Displaying 9 results from an estimated 9 matches for "5r0003".
Did you mean:
  50003
  
2013 Nov 22
1
forcing the driver to issue a different command on shutdown
...p] failed
   2.872768     instcmd(shutdown.stop, [NULL])
   2.872840     send: C
   3.385610     received 3 (67)
   3.385679     read:
   3.385738     instcmd: command [shutdown.stop] failed
   3.385787     No shutdown pending
   3.385848     instcmd(shutdown.return, [NULL])
   3.385918     send: S.5R0003
   3.385985     read: S.5R0003
   3.386046     instcmd: command [shutdown.return] handled
   3.386106     Shutting down in 30 seconds
2018 Mar 02
1
Work around for power recycling after shutdown.return - TSSHARA UPS - nutdrv_qx driver - megatec protocol
...let's see what happens:
- 'offdelay=30', 'ondelay=0' (the driver will send 'S.5' to the device),
- 'offdelay=120', 'ondelay=0' (the driver will send 'S02' to the device),
- 'offdelay=30', 'ondelay=180' (the driver will send 'S.5R0003' to the device),
- 'offdelay=120', 'ondelay=180' (the driver will send 'S02R0003' to the device),
- 'offdelay=30', 'stayoff' flag (the driver will send 'S.5R0000' to the device),
- 'offdelay=120', 'stayoff' flag (the driver will se...
2012 Apr 27
2
HCL: Zigor Danubio 2000 supported(ish) by blazer_usb
http://www.zigor.com/uk/index.php/en/products/upssystems/danubioseries
Ships with UPSilon 2000 software, and appears to work with blazer_usb to
a certain extent with the following config:
[danubio]
       driver = blazer_usb
        langid_fix = 0x409
        port = stupidly, I seem to have to set this even though it's ignored
        vendorid=0001
        productid=0000
Yes, vendor 0001,
2013 Oct 24
2
Shutdown problem with Mecer 1000VA Online UPS
...ot;
    0.031037     send_to_all: SETINFO ups.productid "5161"
    0.031046     Initiating UPS shutdown
    0.033050     send: C
    1.033388     read: error sending control message: Operation not permitted
    1.033404     instcmd: command [shutdown.stop] handled
    1.038035     send: S.5R0003
    1.109163     read: (ACK
    1.109179     instcmd: command [shutdown.return] failed
    1.111018     send: C
    1.149165     read: (ACK
    1.149180     instcmd: command [shutdown.stop] failed
    1.151017     send: C
    1.197111     read: (NAK
    1.197125     instcmd: command [shutdown.stop]...
2014 Nov 02
0
nutdrv_qx and Best Power equipment
> I finally got a Best Power Patriot Pro II fixed up with a new battery and cable, and tried it with nutdrv_qx (since it uses a variant of the Q1 protocol). It auto-detected the use of Q1.
>
> It looks like things mostly work:
Nice, merging bestups.c into nutdrv_qx has been on my todo list for a
while, let's see how far we can get.
> 1) The bestups driver uses an "ID"
2014 Nov 02
2
nutdrv_qx and Best Power equipment
...114.998222     instcmd(test.battery.stop, [NULL])
 114.998469     send: 'CT'
 115.999538     read: timeout (0)
 115.999573     instcmd: SUCCEED
I ran the shutdown.return command while the UPS was still on AC:
 197.276833     instcmd(shutdown.return, [NULL])
 197.277314     send: 'S.5R0003'
 198.278346     read: timeout (0)
 198.278366     instcmd: SUCCEED
Sure enough, it turned off after about 30 seconds (t=228). I unplugged it for about five seconds, and it came back on three minutes after I plugged it back in. However, the bypass bit inversion might be responsible for this:...
2018 Feb 28
2
Work around for power recycling after shutdown.return - TSSHARA UPS - nutdrv_qx driver - megatec protocol
Answers bellow.
2018-02-28 1:41 GMT-03:00 Daniele Pezzini <hyouko at gmail.com>:
> 2018-02-27 14:51 GMT+01:00 Jairo Rotava <jairo.rotava at gmail.com>:
> > Hi,
> >
> > I had an issue where after returning the power from a shutdown.return the
> > ups would do another shutdown.return during the boot, and kept this
> forever.
> > After some
2013 Oct 24
0
Shutdown problem with Mecer 1000VA Online UPS
...send_to_all: SETINFO ups.productid "5161"
>    0.031046     Initiating UPS shutdown
>    0.033050     send: C
>    1.033388     read: error sending control message: Operation not permitted
>    1.033404     instcmd: command [shutdown.stop] handled
>    1.038035     send: S.5R0003
>    1.109163     read: (ACK
>    1.109179     instcmd: command [shutdown.return] failed
>    1.111018     send: C
>    1.149165     read: (ACK
>    1.149180     instcmd: command [shutdown.stop] failed
>    1.151017     send: C
>    1.197111     read: (NAK
>    1.197125...
2014 Nov 01
3
nutdrv_qx and Best Power equipment
Hi Daniele,
I finally got a Best Power Patriot Pro II fixed up with a new battery and cable, and tried it with nutdrv_qx (since it uses a variant of the Q1 protocol). It auto-detected the use of Q1.
It looks like things mostly work:
bestups:
battery.charge: 100.0
battery.voltage: 13.9
battery.voltage.nominal: 12
device.mfr: Best Power
device.model: Patriot Pro II 400
device.type: ups