search for: apcdelaybeforereboot

Displaying 12 results from an estimated 12 matches for "apcdelaybeforereboot".

2018 Aug 24
2
APC Back-UPS CS 650 offdelay and startdelay
...h was necessarily going to be different, just wanted to make sure you had everything set up to recompile. The real test is to see if things change after commenting out that line (such as by changing it to start with "//"): > > // { "shutdown.return", 0, 0, "UPS.Output.APCDelayBeforeReboot", NULL, "1", HU_TYPE_CMD, NULL }, > > For reference, here's the thread related to adding that mapping: https://alioth-lists.debian.net/pipermail/nut-upsuser/2011-January/006550.html > Hi I'm bit closer :) Acctually change "UPS.Output.APCDelayBeforeReboot" t...
2018 Aug 23
2
APC Back-UPS CS 650 offdelay and startdelay
W dniu 23.08.2018 o 02:16, Charles Lepple pisze: > > For some reason, this is being hardcoded to 1: > > drivers/apc-hid.c- /* used by APC BackUPS CS */ > drivers/apc-hid.c: { "shutdown.return", 0, 0, "UPS.Output.APCDelayBeforeReboot", NULL, "1", HU_TYPE_CMD, NULL }, > > Can you rebuild the NUT drivers as described here? https://github.com/networkupstools/nut/wiki/Building-NUT-on-Debian,-Raspbian-and-Ubuntu Ok, this is version from today github sync and compile (Ubuntu 18.04): Network UPS Tools - Generic H...
2018 Aug 22
2
APC Back-UPS CS 650 offdelay and startdelay
W dniu 22.08.2018 o 14:41, Charles Lepple pisze: > /lib/nut/usbhid-ups -a apc -DDD -k Please see attachement. -- Karol Olszewski ipflow.pl -------------- next part -------------- A non-text attachment was scrubbed... Name: APC_BackUPS_CS_650_fsd.log.gz Type: application/gzip Size: 5735 bytes Desc: not available URL:
2018 Aug 23
0
APC Back-UPS CS 650 offdelay and startdelay
On Aug 22, 2018, at 1:20 PM, Karol Olszewski <karol.olszewski at ipflow.pl> wrote: > > W dniu 22.08.2018 o 14:41, Charles Lepple pisze: >> /lib/nut/usbhid-ups -a apc -DDD -k > Please see attachement. 1.872180 Report[buf]: (2 bytes) => 40 00 1.872196 Path: UPS.Output.APCDelayBeforeReboot, Type: Feature, ReportID: 0x40, Offset: 0, Size: 8, Value: 0 [...] 1.872439 Initiating UPS shutdown 1.872455 upsdrv_shutdown... 1.872470 instcmd(shutdown.return, [NULL]) 1.884650 Report[set]: (2 bytes) => 40 01 For some reason, this is being hardcoded to 1: drivers/apc-hid.c- /* u...
2018 Aug 24
0
APC Back-UPS CS 650 offdelay and startdelay
...t ipflow.pl> wrote: > > W dniu 23.08.2018 o 02:16, Charles Lepple pisze: >> >> For some reason, this is being hardcoded to 1: >> >> drivers/apc-hid.c- /* used by APC BackUPS CS */ >> drivers/apc-hid.c: { "shutdown.return", 0, 0, "UPS.Output.APCDelayBeforeReboot", NULL, "1", HU_TYPE_CMD, NULL }, >> >> Can you rebuild the NUT drivers as described here? https://github.com/networkupstools/nut/wiki/Building-NUT-on-Debian,-Raspbian-and-Ubuntu > Ok, this is version from today github sync and compile (Ubuntu 18.04): > > Netwo...
2018 Aug 26
0
APC Back-UPS CS 650 offdelay and startdelay
W dniu 24.08.2018 o 23:13, Karol Olszewski pisze: > Hi > I'm bit closer :) > Acctually change "UPS.Output.APCDelayBeforeReboot" to > >   { "shutdown.return", 0, 0, "UPS.Output.APCShutdownAfterDelay", NULL, > "90", HU_TYPE_CMD, NULL }, > > Now, UPS turn off load after 90 sec, but not power ON when power is back > Dear nut users, Two APC Back-UPS CS 650 1) Firmware 817.v4...
2020 Sep 03
2
UPS reboots with APC UPS
...ID: 0x34, Offset: 0, Size: 8, Value: 129 0.709363 Path: UPS.Input.APCSensitivity, Type: Feature, ReportID: 0x35, Offset: 0, Size: 8, Value: 1 0.713331 Path: UPS.Input.APCLineFailCause, Type: Feature, ReportID: 0x36, Offset: 0, Size: 8, Value: 0 0.717383 Path: UPS.APCGeneralCollection.APCDelayBeforeReboot, Type: Feature, ReportID: 0x40, Offset: 0, Size: 8, Value: 0 0.720381 Path: UPS.APCGeneralCollection.APCDelayBeforeShutdown, Type: Feature, ReportID: 0x41, Offset: 0, Size: 16, Value: -1 0.726432 Path: UPS.APCGeneralCollection.DelayBeforeShutdown, Type: Feature, ReportID: 0x42, Offset: 0...
2019 Jun 11
2
UPS shuts down on NUT boot with low battery [APS Back-UPS RS 550G]
...: 0, Size: 16, Value: 128 > 0.075399 Path: UPS.Input.APCSensitivity, Type: Feature, ReportID: 0x35, Offset: 0, Size: 8, Value: 1 > 0.076023 Path: UPS.Input.APCLineFailCause, Type: Feature, ReportID: 0x36, Offset: 0, Size: 8, Value: 0 > 0.076649 Path: UPS.APCGeneralCollection.APCDelayBeforeReboot, Type: Feature, ReportID: 0x40, Offset: 0, Size: 8, Value: 0 > 0.077279 Path: UPS.APCGeneralCollection.APCDelayBeforeShutdown, Type: Feature, ReportID: 0x41, Offset: 0, Size: 16, Value: -1 > 0.077902 Path: UPS.APCGeneralCollection.DelayBeforeShutdown, Type: Feature, ReportID: 0x42,...
2019 Jun 11
0
UPS shuts down on NUT boot with low battery [APS Back-UPS RS 550G]
...: 16, Value: 128 >> 0.075399 Path: UPS.Input.APCSensitivity, Type: Feature, ReportID: 0x35, Offset: 0, Size: 8, Value: 1 >> 0.076023 Path: UPS.Input.APCLineFailCause, Type: Feature, ReportID: 0x36, Offset: 0, Size: 8, Value: 0 >> 0.076649 Path: UPS.APCGeneralCollection.APCDelayBeforeReboot, Type: Feature, ReportID: 0x40, Offset: 0, Size: 8, Value: 0 >> 0.077279 Path: UPS.APCGeneralCollection.APCDelayBeforeShutdown, Type: Feature, ReportID: 0x41, Offset: 0, Size: 16, Value: -1 >> 0.077902 Path: UPS.APCGeneralCollection.DelayBeforeShutdown, Type: Feature, ReportID:...
2010 Nov 07
3
Support of "shutdown.return" on a APC Back-UPS CS 500
Hi all, I am trying to get a APC Back-UPS CS 500 running on my QNAP 419P Nas. Since on all my work I figure out the following: from Network UPS Tools upscmd 2.4.1 [~] # upscmd -l qnapups Instant commands supported on UPS [qnapups]: beeper.disable - Disable the UPS beeper beeper.enable - Enable the UPS beeper beeper.mute - Temporarily mute the UPS beeper beeper.off - Obsolete (use
2009 Mar 13
7
Weird Load and Battery Temp Readings
I've acquired and installed NUT 2.4.1 on a D-Link DNS323 NAS. With exception of Load and Battery Temp readings all works well. A upsc ups at localhost command returns; battery.charge: 100 battery.charge.low: 10 battery.charge.warning: 50 battery.date: 2001/09/25 battery.mfr.date: 2008/06/05 battery.runtime: 2122 battery.runtime.low: 120 battery.temperature: 3022999999999998800 battery.type:
2012 Apr 09
2
libusb_get_report: Unknown error
...Type: Feature, ReportID: 0x27, Offset: 0, Size: 16, Value: -1 1.082458 Report[get]: (4 bytes) => 29 00 00 00 1.082466 Path: UPS.Output.DelayBeforeReboot, Type: Feature, ReportID: 0x29, Offset: 0, Size: 24, Value: 0 1.088457 Report[get]: (2 bytes) => 40 00 1.088466 Path: UPS.Output.APCDelayBeforeReboot, Type: Feature, ReportID: 0x40, Offset: 0, Size: 8, Value: 0 1.094471 Report[get]: (3 bytes) => 41 ff ff 1.094489 Path: UPS.Output.APCDelayBeforeShutdown, Type: Feature, ReportID: 0x41, Offset: 0, Size: 16, Value: -1 1.100480 Report[get]: (2 bytes) => 2e 05 1.100501 Path: UPS.iPro...