, at 6:52 AM, Greg Vickers wrote:
> hosts.conf:
> MONTIOR admin at localhost "BelkinUPS"
The second field is upsname at hostname (rather than username at hostname).
Along these lines, the third field is descriptive only, and doesn't need to match anything (e.g. "Belkin UPS at the bottom of the rack")
--
Charles Lepple
clepple at gmail
2007 Apr 27
1
success report with megatec and Belkin F6H650UkUNV (was: Success report with network UPS tools)
...quirk was the during the deep battery test, the machine
was shut down by upsmon before the deep discharge test completed,
although I cannot really complain since that was just over an hour on
batteries! The output below was taken whilst the UPS was still
recovering.
[root@root ups]# bin/upsc belkinups@localhost
battery.charge: 65.0
battery.voltage: 12.30
battery.voltage.nominal: 12.0
driver.name: megatec
driver.parameter.port: /dev/ttyS0
driver.version: 2.0.5
driver.version.internal: 1.5
input.frequency: 50.0
input.voltage: 241.0
input.voltage.fault: 241.0
input.voltage.maximum: 243.0
input.volt...