Displaying 2 results from an estimated 2 matches for "baudhunt".
2007 Apr 17
1
HP R3000 XR, warning or perhaps error
Hi,
So far I've gleaned heaps of useful info from the list and got mostly
running with NUT. There was a thread by Paul Battaglia and Kjell
Claesson about the R3000 which has helped me get so far, but now with
the patched driver I still have this on startup:
# /usr/local/ups/bin/upsdrvctl start
Network UPS Tools - UPS driver controller 2.0.5
Network UPS Tools - BCMXCP UPS driver 0.11
2005 Sep 28
1
Re: Hardware Compatibility list - HP R3000 XR ups
Hi Matthijs,
> Arnaud.
>After some trial and error, i found out that the HP R3000 XR ups's we have
>can be used with Network Ups Tools.
>This using the bcmxcp driver.
>
>Note that in the code of this driver (line 1420) , the Baudrate is fixed to
>9600 baud.
>to connect to a serial HP R3000 XR ups one needs to change this to 19200
>baud.
>
>ideally, this should