2019 Sep 06
5
"battery is low" logged
I got around to unplugging my UPS and I found it doesn't last nearly as
long as estimated.
Is the "upsmon[1446]: UPS desktop_ups at localhost battery is low" logged
when "battery.runtime:" = "battery.runtime.low: 120"?
Does any make better batteries that don't go down faster when they get old?
battery.charge: 100
battery.charge.low: 10
2015 Sep 29
0
Nut v2.7.3 - how to force shutdown for a specifc ups only
...rced shutdown command
> to a specific UPS only.
It is possible - simply send a "shutdown.reboot" or "shutdown.stayoff" command via `upscmd`.
Other instant commands (which may or may not be implemented on your UPS):
http://www.networkupstools.org/docs/user-manual.chunked/apcs02.html
--
Charles Lepple
clepple at gmail
2015 Sep 30
0
Nut v2.7.3 - how to force shutdown for a specifc ups only
...a specific UPS only.
>
> It is possible - simply send a "shutdown.reboot" or "shutdown.stayoff"
> command via `upscmd`.
>
> Other instant commands (which may or may not be implemented on your UPS):
>
> http://www.networkupstools.org/docs/user-manual.chunked/apcs02.html
thank you, for your fast reply. It is never to later to learn new
things. I was so focused on the 'upsc -c fsd' command that I didn't
realize that there are other possible ways to solve my problem.
Regards
Juergen
--
Mail: juergen at eisfair.org
2016 Oct 06
0
UPS Shutdown
...opped.)
There are also ways to send shutdown commands to a running driver with "upscmd", which is useful for scenarios other than "shutdown and return when the power returns".
http://networkupstools.org/docs/man/upscmd.html
http://networkupstools.org/docs/user-manual.chunked/apcs02.html ("Instant commands")
2019 Sep 07
0
"battery is low" logged
...of the battery by periodically removing the power input and see how long
> it actually runs down to, say, 20%.
>
> Vendor software usually has a "test" feature, don't know if nut has this.
test.battery* instant commands: https://networkupstools.org/docs/user-manual.chunked/apcs02.html
(I don't know if test.panel.start is exactly the same.)
More detailed status is typically reported in the "ups.test.result" variable: https://networkupstools.org/docs/user-manual.chunked/apcs01.html
(The driver should pick up on this and also include "RB" (replace ba...
2012 Apr 14
2
running xcp (or xenserver) from usb driver or SD card
Hi,
Do you think it''s possible to run Xenserver/XCP or xen from an usb drive or
memory card like it''s possible for vmware please ? Is it recommended ? Are
there any performance issue :-) ? I would like to dedicate all of the
local storage to hosting VMs only.
Looking at xen/xenserver/xcp doc, i was wondering why there''s so few
tutorial on installing them on usb
2016 Oct 06
5
UPS Shutdown
> > How does this work in conjunction with the UPS hardware? Does NUT
> > immediately send a command to the UPS to wait for 300 seconds and then
> > shut itself down, thereby allowing the server enough time to safely
> > shut itself down as well?
>
> Yes.
Very good, thank you.
> The command is "upsdrvctl shutdown".
That's what I thought, but I
2012 Jun 16
15
Installing XCP from USB thumb drive
Has anyone experimented with installing XCP from a USB thumb drive? Is it possible? How was the installation media installed to the USB thumb drive (e.g., dd)?
Eric Pretorious
Truckee, CA
_______________________________________________
Xen-users mailing list
Xen-users@lists.xen.org
http://lists.xen.org/xen-users