Logic problem in NUT with upscode2 driver
Hi All,
I have what is probably a 12 year old (or older) Compaq R3000 UPS
plugged into a FreeBSD 8 system running NUT version 2.6.5
This UPS contains a total of 16 batteries in 2 banks of 8,
each battery is 6 volts and the bank produces 50 volts.
The UPS monitors battery voltage and the battery charger in
the UPS works like this. For about 2 days it will apply a
charge/float/topping
2014 Nov 03
0
RFC: new variable battery.status (was: [PATCH] upscode2: Report ABM Status)
...PS are
- * applicable to battery charge, but they usually aren't */
+ * applicable to battery charge, but they usually aren't, cause high is a UPS internal and/or battery
+ * ABSOLUTE MAXIMUM RATING, not reported as "nominal" value, the upscode2 spec maybe wrong. */
else if (batt_volt_low > 0 && batt_volt_high > 0 && batt_volt > 0) {
- if (batt_volt > batt_volt_high) {
+ if (batt_volt > batt_volt_rs) {
chg=100;
}
else if (batt_volt < batt_volt_low) {
@@ -1399,7 +1401,7 @@
}
else {
chg = (batt_volt - batt_volt_low) /
-...
2012 Feb 13
3
RFC: new variable battery.status (was: [PATCH] upscode2: Report ABM Status)
2012/2/6 thomas schorpp <thomas.schorpp at googlemail.com>:
> Hi,
Hi Thomas,
> I want the driver report the battery status from ABM charging controllers
> -patch attached- :
thanks for your patch.
since it introduces a new variable (battery.status.abm), I prefer to
step back and think to something useful more widely.
thus, I'm thinking about a generic
2014 Nov 04
2
RFC: new variable battery.status
...le to battery charge, but they usually aren't */
> + * applicable to battery charge, but they usually aren't, cause high is
> a UPS internal and/or battery
> + * ABSOLUTE MAXIMUM RATING, not reported as "nominal" value, the
> upscode2 spec maybe wrong. */
> else if (batt_volt_low > 0 && batt_volt_high > 0 && batt_volt > 0) {
> - if (batt_volt > batt_volt_high) {
> + if (batt_volt > batt_volt_rs) {
> chg=100;
> }
> else if (batt_volt < batt_volt_low) {
> @@ -1399,7 +1401,7 @@
> }
> else {