search for: 5r0000

Displaying 7 results from an estimated 7 matches for "5r0000".

Did you mean: 50000
2015 Jan 18
2
nutdrv_qx and Best Power equipment
...run load.on 6) UPS turns on > 3. (OK, I lied - 3 things more) does the shutdown.stayoff command > ('SnR0000') work? shutdown.stayoff does not work - the UPS turns on immediately after its usual (~5 second) self-test. I tried it with both the default 30-second ups.delay.shutdown (S.5R0000), as well as 60 seconds (S01R0000). I don't think this is a regression for my model, although the docs suggest sending the command without the "R####": http://buildbot.networkupstools.org/~buildbot/cayman/docs/latest/protocols/sola.html#_shutdown_command -- - Charles Lepple
2015 Jan 18
0
nutdrv_qx and Best Power equipment
...t; 3. (OK, I lied - 3 things more) does the shutdown.stayoff command >> ('SnR0000') work? > > shutdown.stayoff does not work - the UPS turns on immediately after > its usual (~5 second) self-test. > > I tried it with both the default 30-second ups.delay.shutdown > (S.5R0000), as well as 60 seconds (S01R0000). > > I don't think this is a regression for my model, although the docs > suggest sending the command without the "R####": > http://buildbot.networkupstools.org/~buildbot/cayman/docs/latest/protocols/sola.html#_shutdown_command For compl...
2018 Mar 02
1
Work around for power recycling after shutdown.return - TSSHARA UPS - nutdrv_qx driver - megatec protocol
...the device), - 'offdelay=30', 'ondelay=180' (the driver will send 'S.5R0003' to the device), - 'offdelay=120', 'ondelay=180' (the driver will send 'S02R0003' to the device), - 'offdelay=30', 'stayoff' flag (the driver will send 'S.5R0000' to the device), - 'offdelay=120', 'stayoff' flag (the driver will send 'S02R0000' to the device). > > Jairo
2012 Apr 27
2
HCL: Zigor Danubio 2000 supported(ish) by blazer_usb
http://www.zigor.com/uk/index.php/en/products/upssystems/danubioseries Ships with UPSilon 2000 software, and appears to work with blazer_usb to a certain extent with the following config: [danubio] driver = blazer_usb langid_fix = 0x409 port = stupidly, I seem to have to set this even though it's ignored vendorid=0001 productid=0000 Yes, vendor 0001,
2015 Jan 03
0
nutdrv_qx and Best Power equipment
Yet again, sorry for the delay - I hope the UPS is still alive. >> I noticed that your UPS seems to support the 'M' command as a query of >> some sort (it replies '0'): now I'm curious as to what it does mean. >> >> It could be the 0-9 index of the user-settable voltage limits, page 19 of: >>
2014 Nov 09
3
nutdrv_qx and Best Power equipment
On Nov 7, 2014, at 5:31 PM, hyouko at gmail.com wrote: >> Sure enough, it turned off after about 30 seconds (t=228). I unplugged it for about five seconds, and it came back on three minutes after I plugged it back in. However, the bypass bit inversion might be responsible for this: >> >> 228.304623 send: 'Q1' >> 228.515426 read: '(119.0 119.0 000.0 000
2018 Feb 28
2
Work around for power recycling after shutdown.return - TSSHARA UPS - nutdrv_qx driver - megatec protocol
Answers bellow. 2018-02-28 1:41 GMT-03:00 Daniele Pezzini <hyouko at gmail.com>: > 2018-02-27 14:51 GMT+01:00 Jairo Rotava <jairo.rotava at gmail.com>: > > Hi, > > > > I had an issue where after returning the power from a shutdown.return the > > ups would do another shutdown.return during the boot, and kept this > forever. > > After some