2010 Mar 02
3
Back to apcupsd
...found nothing in the logs.
However, when I kill -HUPped it, and restarted the service, the USB stuff
had stopped. Ok, one problem down.
The change battery light's still on. I'll see if it still is in the
morning. One thing I did note, while skimming the docs, and comparing my
results from apcaccess, was that while the nominal voltage for the APC
SmartUPS 3000 is 48V, the new batteries are showing 55.4V. Anyone have any
idea if this could be why the replace battery light's on - it's more than
5V difference?
      mark
2024 Aug 20
1
APC BX ...MI series
Peter Bell <peter at bellfamily.org.uk> writes:
> The problem I had with my BX950MI unit was that it was frequently
> reporting off-line, on batt and often not responding to requests from
> apcupsd (apcaccess) and then going back online again. However, the
> warranty replacement was prompted by a failed battery, apparently
> leaking acid, after around ten months use.? As a matter of interest, I
> had a problem a few years ago with battery failure on another APC
> (possibly a BX750 model?).?...
2024 Aug 20
1
APC BX ...MI series
Hi,
 ?Thank you for your prompt response!
The problem I had with my BX950MI unit was that it was frequently 
reporting off-line, on batt and often not responding to requests from 
apcupsd (apcaccess) and then going back online again. However, the 
warranty replacement was prompted by a failed battery, apparently 
leaking acid, after around ten months use.? As a matter of interest, I 
had a problem a few years ago with battery failure on another APC 
(possibly a BX750 model?).? After two like-f...
2005 Jul 09
1
apcsmart varibles
Hello,
I am working on getting NUT working with my Smart-UPS 900 UPS (with the C c=
able)
For several years, I have used the apcupsd product, but because of the
nagios support for nut, I am working on switching over.
Under apcupsd, I get tons of information from my UPS:
#  /usr/local/sbin/apcaccess status
DATE     : Sat Jul 09 12:56:41 CDT 2005
HOSTNAME : homer
RELEASE  : 3.8.6
UPSNAME  : UPS_IDEN
CABLE    : Custom Cable Smart
MODEL    : APC Smart-UPS 900
UPSMODE  : Net Master
STARTTIME: Sat Jul 09 12:55:48 CDT 2005
SHARE    : NetworkUPS
STATUS   : ONLINE
LINEV    : 112.8 Volts
LOADPCT  :  97...
2017 May 11
4
APC Back-UPS XS 1500G says "No battery"
I have a new-ish APC Back-UPS XS 1500G connected via USB. It's giving me 
a "ups.alarm: No battery installed!" error. I also installed and 
configured apcupsd to give that a try and it's giving me the same error.
I suspect this is a driver problem because while NUT claims the battery 
isn't plugged in, it's giving me battery runtime/charge info. Both can't 
be valid
2005 Jan 03
3
UPS - a little OT
Hi all.
Can someone recommend a good UPS for using with an * machine that
provides some linux tested software to do managed shutdown in case of
power loss?
Thanks.
Shoval Tomer,
IT Manager,
SofTov Advanced Systems, Ltd.
Office: +972-3-9230686 ext. 179
Fax: +972-3-9216642
Mobile: +972-54-8000200
2007 May 29
3
wich apc ups?
Hi,
I want to buy a UPS wfor a PE2800 but I'm mnot sure wich one to choose. is
1000 VA enough or do I need the 1500 VA version?
1) APC Smart-UPS 1000 VA Black SMART UPS 1000 VA BLACK 1000 VA
LINE-INTERACTIV [SUA1000I]
2)  Power Supply Apc-ups 1500va Floorstand Incl Control Cable Usb And Com
Port Output Power 980w
Other suggestions are also welcome As long as they can talk to the apcd
2024 Aug 20
1
APC BX ...MI series
On 20/08/2024 19:18, Greg Troxel wrote:
> Peter Bell<peter at bellfamily.org.uk> writes:
>
>> The problem I had with my BX950MI unit was that it was frequently
>> reporting off-line, on batt and often not responding to requests from
>> apcupsd (apcaccess) and then going back online again. However, the
>> warranty replacement was prompted by a failed battery, apparently
>> leaking acid, after around ten months use.? As a matter of interest, I
>> had a problem a few years ago with battery failure on another APC
>> (possibly a...
2017 May 12
0
APC Back-UPS XS 1500G says "No battery"
...;    0.571473     Unit = 00000000, UnitExp = 0 
>    0.571475     Exponent = 0
Both the Input and Feature seem to agree that the battery is not present. (0x04 -> 0000 0100 corresponds to "Offset: 2" and the "AC Present" bit; all others are zero.
> 
> user at host>apcaccess 
> APC      : 001,036,0870 
> DATE     : 2017-05-08 23:44:14 -0700 
> HOSTNAME : myhost 
> VERSION  : 3.14.14 (31 May 2016) debian 
> UPSNAME  : myups 
> CABLE    : USB Cable 
> DRIVER   : USB UPS Driver 
> UPSMODE  : Stand Alone 
> STARTTIME: 2017-05-08 23:32:58 -0700 
&...
2008 Dec 12
1
APC Backups-Pro 650 - Any way to use apcsmart?
...l name and try again
	Huh?? Nothing in syslog with this attempt.
	Has anyone actually managed to get this ups running with apcsmart? The
genericups driver offers just the bare minimum of information.
	I reloaded the apcupsd so I could show you the output available:
[12:27 nemesis/etc/apcupsd] # apcaccess
APC      : 001,049,1178
DATE     : Fri Dec 12 12:28:11 CST 2008
HOSTNAME : nemesis
RELEASE  : 3.14.4
VERSION  : 3.14.4 (18 May 2008) suse
UPSNAME  : NEM_0650
CABLE    : APC Cable 940-0095A
MODEL    : BACK-UPS PRO 650
UPSMODE  : Stand Alone
STARTTIME: Fri Dec 12 12:27:56 CST 2008
STATUS   : ONLINE L...
2024 Aug 19
1
APC BX ...MI series
Hello,
  Just wanted to clarify: what sort of issues did you have with the APC?
  Since last year there have been several posts such as
https://github.com/networkupstools/nut/issues/2347 about BX****MI (3-4
digits for wattage) series built (or flashed with firmware?) roughly in
2023-2024 as frequently reporting low-battery/replace-battery/all-good
events in a short timeframe, both with NUT and
2009 Sep 02
6
Selftest intervall, APC Smart-UPS 750 RM
Hello
I recently switched from apcupsd to NUT2.2.2  without 
any troubles.
I tried to figure out how I can configure the self-test
intervall. The command upsrw lists only the variables
battery.charge.low
battery.runtime.low
ups.delay.shutdown
ups.delay.start
The command usbhid-ups -D and the listing under
http://obsvermes.org/cgi-bin/nut/upsstats.cgi?host=apcsmart at localhost&treemode