2017 Apr 03
4
battery not installed, but battery still 100% and NUT 2.7.2-4 does not catch this and report a error
On 03/04/17 17.24, Roger Price wrote: > On Mon, 3 Apr 2017, Jon Bendtsen wrote: > >> On 03/04/17 17.10, Roger Price wrote: >>> On Mon, 3 Apr 2017, Jon Bendtsen wrote: >>> >>>> Power seem to be lost immediately. >>>> But my APC Smart-UPS 1500 always reported everything OK. >>>> battery.charge : 100 >>> ...
2017 Apr 03
4
battery not installed, but battery still 100% and NUT 2.7.2-4 does not catch this and report a error
...AS0535132782 ups.status : ALARM OL ups.test.result : No test initiated ups.timer.reboot : -1 ups.timer.shutdown : -1 ups.timer.start : -1 ups.vendorid : 051d what? no battery installed, and the status is ALARM? how come NUT doesnt report this? root at dkfitlet:/etc/nut# upslog -s apc1500 -l - Network UPS Tools upslog 2.7.2 logging status of apc1500 to - (30s intervals) Init SSL without certificate database 20170403 154055 100 230.4 21.4 [ALARM OL] NA NA 20170403 154125 100 230.4 20.8 [ALARM OL] NA NA 20170403 154155 100 230.4 21.4 [ALARM OL] NA NA root at dkfitlet:/etc/nut# ups...
2014 Nov 10
1
APC Smart-UPS C1500 connected by usb
...man/docs/latest/ddl/APC/Smart-UPS_1000.html > > Yes it does (except that mine is a 120 V model, so input/output voltage is about 125) It doesn't look like we have an entry for a C1500 yet. Would you care to > submit the output of upsc, upsrw and upscmd -l? > Here it is $upscmd -l apc1500 Instant commands supported on UPS [apc1500]: beeper.disable - Disable the UPS beeper beeper.enable - Enable the UPS beeper beeper.mute - Temporarily mute the UPS beeper beeper.off - Obsolete (use beeper.disable or beeper.mute) beeper.on - Obsolete (use beeper.enable) load.off - Turn off the load i...
2014 Nov 09
0
APC Smart-UPS C1500 connected by usb
On Nov 8, 2014, at 6:12 PM, Selva Nair <selva.nair at gmail.com> wrote: > Everything works rather well, except that the cgi-interface does not report input/output voltages and load for the C 1500 unit. > upsc also reports these values only for model 1000, not for 1500. Battery charge is and runtime are reported. For the 1000, do the values match this page?
2012 Jan 03
1
2 different APC UPS using USB get in power off recoverable state
...-0:1.0: unable to enumerate USB device on port 1 The machine is a guruplug server plus, running debian lenny on armtel. Linux dkplugbab9 2.6.32-00007-g56678ec #1 PREEMPT Mon Feb 8 03:49:55 PST 2010 armv5tel GNU/Linux I have hand installed Network UPS Tools upsstats 2.4.3 from source. ups.conf: [apc1500] driver = usbhid-ups port = auto serial=AS0535132782 # powers switches and routers [Smart-UPS_3000] driver = usbhid-ups port = auto serial=JS1030003421 [R3000XR] port = /dev/ttyUSB0 driver = bcmxcp The R3000XR did work, but neither apc1500 nor Smart-UPS_3000. I tried restartin...
2014 Nov 08
3
APC Smart-UPS C1500 connected by usb
Hi, I have setup NUT in netserver mode on debian wheezy with two APC UPS units connected to it by usb. lsusb identifies the units as Smart-UPS 1000 and Smart-UPS C1500. It appears these do not use the smart protocol and usbhid-ups is the correct driver to use. System: Debian wheezy with stock version of nut (Version: 2.6.4-2.3+deb7u1) Everything works rather well, except that the
2010 Nov 07
3
Support of "shutdown.return" on a APC Back-UPS CS 500
Hi all, I am trying to get a APC Back-UPS CS 500 running on my QNAP 419P Nas. Since on all my work I figure out the following: from Network UPS Tools upscmd 2.4.1 [~] # upscmd -l qnapups Instant commands supported on UPS [qnapups]: beeper.disable - Disable the UPS beeper beeper.enable - Enable the UPS beeper beeper.mute - Temporarily mute the UPS beeper beeper.off - Obsolete (use
2017 Apr 10
2
battery not installed, but battery still 100% and NUT 2.7.2-4 does not catch this and report a error
...t; 2017-04-04 14:18 GMT+02:00 Jon Bendtsen <jon.bendtsen at jonix.dk >> <mailto:jon.bendtsen at jonix.dk>>: [cuuuuut] > I'd say your change is a success :-) well, almost, but maybe that is outside NUT's control. /usr/lib/nagios/plugins/check_ups -H dkvideobackup -u apc1500 UPS OK - Status=Online, Unknown Utility=227.5V Batt=100.0% Load=0.0% |voltage=227500mV;;;0 battery=100%;;;0;100 load=0%;;;0;100 JonB
2017 Apr 10
0
battery not installed, but battery still 100% and NUT 2.7.2-4 does not catch this and report a error
...32 upsrw -rwxr-xr-x 1 root staff 113208 Apr 10 14:32 upsset.cgi -rwxr-xr-x 1 root staff 124888 Apr 10 14:32 upsstats.cgi So I ran it from the build directory, and here is the WALL I get Broadcast message from jonbendtsen at dkvideobackup (somewhere) (Mon Apr 10 15:07: Communications with UPS apc1500 at localhost established Broadcast message from jonbendtsen at dkvideobackup (somewhere) (Mon Apr 10 15:07: UPS apc1500 at localhost has one or more alarms (check ups.alarm) got CGI scripts up and running, and the status field is indeed now red and says: ALARM ONLINE Network UPS Tools upss...
2017 Apr 04
4
battery not installed, but battery still 100% and NUT 2.7.2-4 does not catch this and report a error
2017-04-04 14:18 GMT+02:00 Jon Bendtsen <jon.bendtsen at jonix.dk>: > On 04/04/17 14.10, Roger Price wrote: > >> On Tue, 4 Apr 2017, Arnaud Quette wrote: >> >> > [cuuuuut] > > Hi Arnaud, It seems to me that, looking out into the future, there are >> three >> things upsmon needs: >> >> 1. A fall-through <notify type> of
2010 Nov 12
4
NUT 2.4.3 on new server can not see serial number, but old nut on different hardware can?
...8-vs2.2.0.6 #1 SMP Sat Feb 16 20:54:32 CET 2008 i686 GNU/Linux debian package 2.2.2-6.5 it does not work on Linux dkplugbab9 2.6.32-00007-g56678ec #1 PREEMPT Mon Feb 8 03:49:55 PST 2010 armv5tel GNU/Linux NUT 2.4.3 self compiled dkplugbab9:/usr/local/ups/etc# /usr/local/ups/bin/usbhid-ups -a apc1500 -u nut -DD Network UPS Tools - Generic HID driver 0.34 (2.4.3) USB communication driver 0.31 0.000000 debug level is '2' 0.002738 upsdrv_initups... 0.005059 Checking device (051D/0002) (001/011) 0.005304 - VendorID: 051d 0.005351 - ProductID: 0002 0.005383 - Manufacturer:...
2017 Apr 10
0
battery not installed, but battery still 100% and NUT 2.7.2-4 does not catch this and report a error
...<jon.bendtsen at jonix.dk >>> <mailto:jon.bendtsen at jonix.dk>>: > > [cuuuuut] > > >> I'd say your change is a success :-) > > well, almost, but maybe that is outside NUT's control. > > /usr/lib/nagios/plugins/check_ups -H dkvideobackup -u apc1500 > UPS OK - Status=Online, Unknown Utility=227.5V Batt=100.0% Load=0.0% > |voltage=227500mV;;;0 battery=100%;;;0;100 load=0%;;;0;100 Actually maybe it is within NUT's control. Maybe NUT should only claim that a UPS is ONLINE if ONLINE is the only thing it is? JonB