Fw: [Nut-upsdev] POWERCOM-UPS-USB : UPS Shutdown
Good Day Roger
AA. notice that during the test, you have little or no load, since despite
being in state OB
DISCHRG the battery.charge is still 100. It's best to perform such tests
with a dummy load
such as a table lamp and an old fashioned incandescent 100 watt bulb.
==> Yes. I got it and try to ascend load as below results
dinow-All-Series:~# upsc pcmups
Init SSL without
2017 May 17
0
[Nut-upsdev] POWERCOM-UPS-USB : UPS Shutdown
...ERR ACCESS-DENIED
>
This error is not from the driver. Be sure to specify a NUT user and password that is allowed to send instcmds:
http://networkupstools.org/docs/man/upsd.users.html
If you need to modify upsd.users, tell upsd to reload it:
http://networkupstools.org/docs/man/upsd.html#_reloading
2011 Nov 21
3
Confusing Generic USB UPS cannot be matched
I was dropping off junk at the waste transfer station and scarfed a UPS
out of the pile of old TV's and VCR's. It was in good physical condition
and as I expected, the battery was toast. A new RBC-2 battery restored
it to working condition. Then I tried to get it to talk to some
software. And I am having no luck.
The unit is branded as a Nexxtech Model 6118507 650VA imported into