2018 Sep 04
2
NUT messes up UPS after mains power is restored
...ted :)
>
Unfortunately, electric utilities are not always so polite. They have a
habit of restoring power at the most inopportune times.
-------------- next part --------------
An HTML attachment was scrubbed...
URL: <http://alioth-lists.debian.net/pipermail/nut-upsuser/attachments/20180904/25cebb1a/attachment.html>
2018 Sep 03
2
NUT messes up UPS after mains power is restored
Hi Charles,
Ok. I'm testing NUT now with only pfsense running as the master and no slaves. I'm noticing a very strange behavior that totally doesn't make sense to me. So here's what I did (in chronological order):
1. Set override.battery.charge.warning to 55 and override.battery.charge.low to 50.
2. I started with a full charge battery and unplugged the UPS from the mains.