search for: apas01

Displaying 8 results from an estimated 8 matches for "apas01".

2014 Mar 15
0
Creating a new NUT USB HID subdriver
...help if there was some master list > of all the paths (input.voltage, battery.temperature, etc) NUT supports, > instead of having to dig through different driver files to see what's available. Is there some list? How about http://www.networkupstools.org/docs/developer-guide.chunked/apas01.html /Niels -- Niels Baggesen - @home - ?rhus - Denmark - nba at users.sourceforge.net The purpose of computing is insight, not numbers --- R W Hamming
2014 Mar 14
2
Creating a new NUT USB HID subdriver
Thanks to the great help here, I now have a UPS spitting out something resembling a report descriptor. So since I seem destined to have to create a new USB HID subdriver, I figured I'd get started on the path. I followed all of the directions on the web....I used the script to generate the usbhid subdriver, feeding it the output of the usbhid-ups driver from reading my UPS. All that worked
2017 Jun 07
1
new driver- or vendor-specific variable prefix?
Not to pick on anyone in particular, but for the sake of organization, I think we might need to address the need for variables beyond the standard ones defined here: http://networkupstools.org/docs/developer-guide.chunked/apas01.html From http://networkupstools.org/docs/developer-guide.chunked/ar01s04.html#_variable_names : "PLEASE don?t make up new variables and commands just because you can. The new dstate functions give us the power to create just about anything, but that is a privilege and not a right. Imagine t...
2013 Jul 02
2
bcmxcp: Patch for adding ups.load and battery.voltage.low
...n; may vary dynamically with load. V dc 48 % LOAD PHASE A Output Load on Phase A, in per cent. Normally the greater of VA and Watts. For a single phase UPS, the % Load for the whole UPS is reported in this Phase A meter. % Looking at : http://www.networkupstools.org/docs/developer-guide.chunked/apas01.html I draw the conclusions that the BATTERY DCUV BAR CHART bcmxcp meter should be mapped to NUT variable battery.voltage.low Do you agree that this is correct ? I draw the conclusions that the LOAD PHASE A bcmxcp meter should be mapped to NUT variable ups.load Do you agree that this is correct...
2014 Oct 10
1
Return on experience with an Emerson/Liebert GXT3
...m out again before checking the driver in to version control. Please find attached the patches i have applied to the current master. >> >> Is there a list of all official NUT names (i haven't searched yet) ? >> > http://www.networkupstools.org/docs/developer-guide.chunked/apas01.html > Thank you. Paul. -------------- next part -------------- A non-text attachment was scrubbed... Name: 0001-drivers-fix-possible-memory-leak.patch Type: text/x-patch Size: 637 bytes Desc: not available URL: <http://lists.alioth.debian.org/pipermail/nut-upsuser/attachments/20141010/9...
2014 Feb 18
1
Add general UPS SNMP agent as a nut client
hem, in the hurry of sending, I've forgotten a link... 2014-02-18 22:45 GMT+01:00 Arnaud Quette <aquette.dev at gmail.com>: > > > 2014-02-16 8:31 GMT+01:00 <alf at i100.no>: > (...) > > That made me realize that it's still not referenced on the NUT Related > Projects page. > (yup Charles, yet another unshared thing...) > This last point is now
2013 Jul 02
0
bcmxcp: Patch for adding ups.load and battery.voltage.low
...% LOAD PHASE A > Output Load on Phase A, in per cent. Normally the greater of VA and > Watts. For a single phase UPS, the % Load for the whole UPS is > reported in this Phase A meter. % > Check:-) > > Looking at : > http://www.networkupstools.org/docs/developer-guide.chunked/apas01.html > I draw the conclusions that the BATTERY DCUV BAR CHART bcmxcp meter > should be mapped to NUT variable battery.voltage.low > Do you agree that this is correct ? > Yes this is correct. One more point to scratch from the todo list :-) > I draw the conclusions that the LOAD PHAS...
2014 Oct 06
1
Return on experience with an Emerson/Liebert GXT3
Hi On 10/03/2014 03:42 PM, Charles Lepple wrote:> On Oct 3, 2014, at 7:50 AM, paul.chavent at fnac.net wrote: > > > This is what I was referring to (from the belkin-hid log): > >???? 1.325782??? Report[buf]: (5 bytes) => 05 53 00 48 00 >???? 1.325799??? Path: UPS.PowerSummary.ConfigVoltage, Type: Feature, ReportID: 0x05, Offset: 16, Size: 16, Value: 0 >????