Two APC900 UPS on the same usbbus1
Hi!
On my FreeBSD 12.0-RELEASE-p7 server I was unable to retrieve the
correct information from my two UPS. Every time only the first UPS will
returned when I entering "upsc apc900" or "upsc apc901". I don't know
why (Bug or configuration issue on my side?!). I have downloaded the
latest source code and with my "patch" I was able to get the right
information from each UPS are expected (correct serial no and other).
In my ups.conf I have added...
2019 Jul 18
1
Two APC900 UPS on the same usbbus1
...tching the serial number specified in ups.conf. (I am not ready to rule out incompatible changes in FreeBSD 12.) Probably two "-D" flags should be sufficient. You can stop them with upsdrvctl first, but I would recommend starting usbhid-ups directly ("/usr/local/ups/bin/usbhid-ups -a apc900 -D -D"; otherwise, if you specify "upsdrvctl -D -D", NUT thinks you are trying to debug upsdrvctl itself.)
You are right Chalres !!! But I don't know why I have not probed this
variant in the past :-(
I have used the origin upsdrvctl binary in the following test and it
works al...
2019 Jul 18
0
Two APC900 UPS on the same usbbus1
...tching the serial number specified in ups.conf. (I am not ready to rule out incompatible changes in FreeBSD 12.) Probably two "-D" flags should be sufficient. You can stop them with upsdrvctl first, but I would recommend starting usbhid-ups directly ("/usr/local/ups/bin/usbhid-ups -a apc900 -D -D"; otherwise, if you specify "upsdrvctl -D -D", NUT thinks you are trying to debug upsdrvctl itself.)