2014 Jun 02
2
blazer_ser battery.high / battery.low
.... should the blazer_ser's high voltage be the voltage during charging >> or right after I've unplugged it from the mains? > sounds like during charging (or more accurately, during float charging at the end of the cycle): > > http://www.networkupstools.org/docs/man/blazer.html#_extra_arguments Are you sure? If I put the 27.4 (reported voltage @ 100%) in the config, battery.charge drops immediately when unplugged, because the reported battery.voltage then is only 26.xV. (But I'm not sure the battery was at 100% when I saw the 26.xV) >> 2. should the blazer_ser's low voltag...
2014 Jun 02
0
blazer_ser battery.high / battery.low
...er_ser's high voltage be the voltage during charging >>> or right after I've unplugged it from the mains? >> sounds like during charging (or more accurately, during float charging at the end of the cycle): >> >> http://www.networkupstools.org/docs/man/blazer.html#_extra_arguments > > Are you sure? If I put the 27.4 (reported voltage @ 100%) in the config, > battery.charge drops immediately when unplugged, because the reported > battery.voltage then is only 26.xV. (But I'm not sure the battery was at > 100% when I saw the 26.xV) I'm pretty sure I wou...
2016 Oct 05
2
UPS Shutdown
I'm trying to better understand OffDelay and OnDelay: http://networkupstools.org/docs/man/usbhid-ups.html#_extra_arguments My server requires ~3? minutes to shut itself down. Considering this I'm comfortable setting OffDelay to 300 (five minutes). How does this work in conjunction with the UPS hardware? Does NUT immediately send a command to the UPS to wait for 300 seconds and then shut itself down, thereby allow...
2015 Aug 14
2
occassional problem wtih upslog and apc ups units via snmp ... [NA] status
I see this in syslog: Aug 12 03:57:22 orion upsd[18274]: Data for UPS [a102-apc-10] is stale - check driver (one for each UPS). Then I see a bunch of messages like this: Aug 12 03:58:02 orion upsd[18274]: write() failed for ::1: Broken pipe Aug 12 03:58:02 orion snmpd[2872]: Connection from UDP: [127.0.0.1]:50940 And then it returns to normal like this: Aug 12 03:58:04 orion upsd[18274]: UPS
2013 Dec 16
1
upsrw: "Unexpected response from upsd: ERR READONLY"
After issuing this command: /upsrw -s ups.delay.shutdown=180 -u admin -p mypassword myups /I obtain this error:/ Unexpected response from upsd: ERR READONLY /After issuing this command:/ upsrw myups /I obtain no output./ /In my /upsd.users/ file I have these settings: /[admin]// //password = mypassword// //actions = SET// //instcmds = ALL// // //[myuser]// //password = mypassword//
2014 Apr 29
1
blazer_ser battery.high / battery.low
Hello list, we've got a PowerWalker VI 1000E/RT LCD UPS and like to use it with NUT using the blazer_ser driver. For the blazer_ser driver to display percentage, one has to add battery.voltage.high and battery.voltage.low voltages to the ups config. Here's what I received from the powerwalker customer service: Battery-Low Voltage: 21.6VDC Battery Shutdown: 19.2VDC Now my questions: 1.
2018 Jul 25
0
Adding drivers to NUT?
...r a given device. See: - https://networkupstools.org/docs/man/nutdrv_qx.html#_battery_charge - the various 'default.battery.*' and 'override.battery.*' items, 'runtimecal', 'chargetime' and 'idleload', here: https://networkupstools.org/docs/man/nutdrv_qx.html#_extra_arguments If you still can't find acceptable values, and you have any idea on how to improve our calculations, we're open to contributions. > - third: we have products with VID and PID: FFFF 0000, this is a problem > because the combination is occuped by Krauler and in this way it will match...
2016 Oct 06
0
UPS Shutdown
On Wed, 5 Oct 2016, Jeff Bowman wrote: > I?m trying to better understand OffDelay and OnDelay: > http://networkupstools.org/docs/man/usbhid-ups.html#_extra_arguments > > My server requires ~3? minutes to shut itself down. Considering this I?m > comfortable setting OffDelay to 300 (five minutes). > > How does this work in conjunction with the UPS hardware? Does NUT > immediately send a command to the UPS to wait for 300 seconds and then &g...
2011 Jul 28
1
Ippon Back Power Pro 700 USB driver.
Hello! I've got an "Ippon Back Power Pro 700 USB" UPS. The system is Gentoo/Calculate. The NUT version is *2.6.0-r1* I've made all necessary instructions to make NUT work properly with my UPS using USB "blazer_usb" driver. But, when I start *upsdrv* it tells me the following: * * Starting UPS drivers ...* *Network UPS Tools - UPS driver controller 2.6.0*
2012 Dec 18
1
Tripplite SmartUPS
We are configuring a server with a Tripplite SmartUPS, Web SNMP Card, and Envirosense Probe. The configuration is good using usbhid driver and we can get it to shutdown clean by producing a "power event" (pull the power cable). It is not very clear how to add or see the values associated with the external probe. We need to be able to shutdown based on the input from the probe as well as
2023 Jun 20
1
had to reinstall on new drive, lost all nut related .conf's
On 6/19/23 20:29, gene heskett wrote: Some speeling korrections > On 6/19/23 18:57, gene heskett wrote: >> Greetings Jim & friends; >> >> Just installed nut 2.7.4 on a debian bullseye system.? ups is: >> Bus 001 Device 006: ID 051d:0003 American Power Conversion UPS >> Device Descriptor: >> ?? bLength??????????????? 18 >> ?? bDescriptorType????????
2017 Jun 03
0
Fwd: Emerson Liebert GXT4
...ue for the port string is ignored, though it must be present - you can change that to "auto" or "dummy" if you want. (See the usbhid-ups man page for details if you need to distinguish between multiple UPSes on a single system: http://networkupstools.org/docs/man/usbhid-ups.html#_extra_arguments ) You can also add "productid=0000" here, and try running the driver and upsd. (Either use the usbhid-ups command line below, and run "sudo /sbin/upsd", or kill the driver and run "sudo service nut-server restart" > My system is running Ubuntu 16.04 with nut versi...
2015 Aug 14
0
occassional problem wtih upslog and apc ups units via snmp ... [NA] status
...d[18274]: Data for UPS [a102-apc-10] is stale - check driver > > I don't have a SNMP UPS to test with, and this might be different for NUT 2.4.1, but the current defaults seem to make stale data more likely in your case. > > In http://www.networkupstools.org/docs/man/snmp-ups.html#_extra_arguments the default for "pollfreq" is 30 seconds, and in http://www.networkupstools.org/docs/man/upsd.conf.html the "MAXAGE" default is 15 seconds. So you might want to either increase MAXAGE, or decrease pollfreq. > > I would recommend making MAXAGE at least pollfreq (possibly 1...
2014 Jan 10
1
Eaton 5PX broken interrupt on usbhid-ups, also pollfreq vs pollinterval?
Linux NUT 2.7.1 Eaton 5PX usbhid-ups It would appear that interrupts are not actually working on my 5PX using the usbhid-ups driver. I will be trying the serial mge-shut driver next. It just seemed like it was working before because of the default pollinterval of 2 seconds. The status update comes in during the pollinterval no matter what I have pollfreq set to. And I can set pollonly and
2013 Jun 19
1
Cannot connect to a Eaton Ellipse Pulsar ASR/6000VA usbs
Hi all, I am trying to communicate to this Eaton Ellipse (see above) using nut from a Debian Squeeze system on Armel architecture. But have not succeeded so far. Version: Linux b3 2.6.39.4-11 #1 Tue Apr 3 21:45:12 FET 2012 armv5tel GNU/Linux Nut version is 2.4.3-1.1squeeze2 this information if from dpkg. NUT installation method:from debian package for armel. The problem is I cannot
2014 Jun 02
2
blazer_ser battery.high / battery.low
...h voltage be the voltage during charging >>>> or right after I've unplugged it from the mains? >>> sounds like during charging (or more accurately, during float charging at the end of the cycle): >>> >>> http://www.networkupstools.org/docs/man/blazer.html#_extra_arguments >> >> Are you sure? If I put the 27.4 (reported voltage @ 100%) in the config, >> battery.charge drops immediately when unplugged, because the reported >> battery.voltage then is only 26.xV. (But I'm not sure the battery was at >> 100% when I saw the 26.xV) >...
2018 Jul 24
2
Adding drivers to NUT?
Dear Daniele, i understand perfectly, i'd like to explain you why we choosed to clone the blazer_usb driver: some of our devices uses Voltronic Q1 protocol and we tried the Krauler Subdriver (it was the one with the right "commands", Q1, F, etc.), but the issues were 2: - first: the Krauler Subdriver expects a different number of bytes in answer because in debug i see "Short
2017 Jun 02
2
Fwd: Emerson Liebert GXT4
Hello, we have a Emerson Liebert GXT4, that we like to connect to our servers to shut them down if there is a power failure (which happens quite often in our area). I couldn't get the GXT4 working with usbhid-ups driver. So I need some advise to continue to get this device working. The GXT3 seems to be working ok with NUT (http://networkupstools.org/ddl/Liebert/GXT3.html). Here is my
2013 Jun 20
3
Cannot connect to a Eaton Ellipse Pulsar ASR/6000VA usbs [solved] but new problem surfaces.
...t if you > provide 'vendor', it must match the 'Manufacturer:' value ('EATON', in your > case). > > To match against the hex values, use 'vendorid' (or 'productid'). > > Reference: > http://www.networkupstools.org/docs/man/usbhid-ups.html#_extra_arguments > > -- > Charles Lepple > clepple at gmail > > > > -------------- next part -------------- An HTML attachment was scrubbed... URL: <http://lists.alioth.debian.org/pipermail/nut-upsuser/attachments/20130620/3ff88762/attachment.html>
2018 Jul 26
5
Adding drivers to NUT?
...r a given device. See: - https://networkupstools.org/docs/man/nutdrv_qx.html#_battery_charge - the various 'default.battery.*' and 'override.battery.*' items, 'runtimecal', 'chargetime' and 'idleload', here: https://networkupstools.org/docs/man/nutdrv_qx.html#_extra_arguments If you still can't find acceptable values, and you have any idea on how to improve our calculations, we're open to contributions. > - third: we have products with VID and PID: FFFF 0000, this is a problem > because the combination is occuped by Krauler and in this way it will match...