2009 Oct 24
1
Shutdown N-POWER MV-1000 LT UPS is not working
...0 SP1.
I downloaded, compiled and configured diver nut 2.4.1 from this link
http://www.networkupstools.org/source/2.4/nut-2.4.1.tar.gz
Here are my configuration files:
---
srv:/usr/local/ups # cat etc/ups.conf
[npower]
driver = megatec
port = /dev/ttyS0
desc = "Srv"
battvolts = 1.8:2.1
battvoltmult = 18
lowbatt = 10
srv:/usr/local/ups #
----
srv:/usr/local/ups # cat etc/upsd.conf
LISTEN 127.0.0.1
LISTEN 192.168.0.10
srv:/usr/local/ups #
---
srv:/usr/local/ups # cat etc/upsmon.conf
#
RUN_AS_USER ups
MONITOR npower at localhost 1 admin karamba master
MINSUPPLIES 1
SHUTDOWNCMD "/usr/local...
2012 May 10
3
battery.charge and other fixes needed for X-Power Tigra 1kVA
...99,999,041.1,50.0,035,030
So I disabled this bundled software and installed the windows version
NUT-Installer-2.6.3-3.msi, without the libusb option (since I had a
serial UPS)
In ups.conf I used the following
[ups1]
driver = bestups
port = com1
id = 610,1000,230,230,10.0,36.0
nombattvolt=41.1
battvoltmult = 18
With regard to the id option, the 2nd, 3rd and 4th options seemed ok.
Not sure about the fifth (10.0). And definitely not sure about the last
(36.0). I used 36.0 because the Best 610-1000 lists 36V as the DC bus
voltage. Not sure if that is correct or not. According to specs (
http://www....
2012 Jan 09
1
bestups bug fix
hi all,
really simple fix for the bestups driver:
In function:
upsdrv_makevartable()
you need to add the line
addvar(VAR_VALUE, "battvoltmult", "Battery voltage multiplier");
There are a number of simple improvements I could make to this driver, but I'm assuming that since the above bug has been around since nut v2.4, not many people are using this driver.
Is this driver worth improving?
-Sadara
2010 Mar 16
1
NUT megatec driver tunning
...e end - part of my config (ups.conf), needed for correct working
> and displayed data with my UPS.
>
> [sinapse]
> ? ? ? ?driver = megatec
> ? ? ? ?port = /dev/ttyu0
> ? ? ? ?desc = "Sinapse 6000"
> ? ? ? ?sendpace=10 ? ? ? ? ? ? # or less, but not more 10
> ? ? ? ?battvoltmult=108 ? ? ? ?# for same as on LCD-display on UPS device
> ? ? ? ?battvolts=1.90:2.2400
> _____________________________________________________
>
> RESULTS:
>
> proxy# ./megatec -DDD -a sinapse
> Network UPS Tools - Megatec protocol driver 1.6 (2.4.1)
> debug level is '3...
2008 Oct 06
4
UPS (Megatec) with strange voltage values
Hello Nut List!
I have 2 "Lacerda 10KVA" UPS that returns strange values for Q1 and F
commands:
Q1
(215.0 215.0 219.0 004 60.0 2.27 39.0 00000001
F
#220.0 045 240.0 60.0
At least what I know about Megatec, It seems to say that it has a 240.0 V
battery with currently 2.27V. Quite strange.
I contacted Lacerda to help me interpret this values and they said that 2.27
is just 1 element