2015 Jan 18
2
nutdrv_qx and Best Power equipment
...default 30-second ups.delay.shutdown
(S.5R0000), as well as 60 seconds (S01R0000).
I don't think this is a regression for my model, although the docs
suggest sending the command without the "R####":
http://buildbot.networkupstools.org/~buildbot/cayman/docs/latest/protocols/sola.html#_shutdown_command
--
- Charles Lepple
2015 Jan 18
0
nutdrv_qx and Best Power equipment
...elay.shutdown
> (S.5R0000), as well as 60 seconds (S01R0000).
>
> I don't think this is a regression for my model, although the docs
> suggest sending the command without the "R####":
> http://buildbot.networkupstools.org/~buildbot/cayman/docs/latest/protocols/sola.html#_shutdown_command
For completeness' sake, I should mention that this was tested against
commit 99b37b4. No surprises in the log file (-DDDDD), but I have it
in case you need it.
--
- Charles Lepple
2015 Sep 10
0
blazer_usb Shutdown
...twork UPS Tools - Megatec/Q1 protocol USB driver 0.10 (2.7.1)
[...]
> I set delay.shutdown to 600 sec but UPS turns power off after about 120 sec.
The shutdown delay gets discretized into a few different values, and is then sent to the UPS:
http://www.networkupstools.org/protocols/megatec.html#_shutdown_command
I'm not too familiar with the internals of this driver (development has shifted to its successor, nutdrv_qx, which should also be available in v2.7.1) but it looks like you can manually test the shutdown with the following command (after everything else has been stopped; perhaps send this from...
2015 Jan 03
0
nutdrv_qx and Best Power equipment
Yet again, sorry for the delay - I hope the UPS is still alive.
>> I noticed that your UPS seems to support the 'M' command as a query of
>> some sort (it replies '0'): now I'm curious as to what it does mean.
>>
>> It could be the 0-9 index of the user-settable voltage limits, page 19 of:
>>
2015 Sep 10
2
blazer_usb Shutdown
Hi,
I am using a ALLNET 91500 UPS with blazer_usb driver
/usr/lib/ups/driver/blazer_usb -a ups91500 -L
Network UPS Tools - Megatec/Q1 protocol USB driver 0.10 (2.7.1)
I have this settings:
upsc ups91500 at localhost
battery.charge: 100
battery.runtime: 12000
battery.voltage: 27.50
battery.voltage.high: 27.3
battery.voltage.low: 18.0
device.type: ups
driver.flag.novendor: enabled
driver.name:
2014 Nov 09
3
nutdrv_qx and Best Power equipment
On Nov 7, 2014, at 5:31 PM, hyouko at gmail.com wrote:
>> Sure enough, it turned off after about 30 seconds (t=228). I unplugged it for about five seconds, and it came back on three minutes after I plugged it back in. However, the bypass bit inversion might be responsible for this:
>>
>> 228.304623 send: 'Q1'
>> 228.515426 read: '(119.0 119.0 000.0 000