1
Nut and UPSes+ATSes
Is there any documentation somewhere about how NUT can incorporate
automatic transfer switches into its monitoring and operational
framework to provide more comprehensive operational functionality?
H
2017 Mar 29
2
upsd/upsc, LISTEN and hostname resolution in master/slave
Hi,
I've been setting up a few Eatons 1500 USB in master/slave mode and run
into what I'm thinking is a hostname resolution problem.
Basically, to avoid hardcoding ips, I'd love to be able to add a LISTEN on
the lan's ip which has hostname, let's say, server1.local .
If I set up upsd.conf such as LISTEN server1.local 3493 what I end up with
is upsd listening on 127.0.0.1 .
2017 Mar 29
1
Eaton 1500 USB constant disconnections
...s indeed a SW communication setup (NUT or
> UPower for example),
> - send me back the upsc output for this unit, including the serial number
> and firmware revision
>
> thanks and regards,
> Arno
> --
> Eaton Data Center Automation Solutions - Opensource Leader -
> http://42ity.org
> NUT (Network UPS Tools) Project Leader - http://www.networkupstools.org
> Debian Developer - http://www.debian.org
> Free Software Developer - http://arnaud.quette.fr
>
-------------- next part --------------
An HTML attachment was scrubbed...
URL: <http://lists.alioth.debian.o...
2017 Mar 11
2
Eaton 1500 USB constant disconnections
Hi,
I have a eaton 1500 that connects to an Ubuntu Xenial box via USB. The UPS
works, however exactly *ever 5 minutes* it disconnects and reconnects and I
see this in syslog:
Mar 10 19:50:32 spike kernel: usb 4-5: USB disconnect, device number 103
Mar 10 19:50:33 spike kernel: usb 4-5: new low-speed USB device number 104
using ohci-pci
Mar 10 19:50:34 spike kernel: usb 4-5: New USB device found,
2024 May 18
1
Supporting a DIY UPS with minimal effort but maximum gain
...d, it is a long-term hope that one day this would be possible. Each
recent NUT release milestone had some work that chipped away the technical
barriers to including DMF into the main project.
For a longer version: DMF was designed and developed, fairly well tested
and then a bit abandoned in the 42ITy fork of NUT, which went back to using
upstream NUT for their appliances. The developed code base however for a
long time acts as the source of backports for features and vendor device
nuances into upstream NUT to benefit everyone. That codebase is available
in the FTY branch, including DMF along wi...
battery not installed, but battery still 100% and NUT 2.7.2-4 does not catch this and report a error
2017 Apr 04
4
battery not installed, but battery still 100% and NUT 2.7.2-4 does not catch this and report a error
...that
requires more thinking and time.
And the current implementation already points at this data.
@Jon: would you be able to test this branch and ack? (including the "covers
(or not) my needs...)
thanks and cheers,
Arno
--
Eaton Data Center Automation Solutions - Opensource Leader -
http://42ity.org
NUT (Network UPS Tools) Project Leader - http://www.networkupstools.org
Debian Developer - http://www.debian.org
Free Software Developer - http://arnaud.quette.fr
-------------- next part --------------
An HTML attachment was scrubbed...
URL: <http://lists.alioth.debian.org/pipermail/nut-ups...
2017 Mar 23
5
Fatal EEPROM fault!
Hello,
Sorry if any of this is obvious - I'm new to NUT.
NUT via upsc is displaying (edited for length):
device.model: Eaton 5P 2200
device.type: ups
driver.name: usbhid-ups
ups.alarm: Fatal EEPROM fault!
ups.status: ALARM OL CHRG
ups.test.interval: 604800
ups.test.result: Done and passed
driver.version: 2.7.2
driver.version.data: MGE HID 1.33
driver.version.internal: 0.38
Is this possibly
2017 Jun 13
2
Unable to use nut-2.7.4 with Eaton 5E1500I USB
...elay.shutdown: 20
ups.firmware: 02.06.0019
ups.load: 0
ups.mfr: EATON
ups.model: 5E 1500i
ups.power.nominal: 1500
ups.productid: ffff
ups.start.battery: yes
ups.status: OL
ups.timer.shutdown: -1
ups.vendorid: 0463
cheers,
Arno
--
Eaton Data Center Automation Solutions - Opensource Leader -
http://42ity.org
NUT (Network UPS Tools) Project Leader - http://www.networkupstools.org
Debian Developer - http://www.debian.org
Free Software Developer - http://arnaud.quette.fr
-------------- next part --------------
An HTML attachment was scrubbed...
URL: <http://lists.alioth.debian.org/pipermail/nut-ups...
2017 Apr 14
0
NUT namespace: RFC for new variable addition
...39;d like to extend the NUT namespace to add a new variable:
outlet.group.n.phase
Details and implementation can be found on:
https://github.com/networkupstools/nut/pull/422
Comments and feedback warmly welcome.
cheers,
Arno
--
Eaton Data Center Automation Solutions - Opensource Leader -
http://42ity.org
NUT (Network UPS Tools) Project Leader - http://www.networkupstools.org
Debian Developer - http://www.debian.org
Free Software Developer - http://arnaud.quette.fr
-------------- next part --------------
An HTML attachment was scrubbed...
URL: <http://lists.alioth.debian.org/pipermail/nut-ups...
2017 Jun 14
0
NUT namespace: RFC for new variable addition
...tied to ATS. I don't see that applying to 3ph
UPS, since there is only 1 source.
The point for ATS is that a source may be the main, and the other a UPS.
Hence the potential phase shift.
The nominal value is 0
cheers,
Arno
--
Eaton Data Center Automation Solutions - Opensource Leader -
http://42ity.org
NUT (Network UPS Tools) Project Leader - http://www.networkupstools.org
Debian Developer - http://www.debian.org
Free Software Developer - http://arnaud.quette.fr
-------------- next part --------------
An HTML attachment was scrubbed...
URL: <http://lists.alioth.debian.org/pipermail/nut-ups...
2017 Mar 21
0
Is a timer a file?
...BATT) has a
counterpart to cancel it (like ONLINE).
Ex (from the doc):
AT ONBATT * START-TIMER onbattwarn 30
AT ONLINE * CANCEL-TIMER onbattwarn
So is there any use case we're missing here?
Thanks and cheers,
Arno
--
Eaton Data Center Automation Solutions - Opensource Leader -
http://42ity.org
NUT (Network UPS Tools) Project Leader - http://www.networkupstools.org
Debian Developer - http://www.debian.org
Free Software Developer - http://arnaud.quette.fr
-------------- next part --------------
An HTML attachment was scrubbed...
URL: <http://lists.alioth.debian.org/pipermail/nut-ups...
2017 Mar 23
0
Fatal EEPROM fault!
...things...)
For now, I'm checking with our support and HW team to provide you with a
solution.
Have you done anything special or had anything special with the unit (can
help a lot to troubleshoot)?
Thanks and cheers,
Arno
--
Eaton Data Center Automation Solutions - Opensource Leader -
http://42ity.org
NUT (Network UPS Tools) Project Leader - http://www.networkupstools.org
Debian Developer - http://www.debian.org
Free Software Developer - http://arnaud.quette.fr
-------------- next part --------------
An HTML attachment was scrubbed...
URL: <http://lists.alioth.debian.org/pipermail/nut-ups...
2017 Mar 23
2
Fatal EEPROM fault!
On Thu, Mar 23, 2017 at 11:26 AM, Gene Heskett <gheskett at shentel.net> wrote:
> Have you the file to be used to update the EEPROM with?
Eaton shows a firmware file:
https://powerquality.eaton.com/Support/Software-Drivers/Downloads/5P-UPS-firmware.asp
However I'm not sure if it is for the questionable EEPROM and if so
maybe it is downlevel from the current reported firmware.
upsc
2017 Mar 27
0
Fatal EEPROM fault!
..., and looking at the link above,
the latest FW is "02.12.0025".
This FW upgrade may fix the EEPROM fault too, but it's not yet confirmed.
Please update me if you go through this upgrade.
Thanks and cheers,
Arno
--
Eaton Data Center Automation Solutions - Opensource Leader -
http://42ity.org
NUT (Network UPS Tools) Project Leader - http://www.networkupstools.org
Debian Developer - http://www.debian.org
Free Software Developer - http://arnaud.quette.fr
-------------- next part --------------
An HTML attachment was scrubbed...
URL: <http://lists.alioth.debian.org/pipermail/nut-ups...
2017 Mar 27
1
Fatal EEPROM fault!
On Mon, Mar 27, 2017 at 3:04 AM, Arnaud Quette <arnaud.quette at gmail.com> wrote:
> as per confirmation from Eaton support team, and looking at the link above,
> the latest FW is "02.12.0025".
Hi Arno,
According to that link, unless I'm missing something, as the 5P2200RT
is a 2U sized unit (2 rack spaces) the proper firmware should be
"03.00.0000". Firmware
2017 Mar 28
0
Eaton 1500 USB constant disconnections
...uld you please:
- confirm back that there is indeed a SW communication setup (NUT or UPower
for example),
- send me back the upsc output for this unit, including the serial number
and firmware revision
thanks and regards,
Arno
--
Eaton Data Center Automation Solutions - Opensource Leader -
http://42ity.org
NUT (Network UPS Tools) Project Leader - http://www.networkupstools.org
Debian Developer - http://www.debian.org
Free Software Developer - http://arnaud.quette.fr
-------------- next part --------------
An HTML attachment was scrubbed...
URL: <http://lists.alioth.debian.org/pipermail/nut-ups...
battery not installed, but battery still 100% and NUT 2.7.2-4 does not catch this and report a error
2017 Apr 04
0
battery not installed, but battery still 100% and NUT 2.7.2-4 does not catch this and report a error
...ify type> "ALARM" to upsmon (and its .conf), and
have it processing like other notifications?
That would mean to you can have WALL / SYSLOG notifications, along with
EXEC reaction if NOTIFYCMD is set.
cheers,
Arno
--
Eaton Data Center Automation Solutions - Opensource Leader -
http://42ity.org
NUT (Network UPS Tools) Project Leader - http://www.networkupstools.org
Debian Developer - http://www.debian.org
Free Software Developer - http://arnaud.quette.fr
-------------- next part --------------
An HTML attachment was scrubbed...
URL: <http://lists.alioth.debian.org/pipermail/nut-ups...
2017 Feb 17
0
EATON 9SX not display battery.charge
...ything is available here (for Windows only though): h
ttp://powerquality.eaton.com/Support/Software-Drivers/Downloads/9SX-UPS-firmware.asp
I hope the above information will help you in solving your issue.
Best regards,
Arnaud
--
Eaton Data Center Automation Solutions - Opensource Leader -
http://42ity.org
NUT (Network UPS Tools) Project Leader - http://www.networkupstools.org
Debian Developer - http://www.debian.org
Free Software Developer - http://arnaud.quette.fr
-------------- next part --------------
An HTML attachment was scrubbed...
URL: <http://lists.alioth.debian.org/pipermail/nut-ups...
2017 Mar 29
0
upsd/upsc, LISTEN and hostname resolution in master/slave
...CCEPT / REJECT) to refine the job, but that's really a
firewall job ;)
So another approach is to "LISTEN 0.0.0.0" (i.e. everything) and use your
firewall to restrict INPUT interfaces.
Hope it helps,
cheers,
Arno
--
Eaton Data Center Automation Solutions - Opensource Leader -
http://42ity.org
NUT (Network UPS Tools) Project Leader - http://www.networkupstools.org
Debian Developer - http://www.debian.org
Free Software Developer - http://arnaud.quette.fr
-------------- next part --------------
An HTML attachment was scrubbed...
URL: <http://lists.alioth.debian.org/pipermail/nut-ups...
2017 May 24
2
NUT namespace: RFC for new variable addition
...ces (1 and 2), I'd like to
add a new variable: "input.phase.shift"
Details and implementation can be found on:
https://github.com/networkupstools/nut/pull/433
Comments and feedback warmly welcome.
cheers,
Arno
--
Eaton Data Center Automation Solutions - Opensource Leader -
http://42ity.org
NUT (Network UPS Tools) Project Leader - http://www.networkupstools.org
Debian Developer - http://www.debian.org
Free Software Developer - http://arnaud.quette.fr
-------------- next part --------------
An HTML attachment was scrubbed...
URL: <http://lists.alioth.debian.org/pipermail/nut-ups...