Displaying 12 results from an estimated 12 matches for "apc1500".
battery not installed, but battery still 100% and NUT 2.7.2-4 does not catch this and report a error
2017 Apr 03
4
battery not installed, but battery still 100% and NUT 2.7.2-4 does not catch this and report a error
On 03/04/17 17.24, Roger Price wrote:
> On Mon, 3 Apr 2017, Jon Bendtsen wrote:
>
>> On 03/04/17 17.10, Roger Price wrote:
>>> On Mon, 3 Apr 2017, Jon Bendtsen wrote:
>>>
>>>> Power seem to be lost immediately.
>>>> But my APC Smart-UPS 1500 always reported everything OK.
>>>> battery.charge : 100
>>> ...
battery not installed, but battery still 100% and NUT 2.7.2-4 does not catch this and report a error
2017 Apr 03
4
battery not installed, but battery still 100% and NUT 2.7.2-4 does not catch this and report a error
...AS0535132782
ups.status : ALARM OL
ups.test.result : No test initiated
ups.timer.reboot : -1
ups.timer.shutdown : -1
ups.timer.start : -1
ups.vendorid : 051d
what? no battery installed, and the status is ALARM? how come NUT doesnt report
this?
root at dkfitlet:/etc/nut# upslog -s apc1500 -l -
Network UPS Tools upslog 2.7.2
logging status of apc1500 to - (30s intervals)
Init SSL without certificate database
20170403 154055 100 230.4 21.4 [ALARM OL] NA NA
20170403 154125 100 230.4 20.8 [ALARM OL] NA NA
20170403 154155 100 230.4 21.4 [ALARM OL] NA NA
root at dkfitlet:/etc/nut# ups...
2014 Nov 10
1
APC Smart-UPS C1500 connected by usb
...man/docs/latest/ddl/APC/Smart-UPS_1000.html
>
>
Yes it does (except that mine is a 120 V model, so input/output voltage is
about 125)
It doesn't look like we have an entry for a C1500 yet. Would you care to
> submit the output of upsc, upsrw and upscmd -l?
>
Here it is
$upscmd -l apc1500
Instant commands supported on UPS [apc1500]:
beeper.disable - Disable the UPS beeper
beeper.enable - Enable the UPS beeper
beeper.mute - Temporarily mute the UPS beeper
beeper.off - Obsolete (use beeper.disable or beeper.mute)
beeper.on - Obsolete (use beeper.enable)
load.off - Turn off the load i...
2014 Nov 09
0
APC Smart-UPS C1500 connected by usb
On Nov 8, 2014, at 6:12 PM, Selva Nair <selva.nair at gmail.com> wrote:
> Everything works rather well, except that the cgi-interface does not report input/output voltages and load for the C 1500 unit.
> upsc also reports these values only for model 1000, not for 1500. Battery charge is and runtime are reported.
For the 1000, do the values match this page?
2012 Jan 03
1
2 different APC UPS using USB get in power off recoverable state
...-0:1.0: unable to enumerate USB device on port 1
The machine is a guruplug server plus, running debian lenny on armtel. Linux dkplugbab9 2.6.32-00007-g56678ec #1 PREEMPT Mon Feb 8 03:49:55 PST 2010 armv5tel GNU/Linux
I have hand installed Network UPS Tools upsstats 2.4.3 from source.
ups.conf:
[apc1500]
driver = usbhid-ups
port = auto
serial=AS0535132782
# powers switches and routers
[Smart-UPS_3000]
driver = usbhid-ups
port = auto
serial=JS1030003421
[R3000XR]
port = /dev/ttyUSB0
driver = bcmxcp
The R3000XR did work, but neither apc1500 nor Smart-UPS_3000. I tried restartin...
2014 Nov 08
3
APC Smart-UPS C1500 connected by usb
Hi,
I have setup NUT in netserver mode on debian wheezy with two APC UPS units
connected to it by usb. lsusb identifies the units as Smart-UPS 1000 and
Smart-UPS C1500. It appears these do not use the smart protocol and
usbhid-ups is the correct driver to use.
System: Debian wheezy with stock version of nut
(Version: 2.6.4-2.3+deb7u1)
Everything works rather well, except that the
2010 Nov 07
3
Support of "shutdown.return" on a APC Back-UPS CS 500
Hi all,
I am trying to get a APC Back-UPS CS 500 running on my QNAP 419P Nas.
Since on all my work I figure out the following:
from Network UPS Tools upscmd 2.4.1
[~] # upscmd -l qnapups
Instant commands supported on UPS [qnapups]:
beeper.disable - Disable the UPS beeper
beeper.enable - Enable the UPS beeper
beeper.mute - Temporarily mute the UPS beeper
beeper.off - Obsolete (use
battery not installed, but battery still 100% and NUT 2.7.2-4 does not catch this and report a error
2017 Apr 10
2
battery not installed, but battery still 100% and NUT 2.7.2-4 does not catch this and report a error
...t; 2017-04-04 14:18 GMT+02:00 Jon Bendtsen <jon.bendtsen at jonix.dk
>> <mailto:jon.bendtsen at jonix.dk>>:
[cuuuuut]
> I'd say your change is a success :-)
well, almost, but maybe that is outside NUT's control.
/usr/lib/nagios/plugins/check_ups -H dkvideobackup -u apc1500
UPS OK - Status=Online, Unknown Utility=227.5V Batt=100.0% Load=0.0%
|voltage=227500mV;;;0 battery=100%;;;0;100 load=0%;;;0;100
JonB
battery not installed, but battery still 100% and NUT 2.7.2-4 does not catch this and report a error
2017 Apr 10
0
battery not installed, but battery still 100% and NUT 2.7.2-4 does not catch this and report a error
...32 upsrw
-rwxr-xr-x 1 root staff 113208 Apr 10 14:32 upsset.cgi
-rwxr-xr-x 1 root staff 124888 Apr 10 14:32 upsstats.cgi
So I ran it from the build directory, and here is the WALL I get
Broadcast message from jonbendtsen at dkvideobackup (somewhere) (Mon Apr 10 15:07:
Communications with UPS apc1500 at localhost established
Broadcast message from jonbendtsen at dkvideobackup (somewhere) (Mon Apr 10 15:07:
UPS apc1500 at localhost has one or more alarms (check ups.alarm)
got CGI scripts up and running, and the status field is indeed now red and says:
ALARM
ONLINE
Network UPS Tools upss...
battery not installed, but battery still 100% and NUT 2.7.2-4 does not catch this and report a error
2017 Apr 04
4
battery not installed, but battery still 100% and NUT 2.7.2-4 does not catch this and report a error
2017-04-04 14:18 GMT+02:00 Jon Bendtsen <jon.bendtsen at jonix.dk>:
> On 04/04/17 14.10, Roger Price wrote:
>
>> On Tue, 4 Apr 2017, Arnaud Quette wrote:
>>
>>
> [cuuuuut]
>
> Hi Arnaud, It seems to me that, looking out into the future, there are
>> three
>> things upsmon needs:
>>
>> 1. A fall-through <notify type> of
2010 Nov 12
4
NUT 2.4.3 on new server can not see serial number, but old nut on different hardware can?
...8-vs2.2.0.6 #1 SMP Sat Feb 16 20:54:32 CET 2008 i686 GNU/Linux
debian package 2.2.2-6.5
it does not work on
Linux dkplugbab9 2.6.32-00007-g56678ec #1 PREEMPT Mon Feb 8 03:49:55 PST 2010 armv5tel GNU/Linux
NUT 2.4.3 self compiled
dkplugbab9:/usr/local/ups/etc# /usr/local/ups/bin/usbhid-ups -a apc1500 -u nut -DD
Network UPS Tools - Generic HID driver 0.34 (2.4.3)
USB communication driver 0.31
0.000000 debug level is '2'
0.002738 upsdrv_initups...
0.005059 Checking device (051D/0002) (001/011)
0.005304 - VendorID: 051d
0.005351 - ProductID: 0002
0.005383 - Manufacturer:...
battery not installed, but battery still 100% and NUT 2.7.2-4 does not catch this and report a error
2017 Apr 10
0
battery not installed, but battery still 100% and NUT 2.7.2-4 does not catch this and report a error
...<jon.bendtsen at jonix.dk
>>> <mailto:jon.bendtsen at jonix.dk>>:
>
> [cuuuuut]
>
>
>> I'd say your change is a success :-)
>
> well, almost, but maybe that is outside NUT's control.
>
> /usr/lib/nagios/plugins/check_ups -H dkvideobackup -u apc1500
> UPS OK - Status=Online, Unknown Utility=227.5V Batt=100.0% Load=0.0%
> |voltage=227500mV;;;0 battery=100%;;;0;100 load=0%;;;0;100
Actually maybe it is within NUT's control. Maybe NUT should only claim that a
UPS is ONLINE if ONLINE is the only thing it is?
JonB