Displaying 5 results from an estimated 5 matches for "008500d1".
2017 May 11
4
APC Back-UPS XS 1500G says "No battery"
I have a new-ish APC Back-UPS XS 1500G connected via USB. It's giving me
a "ups.alarm: No battery installed!" error. I also installed and
configured apcupsd to give that a try and it's giving me the same error.
I suspect this is a driver problem because while NUT claims the battery
isn't plugged in, it's giving me battery runtime/charge info. Both can't
be valid
2017 May 12
0
APC Back-UPS XS 1500G says "No battery"
...;
This seems to be the source of the "no battery" alarm:
> 0.571436 hid_lookup_path: 00840004 -> UPS
> 0.571438 hid_lookup_path: 00840024 -> PowerSummary
> 0.571440 hid_lookup_path: 00840002 -> PresentStatus
> 0.571443 hid_lookup_path: 008500d1 -> BatteryPresent
> 0.571446 Path: UPS.PowerSummary.PresentStatus.BatteryPresent, Type: Input, ReportID: 0x16, Offset: 3, Size: 1, Value: 0
> 0.571449 Report[buf]: (5 bytes) => 16 04 00 00 00
> 0.571451 PhyMax = 0, PhyMin = 0, LogMax = 1, LogMin = 0
> 0...
2014 Oct 10
1
Return on experience with an Emerson/Liebert GXT3
...8215??? PhyMax = 0, PhyMin = 0, LogMax = 1, LogMin = 0
>???? 0.428240??? Unit = 00000000, UnitExp = 0
>???? 0.428264??? Exponent = 0
>???? 0.428290??? hid_lookup_path: 00840004 -> UPS
>???? 0.428316??? hid_lookup_path: 00840024 -> PowerSummary
>???? 0.428344??? hid_lookup_path: 008500d1 -> BatteryPresent
>???? 0.428373??? Path: UPS.PowerSummary.BatteryPresent, Type: Input, ReportID: 0x0c, Offset: 4, Size: 1, Value: 0
>
Yes the presence of the battery isn't reported as i expected.
>
>>>> (4) would it be useful to add missing items to the driver's...
2014 Oct 06
1
Return on experience with an Emerson/Liebert GXT3
Hi
On 10/03/2014 03:42 PM, Charles Lepple wrote:> On Oct 3, 2014, at 7:50 AM, paul.chavent at fnac.net wrote:
>
>
> This is what I was referring to (from the belkin-hid log):
>
>???? 1.325782??? Report[buf]: (5 bytes) => 05 53 00 48 00
>???? 1.325799??? Path: UPS.PowerSummary.ConfigVoltage, Type: Feature, ReportID: 0x05, Offset: 16, Size: 16, Value: 0
>????
2009 Mar 13
7
Weird Load and Battery Temp Readings
I've acquired and installed NUT 2.4.1 on a D-Link DNS323 NAS. With
exception of Load and Battery Temp readings all works well. A upsc
ups at localhost command returns;
battery.charge: 100
battery.charge.low: 10
battery.charge.warning: 50
battery.date: 2001/09/25
battery.mfr.date: 2008/06/05
battery.runtime: 2122
battery.runtime.low: 120
battery.temperature: 3022999999999998800
battery.type: